Nebraska Administrative Code
Topic - FIRE MARSHAL, STATE
Title 159 - UNDERGROUND STORAGE TANKS
Chapter 7 - RELEASE DETECTION REQUIREMENTS
Section 159-7-001 - GENERAL REQUIREMENTS FOR ALL UST SYSTEMS
Universal Citation: 159 NE Admin Rules and Regs ch 7 ยง 001
Current through September 17, 2024
The requirements of 40 CFR 280.40 as it existed on July 15, 2015 are adopted and incorporated and by reference.
001.01 UST systems larger than 1,100 gallons used to store heating oil are excluded for purposes of all release detection on tanks required in this chapter except that they must perform the manual tank gauging procedures in 40 CFR 280.43(b) on a monthly basis from April 1 to November 1.
Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.