Nebraska Administrative Code
Topic - FIRE MARSHAL, STATE
Title 159 - UNDERGROUND STORAGE TANKS
Chapter 6 - GENERAL OPERATING REQUIREMENTS FOR EXISTING UST SYSTEMS
Section 159-6-002 - OPERATION AND MAINTENANCE OF CATHODIC PROTECTION

Current through September 17, 2024

The requirements of 40 CFR 280.31 as they existed on July 15, 2015 are adopted and incorporated by reference.

002.01A. Frequency. All cathodic protection systems must be tested within 6 months of installation; and

002.01A1. Impressed current cathodic protection systems will be tested annually thereafter; and

002.01A2. Galvanic or sacrificial anode cathodic protection systems will be tested at least every 3 years thereafter.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.