Nebraska Administrative Code
Topic - ENVIRONMENT AND ENERGY
Title 103 - NEBRASKA ADMINISTRATIVE CODE
Chapter 1 - Construction of State-Funded Buildings
Section 103-1-003 - Standard Design Conditions

Current through March 20, 2024

The following values may be entered in IECC Table 302.1 and used to determine compliance of subject buildings to be constructed anywhere in Nebraska:

Winter, Design Dry-bulb Temperature = -4°F

Summer, Design Dry-bulb Temperature = 92°F

Summer, Design Wet-bulb Temperature = 69°F

Degree days, heating (65° base) = 6500

Degree days, cooling (65° base) = 1000

Climate zone = 5

Interior Design Temperatures: Maximum of 72° (22° C) for heating and minimum of 75° (24°C) for cooling.

Use of these standard conditions for compliance determination does not relieve the designer of responsibility to size equipment correctly. The agency or designer may chose to use actual, historical weather data for the intended building site rather than these standard values.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.