Nebraska Administrative Code
Topic - AGRICULTURE, DEPARTMENT OF
Title 27 - DEPARTMENT OF AGRICULTURE, DIVISION OF WEIGHTS AND MEASURES
Chapter 10 - WEIGHTS AND MEASURES REGULATIONS
Section 27-10-003 - Scales
Universal Citation: 27 NE Admin Rules and Regs ch 10 ยง 003
Current through September 17, 2024
003.01 Scale owners will comply with the Act, maintain in their possession the manufacturer's plans for their scales and meet all of the manufacturer's specifications including those for installation. Failure to comply or to correct any installation characteristic adversely affecting performance subjects a scale to a stop-use, hold or removal order.
003.02 A suitable foundation includes:
003.02A An adequate bearing area
stabilized at the desired grade (elevation) to support the load as specified by
the scale manufacturer and if not specified, a bearing area supporting at least
3,000 pounds per square foot with the scale owner responsible for determining
whether or not soil characteristics are appropriate for a particular design,
and if not, for design modifications to suit the existing soil
conditions;
003.02B Installation
that supports the combined loads applied by the weight of the scale, the
weighbridge, and the maximum anticipated load on the scale distributing loads
evenly over the underlying ground so any settlement of the structure will be
minimized and uniform throughout the structure and reinforced concrete poured
to the depth of the local frost line of not less than four feet, if piers are
listed in the manufacturer's specifications;
003.02C End walls of monolithic construction
with the end piers or foundation and pit type scales with internal piers of
monolithic construction with the pit sidewalls; and
003.02D Clearance (the distance measured from
the bottom of the weighbridge main beams or supporting structure to the bottom
of the pit or the top of the cleaning slab) on all scales not less than the
scale manufacturer's specifications.
003.03 Appropriate floors and slabs are constructed as follows:
003.03A A pit floor,
if installed, made of reinforced concrete sloping to a drain, a sump, ' or
both, located in close proximity to the entrance of the pit keeping the scale
pit clean and dry at all times;
003.03B A pitless or self-contained scale
with a concrete or asphalt slab four inches thick below the weighbridge that is
sloped to provide drainage and aid in cleaning and meet the scale
manufacturer's specifications;
003.03C End walls and sidewalls for all
vehicle, axle load, livestock and railroad track scales constructed in
accordance with the Act and the manufacturer's specifications; and
003.03D Approaches constructed in accordance
with the Act and the manufacturer's specifications. Scales installed in any one
location for a period of six months or more will have not less than 10 ft. of
any approach adjacent to the platform constructed of concrete or similar
durable material to ensure that this portion remains smooth and level and in
the same plane as the platform; however, grating of sufficient strength to
withstand all loads equal to the concentrated load capacity of the scale may be
installed in this portion.
Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.