Administrative Rules of Montana
Department 4 - AGRICULTURE
Chapter 4.12 - AGRICULTURAL SCIENCES DIVISION
Subchapter 4.12.7 - Anhydrous Ammonia Rules
Rule 4.12.712 - FILLINGS DENSITIES

Universal Citation: MT Admin Rules 4.12.712

Current through Register Vol. 6, March 22, 2024

(1) Filling density shall be limited to 85 percent capacity by volume at 60 degrees F.

(2) The filling densities for nonrefrigerated containers by weight shall not exceed the following:

Aboveground Underground

(a) Uninsulated 56% 58%

(b) Insulated 57%

(c) Containers regulated by department of transportation shall be filled in accordance with Hazardous Materials Transportation Regulations (Subch. C, ARM 171.6).

(3) The filling density for refrigerated storage tanks shall be such that the tanks will not be liquid full at a liquid temperature corresponding to the vapor pressure at the start-to-discharge pressure setting of the safety relief valve.

Sec. 80-10-503, MCA; IMP, Sec. 80-10-503, MCA;

Disclaimer: These regulations may not be the most recent version. Montana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.