Rule 37.106.2163 - SECURED UNITS
Current through Register Vol. 18, September 20, 2024
(1) A secured unit within a facility shall have a written policy outlining resident admission criteria, transfer criteria and discharge criteria for the secured unit.
(2) Provisions should be made for secured unit residents to access large group activities when provided by the facility, e.g., holiday activities, etc. except as contraindicated by factors identified within their individual treatment plans.
(3) A secured unit within a facility is considered a separate unit. A staff station shall be located within the secured unit. The station shall provide at a minimum the following:
(4) The nurse/staff call system for a secured unit within a facility shall report to the unit nurse/staff station. The call system may also annunciate the call at another location, such as a main nurse station.
(5) A secured unit within a facility shall provide for a nourishment station. The nourishment station shall contain a work counter, refrigerator, storage cabinets and a sink for serving nourishments between meals. Ice for patient consumption should be provided by icemaker-dispenser units. The nourishment station should include space for trays and dishes used for nonscheduled meal service. Hand washing facilities shall be in or immediately accessible from the nourishment station.
(6) Dining, activities and day space must be provided at a ratio of 30 square feet per resident, with at least 14 square feet dedicated to the dining space.
(7) Resident rooms must be at a ratio of 100 square feet for single bedrooms and 80 square feet for multiple bedrooms. The room square footage should not include bathrooms, door swings, alcoves or vestibules. No more than four residents shall reside in a single room, except in new construction which limits single rooms to two residents.
(8) Each resident must have access to a toilet without requiring them to enter the corridor except as contraindicated by factors identified within their individual treatment plans.
(9) A secured unit within a facility shall comply with the following requirements for special locking arrangements. In buildings protected throughout by an approved supervised automatic fire detection system or approved supervised automatic sprinkler system, the doors in low and ordinary hazard areas may be equipped with approved, listed, locking devices which shall:
Sec. 50-5-103 and 50-5-238, MCA; IMP, Sec. 53-5-103, 50-5-201 and 50-5-238, MCA;