Rule 24.321.312 - STORAGE TANKS

Universal Citation: MT Admin Rules 24.321.312

Current through Register Vol. 6, March 22, 2024

(1) Propane tanks and other flammable or combustible liquids storage shall be buried underground. If soil or subsoil conditions prohibit complete burial, then tanks shall be partially covered by at least one foot of earth, sand, or other noncombustible material.

(2) Other installation methods such as installation in vaults or other protective methods that comply with NFPA 30 and NFPA 58 standards may be used in lieu of burial.

(3) Structures not located in a designated WUI may have storage tanks installed above ground, so long as they conform to the NFPA 58 standard and be located at least 30 feet from any structure.

50-60-901, MCA; IMP, 76-3-504, MCA;

Disclaimer: These regulations may not be the most recent version. Montana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.