Chapter 17.56 - UNDERGROUND STORAGE TANKS PETROLEUM AND CHEMICAL SUBSTANCES
Subchapter 17.56.2 - UST Systems: Design, Construction, and Installation
Rule 17.56.203 - ADDITIONAL PERFORMANCE STANDARDS FOR NEW UNDERGROUND PIPING CONNECTED TO ABOVEGROUND TANKS OR TO UNDERGROUND TANKS WITH A CAPACITY OF 660 GALLONS OR LESS USED TO STORE HEATING OIL

Universal Citation: MT Admin Rules 17.56.203

Current through Register Vol. 6, March 22, 2024

(1) Primary underground piping connected to above ground tanks or to underground tanks with a capacity of 660 gallons or less used exclusively to store heating oil for consumptive use on the premises where stored may be constructed of copper provided that the piping is enclosed in secondary containment consistent with these rules.

(2) In addition to cathodically protected steel or non-metallic pipe listed for use with petroleum products and/or motor fuels, schedule 40 or greater PVC pipe and fittings may be used to provide secondary containment for heating oil tank systems subject to this rule provided that only adhesives resistant to petroleum products are used to bond PVC joints.

(3) If liquid or vapor sensors are not used to monitor the interstitial space for a release, the piping system must be installed so that any liquid released into the interstitial space will not move more than 20 feet before being visually detected in a sump or standpipe.

75-11-302, 75-11-505, MCA; IMP, 75-11-302, 75-11-505, MCA;

Disclaimer: These regulations may not be the most recent version. Montana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.