Administrative Rules of Montana
Department 17 - ENVIRONMENTAL QUALITY
Chapter 17.38 - PUBLIC WATER AND SEWAGE SYSTEM REQUIREMENTS
Subchapter 17.38.3 - Cross-Connections in Drinking Water Supplies
Rule 17.38.310 - VOLUNTARY CROSS-CONNECTION CONTROL PROGRAMS: APPLICATION REQUIREMENTS
Universal Citation: MT Admin Rules 17.38.310
Current through Register Vol. 18, September 20, 2024
(1) To obtain approval of a voluntary cross-connection control program, an owner or operator of a public water supply system shall file an application with the department.
(2) The application must be accompanied by a copy of the local ordinances or plan of operations that describes the methods for implementing the cross-connection control program. The local ordinances or plan of operations must include the following:
(a) a
statement defining the responsibilities of the public water supplier and the
responsibilities of the consumer regarding implementation of the program;
(b) a requirement for a survey to be conducted by
the owner or operator of a public water supply system for the purpose of identifying
locations where cross-connections are likely to occur and evaluating the degree of
hazard at each location;
(c) a
requirement to eliminate cross-connections and hazards in compliance with ARM
17.38.305 on a priority basis beginning
with those identified as having the highest degree of hazard. A health hazard must
be assigned a higher degree of risk than all non-health hazards;
(d) a description of the procedures and criteria
that the public water supplier must or will use to evaluate the degree of hazard
represented by a cross-connection. The procedures and criteria must, at a minimum,
be consistent with the procedures and criteria specified in the "Manual of
Cross-Connection Control", incorporated by reference in ARM
17.38.302;
(e) the method for identifying the appropriate
backflow prevention assembly or device for a specific degree of hazard. The
methodology must be in accordance with the "Manual of Cross-Connection Control"
incorporated by reference in ARM 17.38.302, or as described in ARM
17.38.305(2);
(f) a requirement for the installation of backflow
prevention assemblies or devices where cross-connections identified in the survey
cannot be practically eliminated;
(g) a
provision for maintaining permanent records of the locations and types of backflow
prevention assemblies or devices installed in the public water supply system and a
provision requiring records regarding the inspection and testing of these backflow
prevention assemblies or devices; and
(h) a written procedure that will be used to
inspect and test a backflow prevention assembly or device. The procedures must
provide that a certified backflow prevention assembly tester, as defined in this
subchapter, will be used to conduct the inspection and testing.
AUTH: 75-6-104, MCA; IMP: 75-6-104, MCA
Disclaimer: These regulations may not be the most recent version. Montana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.