Administrative Rules of Montana
Department 17 - ENVIRONMENTAL QUALITY
Chapter 17.38 - PUBLIC WATER AND SEWAGE SYSTEM REQUIREMENTS
Subchapter 17.38.3 - Cross-Connections in Drinking Water Supplies
Rule 17.38.310 - VOLUNTARY CROSS-CONNECTION CONTROL PROGRAMS: APPLICATION REQUIREMENTS

Universal Citation: MT Admin Rules 17.38.310

Current through Register Vol. 18, September 20, 2024

(1) To obtain approval of a voluntary cross-connection control program, an owner or operator of a public water supply system shall file an application with the department.

(2) The application must be accompanied by a copy of the local ordinances or plan of operations that describes the methods for implementing the cross-connection control program. The local ordinances or plan of operations must include the following:

(a) a statement defining the responsibilities of the public water supplier and the responsibilities of the consumer regarding implementation of the program;

(b) a requirement for a survey to be conducted by the owner or operator of a public water supply system for the purpose of identifying locations where cross-connections are likely to occur and evaluating the degree of hazard at each location;

(c) a requirement to eliminate cross-connections and hazards in compliance with ARM 17.38.305 on a priority basis beginning with those identified as having the highest degree of hazard. A health hazard must be assigned a higher degree of risk than all non-health hazards;

(d) a description of the procedures and criteria that the public water supplier must or will use to evaluate the degree of hazard represented by a cross-connection. The procedures and criteria must, at a minimum, be consistent with the procedures and criteria specified in the "Manual of Cross-Connection Control", incorporated by reference in ARM 17.38.302;

(e) the method for identifying the appropriate backflow prevention assembly or device for a specific degree of hazard. The methodology must be in accordance with the "Manual of Cross-Connection Control" incorporated by reference in ARM 17.38.302, or as described in ARM 17.38.305(2);

(f) a requirement for the installation of backflow prevention assemblies or devices where cross-connections identified in the survey cannot be practically eliminated;

(g) a provision for maintaining permanent records of the locations and types of backflow prevention assemblies or devices installed in the public water supply system and a provision requiring records regarding the inspection and testing of these backflow prevention assemblies or devices; and

(h) a written procedure that will be used to inspect and test a backflow prevention assembly or device. The procedures must provide that a certified backflow prevention assembly tester, as defined in this subchapter, will be used to conduct the inspection and testing.

AUTH: 75-6-104, MCA; IMP: 75-6-104, MCA

Disclaimer: These regulations may not be the most recent version. Montana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.