Administrative Rules of Montana
Department 17 - ENVIRONMENTAL QUALITY
Chapter 17.38 - PUBLIC WATER AND SEWAGE SYSTEM REQUIREMENTS
Subchapter 17.38.3 - Cross-Connections in Drinking Water Supplies
Rule 17.38.305 - CROSS-CONNECTIONS: REGULATORY REQUIREMENTS

Universal Citation: MT Admin Rules 17.38.305

Current through Register Vol. 18, September 20, 2024

(1) A cross-connection on a public water supply system must be eliminated by the disconnection of the cross-connection whenever reasonably practicable. Whenever elimination of a cross-connection is not reasonably practicable and the cross-connection creates a health or non-health hazard, the hazard must be eliminated by the insertion into the piping of an approved backflow prevention assembly or device in accordance with (2).

(2) For the cross-connections identified below, the following types of approved backflow prevention assemblies or devices must be used:

(a) A health hazard created by a cross-connection that may be subject to back pressure must be eliminated by an approved reduced pressure principle backflow prevention assembly (RP) or an air-gap.

(b) A health hazard created by a cross-connection that may be subject to back siphonage, but not subject to back pressure, must be eliminated by an approved air-gap, pressure vacuum breaker assembly (PVB), spill-resistant pressure vacuum breaker assembly (SVB), atmospheric vacuum breaker (AVB), or a reduced pressure principle backflow prevention assembly (RP).

(c) A non-health hazard created by a cross-connection that may be subject to back pressure and back siphonage must be eliminated, at a minimum, by an approved double check valve assembly (DC). This cross-connection condition may also be eliminated by an air-gap or by an approved reduced pressure principle backflow prevention assembly (RP).

(d) A non-health hazard created by a cross-connection that may be subject to back siphonage, but is not subject to back pressure, must be eliminated, at a minimum, by an approved double check valve assembly (DC), pressure vacuum breaker assembly (PVB), spill-resistant pressure vacuum breaker assembly (SVB), or an atmospheric vacuum breaker (AVB). This cross-connection condition may also be eliminated by an air-gap or by an approved reduced pressure principle backflow prevention assembly (RP).

(3) Backflow prevention assemblies and devices must be approved by the department.

(4) A backflow prevention assembly or device must be installed and maintained, at a minimum, in accordance with the manufacturer's specifications.

(5) This rule applies to piping between water systems outside of any building and to piping within any building, including cross-connections in plumbing systems.

(6) The department may not approve a plan for the construction of a public water supply system containing provisions for cross-connection unless provisions for the protection of the public water supply are demonstrated in the plan.

AUTH: 75-6-104, MCA; IMP: 75-6-104, MCA

Disclaimer: These regulations may not be the most recent version. Montana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.