Administrative Rules of Montana
Department 17 - ENVIRONMENTAL QUALITY
Chapter 17.35 - VESSEL PUMPOUT FACILITIES
Rule 17.35.106 - HOLDING TANK
Universal Citation: MT Admin Rules 17.35.106
Current through Register Vol. 6, March 22, 2024
(1) Holding tanks should meet the requirements of Department Circular DEQ-4, Subchapter 8.1, except where they conflict with this chapter.
(2) Vessel pumpout holding tanks should be sized to meet the requirements of Table 1 for the volume of sewage generated and the frequency of removal of material from the holding tank.
Table 1
Total Number of Boats Serviced with Holding Tank Between Licensed Septic Pumper Servicings |
Minimum Holding Tank Volume (Gallons) |
1-20 |
500 |
21-40 |
600 |
41-60 |
900 |
61-80 |
1200 |
81-100 |
1500 |
100+ |
2000 |
AUTH: 23-2-522, MCA; IMP: 23-2-522, MCA
Disclaimer: These regulations may not be the most recent version. Montana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.