Current through Register Vol. 49, No. 18, September 16, 2024
PURPOSE: This rule establishes fire safety and
emergency preparedness standards for residential care facilities and assisted
living facilities.
PUBLISHER'S NOTE: The secretary of state has
determined that the publication of the entire text of the material which is
incorporated by reference as a portion of this rule would be unduly cumbersome
or expensive. This material as incorporated by reference in this rule shall be
maintained by the agency at its headquarters and shall be made available to the
public for inspection and copying at no more than the actual cost of
reproduction. This note applies only to the reference material. The entire text
of the rule is printed here.
AGENCY NOTE: All rules relating to long-term care
facilities licensed by the Department of Health and Senior Services are
followed by a Roman Numeral notation which refers to the class (either class I,
II, or III) of standard as designated in section
198.085,
RSMo 2000.
(1) Definitions.
For the purpose of this rule, the following definitions shall apply:
(A) Accessible spaces-shall include all
rooms, halls, storage areas, basements, attics, lofts, closets, elevator
shafts, enclosed stairways, dumbwaiter shafts, and chutes;
(B) Area of refuge-a space located in or
immediately adjacent to a path of travel leading to an exit that is protected
from the effects of fire, either by means of separation from other spaces in
the same building or its location, permitting a delay in evacuation. An area of
refuge may be temporarily used as a staging area that provides some relative
safety to its occupants while potential emergencies are assessed, decisions are
made, and, if applicable, evacuation has begun;
(C) Major renovation-shall include the
following:
1. Addition of any room(s),
accessible by residents, that either exceeds fifty percent (50%) of the total
square footage of the facility or exceeds four thousand five hundred (4,500)
square feet;
2. Repairs,
remodeling, or renovations that involve structural changes to more than fifty
percent (50%) of the building;
3.
Repairs, remodeling, or renovations that involve structural changes to more
than four thousand five hundred (4,500) square feet of a smoke section;
or
4. If the addition is separated
by two-(2-) hour fire-resistant construction, only the addition portion shall
meet the requirements for NFPA 13, 1999 edition, sprinkler system, unless the
facility is otherwise required to meet NFPA 13, 1999 edition;
(D) Fire-resistant
construction-type of construction in residential care and assisted living
facilities in which bearing walls, columns, and floors are of noncombustible
material in accordance with NFPA 101, 2000 edition. All load-bearing walls,
floors, and roofs shall have a minimum of a one- (1-) hour fire-resistant
rating; and
(E) Concealed
spaces-shall include areas within the building that cannot be occupied or used
for storage.
(2) General
Requirements.
(A) All National Fire
Protection Association (NFPA) codes and standards cited in this rule: NFPA 10,
Standard for Portable Fire Extinguishers, 1998 edition; NFPA
13R,
Installation of Sprinkler Systems, 1996 edition; NFPA 13,
Installation of Sprinkler Systems, 1976 edition; NFPA 13 or
NFPA 13R,
Standard for the Installation of Sprinkler Systems in
Residential Occupancies Up to and Including Four Stories in Height,
1999 edition; NFPA 13
, Standard for the Installation of Sprinkler
Systems, 1999 edition; NFPA 96,
Standard for Ventilation
Control and Fire Protection of Commercial Cooking Operations, 1998
edition; NFPA 101,
The Life Safety Code, 2000 edition; NFPA
72,
National Fire Alarm Code, 1999 edition; NFPA 72A,
Local Protective Signaling Systems, 1975 edition; NFPA 25,
Standard for the Inspection, Testing, and Maintenance of Water-Based
Fire Protection Systems, 1998 edition; and NFPA 101A,
Guide to
Alternative Approaches to Life Safety, 2001 edition, with regard to
the minimum fire safety standards for residential care facilities and assisted
living facilities are incorporated by reference in this rule and available for
purchase from the National Fire Protection Agency, 1 Batterymarch Park, Quincy,
MA 02269-9101;
www.nfpa.org; by
telephone at (617) 770-3000 or 1-800-344-3555. This rule does not incorporate
any subsequent amendments or additions to the materials listed above. This rule
does not prohibit facilities from complying with the standards set forth in
newer editions of the incorporated by reference material listed in this
subsection of this rule, if approved by the department.
(B) Facilities that were complying prior to
the effective date of this rule with prior editions of the NFPA provisions
referenced in this rule shall be permitted to continue to comply with the
earlier editions, as long as there is not an imminent danger to the health,
safety, or welfare of any resident or a substantial probability that death or
serious physical harm would result as determined by the department.
(C) All facilities shall notify the
department immediately after the emergency is addressed if there is a fire in
the facility or premises and shall submit a complete written fire report to the
department within seven (7) days of the fire, regardless of the size of the
fire or the loss involved. II/III
(D) The department shall have the right of
inspection of any portion of a building in which a licensed facility is located
unless the unlicensed portion is separated by two- (2-) hour fire-resistant
construction. No section of the building shall present a fire hazard.
I/II
(E) Following the discovery of
any fire, the facility shall monitor the area and/or the source of the fire for
a twenty-four- (24-) hour period. This monitoring shall include, at a minimum,
hourly visual checks of the area. These hourly visual checks shall be
documented. I/II
(F) The facility
shall maintain the exterior premises in a manner as to provide for fire safety.
II
(G) Residential care facilities
that accept deaf residents shall have appropriate assistive devices to enable
each deaf person to negotiate a path to safety, including, but not limited to,
visual or tactile alarm systems. II/III
(H) Facilities shall not use space under
stairways to store combustible materials. I/II
(3) Fire Extinguishers.
(A) Fire extinguishers shall be provided at a
minimum of one (1) per floor, so that there is no more than seventy-five feet
(75') travel distance from any point on that floor to an extinguisher.
I/II
(B) All new or replacement
portable fire extinguishers shall be ABC-rated extinguishers, in accordance
with the provisions of NFPA 10, 1998 edition. A K-rated extinguisher or its
equivalent shall be used in lieu of an ABC-rated extinguisher in the kitchen
cooking areas. II
(C) Fire
extinguishers shall have a rating of at least:
1. Ten pounds (10 lbs.), ABC-rated or the
equivalent, in or within fifteen feet (15') of hazardous areas as defined in
19 CSR
30-83.010; and
2. Five pounds (5 lbs.), ABC-rated or the
equivalent, in other areas. II
(D) All fire extinguishers shall bear the
label of the Underwriters' Laboratories (UL) or the Factory Mutual (FM)
Laboratories and shall be installed and maintained in accordance with NFPA 10,
1998 edition. This includes the documentation and dating of a monthly pressure
check. II/III
(4) Range
Hood Extinguishing Systems.
(A) In facilities
licensed on or before July 11, 1980, or in any facility with fewer than
twenty-one (21) beds, the kitchen shall provide either:
1. An approved automatic range hood
extinguishing system properly installed and maintained in accordance with NFPA
96, 1998 edition; or
2. A portable
fire extinguisher of at least ten pounds (10 lbs.) ABC-rated, or the
equivalent, in the kitchen area in accordance with NFPA 10, 1998 edition.
II/III
(B) In licensed
facilities with a total of twenty-one (21) or more licensed beds and whose
application was filed after July 11, 1980, and prior to October 1, 2000:
1. The kitchen shall be provided with a range
hood and an approved automatic range hood extinguishing system unless the
facility has an approved sprinkler system. Facilities with range hood systems
shall continue to maintain and test these systems; and
2. The extinguishing system shall be
installed, tested, and maintained in accordance with NFPA 96, 1998 edition.
II/III
(C) The range
hood and its extinguishing system shall be certified at least twice annually in
accordance with NFPA 96, 1998 edition. II/III
(5) Fire Drills and Emergency Preparedness.
(A) All facilities shall have a written plan
to meet potential emergencies or disasters and shall request consultation and
assistance annually from a local fire unit for review of fire and evacuation
plans. If the consultation cannot be obtained, the facility shall inform the
state fire marshal in writing and request assistance in review of the plan. An
up-to-date copy of the facility's entire plan shall be provided to the local
jurisdiction's emergency management director. II/III
(B) The plan shall include, but is not
limited to, the following:
1. A phased
response ranging from relocation of residents to an immediate area within the
facility; relocation to an area of refuge, if applicable; or to total building
evacuation. This phased response part of the plan shall be consistent with the
direction of the local fire unit or state fire marshal and appropriate for the
fire or emergency;
2. Written
instructions for evacuation of each floor including evacuation to areas of
refuge, if applicable, and a floor plan showing the location of exits, fire
alarm pull stations, fire extinguishers, and any areas of refuge;
3. Evacuating residents, if necessary, from
an area of refuge to a point of safety outside the building;
4. The location of any additional water
sources on the property such as cisterns, wells, lagoons, ponds, or
creeks;
5. Procedures for the
safety and comfort of residents evacuated;
6. Staffing assignments;
7. Instructions for staff to call the fire
department or other outside emergency services;
8. Instructions for staff to call alternative
resource(s) for housing residents, if necessary;
9. Administrative staff responsibilities;
and
10. Designation of a staff
member to be responsible for accounting for all residents' whereabouts.
II/III
(C) The written
plan shall be accessible at all times and an evacuation diagram shall be posted
on each floor in a conspicuous place so that employees and residents can become
familiar with the plan and routes to safety. II/III
(D) A minimum of twelve (12) fire drills
shall be conducted annually with at least one (1) every three (3) months on
each shift. At least four (4) of the required fire drills must be unannounced
to residents and staff, excluding staff who are assigned to evaluate staff and
resident response to the fire drill. The fire drills shall include a resident
evacuation at least once a year. II/III
(E) The facility shall keep a record of all
fire drills. The record shall include the time, date, personnel participating,
length of time to complete the fire drill, and a narrative notation of any
special problems. III
(F) The fire
alarm shall be activated during all fire drills unless the drill is conducted
between 9 p.m. and 6 a.m., when a facility-generated predetermined message is
acceptable in lieu of the audible and visual components of the fire alarm.
II/III
(6) Fire Safety
Training Requirements.
(A) The facility shall
ensure that fire safety training is provided to all employees:
1. During employee orientation;
2. At least every six (6) months;
and
3. When training needs are
identified as a result of fire drill evaluations. II/III
(B) The training shall include, but is not
limited to, the following:
1. Prevention of
fire ignition, detection of fire, and control of fire development;
2. Confinement of the effects of
fire;
3. Procedures for moving
residents to an area of refuge, if applicable;
4. Use of alarms;
5. Transmission of alarms to the fire
department;
6. Response to
alarms;
7. Isolation of
fire;
8. Evacuation of immediate
area and building;
9. Preparation
of floors and facility for evacuation; and
10. Use of the evacuation plan as required by
section (5) of this rule. II/III
(7) Exits, Stairways, and Fire Escapes.
(A) Each floor of a facility shall have at
least two (2) unobstructed exits remote from each other. I/II
1. For a facility whose plans were approved
on or before December 31, 1987, or a facility licensed for twenty (20) or fewer
beds, one (1) of the required exits from a multi-story facility shall be an
outside stairway or an enclosed stairway that is separated by one- (1-) hour
rated construction from each floor with an exit leading directly to the outside
at grade level. Existing plaster or gypsum board of at least one-half inch
(1/2") thickness may be considered equivalent to one- (1-) hour rated
construction. The other required exit may be an interior stairway leading
through corridors or passageways to outside or to a two- (2-) hour rated
horizontal exit as defined by paragraph 3.3.61 of the 2000 edition NFPA 101.
Neither of the required exits shall lead through a furnace or boiler room.
Neither of the required exits shall be through a resident's bedroom, unless the
bedroom door cannot be locked. I/II
2. For a facility whose plans were approved
after December 31, 1987, for more than twenty (20) beds, the required exits
shall be doors leading directly outside, one- (1-) hour enclosed stairs or
outside stairs or a two- (2-) hour rated horizontal exit as defined by
paragraph 3.3.61 of 2000 edition NFPA 101. The one- (1-) hour enclosed stairs
shall exit directly outside at grade. Access to these shall not be through a
resident bedroom or a hazardous area. I/II
3. Only one (1) of the required exits may be
a two- (2-) hour rated horizontal exit. I/II
(B) In facilities with plans approved after
December 31, 1987, doors to resident use rooms shall not be more than one
hundred feet (100') from an exit. In facilities equipped with a complete
sprinkler system in accordance with NFPA 13 or NFPA 13R, 1999 edition, the exit
distance may be increased to one hundred fifty feet (150'). Dead-end corridors
shall not exceed thirty feet (30') in length. II
(C) In residential care facilities and
facilities formerly licensed as residential care facilities II, floors housing
residents who require the use of a walker, wheelchair, or other assistive
devices or aids, or who are blind, must have two (2) accessible exits to grade
or such residents must be housed near accessible exits as specified in
19
CSR 30-86.042(33) for residential
care facilities and
19
CSR 30-86.043(31) for facilities
formerly licensed as residential care facilities II unless otherwise prohibited
by
19
CSR 30-86.045 or
19
CSR 30-86.047, facilities equipped with a complete
sprinkler system, in accordance with NFPA 13 or NFPA 13R, 1999 edition, with
sprinkler coverage in attics, and smoke partitions, as defined by subsection
(10)(I) of this rule, may house such residents on floors that do not have
accessible exits to grade if each required exit is equipped with an area of
refuge as defined and described in subsections (1)(B) and (7)(D) of this rule.
I/II
(D) An "area of refuge" shall
have-
1. An area separated by one- (1-) hour
rated smoke walls, from the remainder of the building. This area must have
direct access to the exit stairway or access the stair through a section of the
corridor that is separated by smoke walls from the remainder of the building.
This area may include no more than two (2) resident rooms;
2. A two- (2-) way communication or intercom
system with both visible and audible signals between the area of refuge and the
bottom landing of the exit stairway, attendants' work area, or other primary
location as designated in the written plan for fire drills and
evacuation;
3. Instructions on the
use of the area during emergency conditions that are located in the area of
refuge and conspicuously posted adjoining the communication or intercom
system;
4. A sign at the entrance
to the room that states "AREA OF REFUGE IN CASE OF FIRE" and displays the
international symbol of accessibility;
5. An entry or exit door that is at least a
one and three-fourths inch (1 3/4") solid core wood door or has a fire
protection rating of not less than twenty (20) minutes with smoke seals and
positive latching hardware. These doors shall not be lockable;
6. A sign conspicuously posted at the bottom
of the exit stairway with a diagram showing each location of the areas of
refuge;
7. Emergency lighting for
the area of refuge; and
8. The
total area of the areas of refuge on a floor shall equal at least twenty (20)
square feet for each resident who is blind or requires the use of a wheelchair
or walker housed on the floor. II
(E) If it is necessary to lock exit doors,
the locks shall not require the use of a key, tool, special knowledge, or
effort to unlock the door from inside the building. Only one (1) lock shall be
permitted on each door. Delayed egress locks complying with section 7.2.1.6.1
of the 2000 edition NFPA 101 shall be permitted, provided that not more than
one (1) such device is located in any egress path. Self-locking exit doors
shall be equipped with a hold-open device to permit staff to reenter the
building during the evacuation. I/II
(F) If it is necessary to lock resident room
doors, the locks shall not require the use of a key, tool, special knowledge,
or effort to unlock the door from inside the room. Only one (1) lock shall be
permitted on each door. Every resident room door shall be designed to allow the
door to be opened from the outside during an emergency when locked. The
facility shall ensure that facility staff have the means or mechanisms
necessary to open resident room doors in case of an emergency. I/II
(G) All stairways and corridors shall be
easily negotiable and shall be maintained free of obstructions. II
(H) Outside stairways shall be constructed to
support residents during evacuation and shall be continuous to the ground
level. Outside stairways shall not be equipped with a counter-balanced device.
They shall be protected from or cleared of ice or snow. II/III
(I) Facilities with three (3) or more floors
shall comply with the provisions of Chapter 320, RSMo which requires outside
stairways to be constructed of iron or steel. II
(J) Fire escapes constructed on or after
November 13, 1980, whether interior or exterior, shall be thirty-six inches
(36") wide, shall have eight-inch (8") maximum risers, nine-inch (9") minimum
tread, no winders, maximum height between landings of twelve feet (12'),
minimum dimensions of landings of forty-four inches (44"), landings at each
exit door, and handrails on both sides and be of sturdy construction, using at
least two-inch (2") lumber. Exit doors to these fire escapes shall be at least
thirty-six inches (36") wide and the door shall swing outward. II/III
(K) If a ramp is required to meet residents'
needs under
19
CSR 30-86.042, the ramp shall have a maximum slope of
one to twelve (1:12) leading to grade. II/III
(8) Exit Signs.
(A) Signs bearing the word EXIT in plain,
legible letters shall be placed at each required exit, except at doors directly
from rooms to exit passageways or corridors. Letters of all exit signs shall be
at least six inches (6") high and principle strokes three-fourths of an inch
(3/4") wide, except that letters of internally illuminated exit signs shall not
be less than four inches (4") high. II
(B) Directional indicators showing the
direction of travel shall be placed in corridors, passageways, or other
locations where the direction of travel to reach the nearest exit is not
apparent. II/III
(C) All required
exit signs and directional indicators shall be positioned so that both normal
and emergency lighting illuminates them. II/III
(9) Complete Fire Alarm Systems.
(A) All facilities shall have a complete fire
alarm system installed in accordance with NFPA 101, Section 18.3.4, 2000
edition. The complete fire alarm shall automatically transmit to the fire
department, dispatching agency, or central monitoring company. The complete
fire alarm system shall include visual signals and audible alarms that can be
heard throughout the building and a main panel that interconnects all
alarm-activating devices and audible signals. Manual pull stations shall be
installed at or near each required attendant's station and each required exit.
I/II
1. For facilities with a sprinkler
system in accordance with NFPA 13, 1999 edition, smoke detectors interconnected
to the complete fire alarm system shall be installed in all corridors and
spaces open to corridors. Smoke detectors shall be no more than thirty feet
(30') apart with no point on the ceiling more than twenty-one feet (21') from a
smoke detector. I/II
A. In facilities
licensed prior to November 13, 1980, smoke detectors located every fifty feet
(50') will be acceptable if the distance is within the manufacturer's
specifications. I/II
2.
For facilities with a sprinkler system in accordance with NFPA 13R, 1999
edition, smoke detectors interconnected to the complete fire alarm system shall
be installed in all corridors, spaces open to corridors, and in accessible
spaces not protected by the sprinkler system, as required by NFPA 72, 1999
edition. Smoke detectors shall be no more than thirty feet (30') apart with no
point on the ceiling more than twenty-one feet (21') from a smoke detector.
Smoke detectors shall not be installed in areas where environmental influences
may cause nuisance alarms. Such areas include, but are not limited to,
kitchens, laundries, bathrooms, mechanical air handling rooms, and attic
spaces. In these areas, heat detectors interconnected to the complete fire
alarm system shall be installed. Bathrooms not exceeding fifty-five (55) square
feet and clothes closets, linen closets, and pantries not exceeding twenty-four
(24) square feet are exempt from having any detection device if the walls and
ceilings are surfaced with limited-combustible or non-combustible material as
defined in NFPA 101, 2000 edition. Concealed spaces of non-combustible or
limited combustible construction are not required to have detection devices.
These spaces may have limited access but cannot be occupied or used for
storage. I/II
A. In facilities licensed prior
to November 13, 1980, smoke detectors located every fifty feet (50') will be
acceptable if the distance is within the manufacturer's specifications.
I/II
3. For facilities
that are not required to have a sprinkler system, smoke detectors
interconnected to the complete fire alarm system shall be installed in all
accessible spaces, as required by NFPA 72, 1999 edition, within the facility.
Smoke detectors shall be no more than thirty feet (30') apart with no point on
the ceiling more than twenty-one feet (21') from a smoke detector. Smoke
detectors shall not be installed in areas where environmental influences may
cause nuisance alarms. Such areas include, but are not limited to, kitchens,
laundries, bathrooms, mechanical air handling rooms, and attic spaces. In these
areas, heat detectors interconnected to the fire alarm system shall be
installed. Bathrooms not exceeding fifty-five (55) square feet and clothes
closets, linen closets, and pantries not exceeding twenty-four (24) square feet
are exempt from having any detection device if the walls and ceilings are
surfaced with limited-combustible or noncombustible material as defined in NFPA
101, 2000 edition. Concealed spaces of noncombustible or limited-combustible
construction are not required to have detection devices. These spaces may have
limited access but cannot be occupied or used for storage. I/II
A. In facilities licensed prior to November
13, 1980, smoke detectors located every fifty feet (50') will be acceptable if
the distance is within the manufacturer's specifications. I/II
(B) Facilities that are
required to install a sprinkler system in accordance with section (11) of this
rule shall comply with the following requirements:
1. Until the required sprinkler system is
installed, each resident room or any room designated for sleeping shall be
equipped with at least one (1) battery-powered smoke alarm installed, tested,
and maintained in accordance with manufacturer's specifications. In addition,
the facility shall be equipped with interconnected heat detectors installed,
tested, and maintained in accordance with NFPA 72, 1999 edition, with detectors
in all areas subject to nuisance alarms, including, but not limited to,
kitchens, laundries, bathrooms, mechanical air handling rooms, and attic
spaces. I/II
A. The facility shall maintain a
written record of the monthly testing and battery changes. The written records
shall be retained for one (1) year. I/II
B. Upon discovery of a fault with any
detector or alarm, the facility shall correct the fault. I/II
(C) All facilities
shall test and maintain the complete fire alarm system in accordance with NFPA
72, 1999 edition. I/II
(D) All
facilities shall have inspections and written certifications of the complete
fire alarm system completed by an approved qualified service representative in
accordance with NFPA 72, 1999 edition, at least annually. I/II
(E) Facilities shall test by activating the
complete fire alarm system at least once a month. I/II
(F) Facilities shall maintain a record of the
complete fire alarm tests, inspections, and certifications required by
subsections (9)(C) and (D) of this rule. III
(G) Upon discovery of a fault with the
complete fire alarm system, the facility shall correct the fault.
I/II
(H) When a complete fire alarm
system is to be out-of-service for more than four (4) hours in a twenty-four-
(24-) hour period, the facility shall immediately notify the department and the
local fire authority and implement an approved fire watch in accordance with
NFPA 101, 2000 edition, until the complete fire alarm system has returned to
full service. I/II
(I) The complete
fire alarm system shall be activated by all of the following: sprinkler system
flow alarm, smoke detectors, heat detectors, manual pull stations, and
activation of the rangehood extinguishment system. II/III
(10) Protection from Hazards.
(A) In assisted living facilities and
residential care facilities licensed on or after November 13, 1980, for more
than twelve (12) beds, hazardous areas shall be separated by construction of at
least a one- (1-) hour fire-resistant rating. In facilities equipped with a
complete fire alarm system, the one- (1-) hour fire separation is required only
for furnace or boiler rooms. Hazardous areas equipped with a complete sprinkler
system are not required to have this one- (1-) hour fire separation. Doors to
hazardous areas shall be self-closing and shall be kept closed unless an
electromagnetic hold-open device is used which is interconnected with the fire
alarm system. When the sprinkler option is chosen, the areas shall be separated
from other spaces by smoke-resistant partitions and doors. The doors shall be
self-closing or automatic-closing. Facilities formerly licensed as residential
care facility I or II, and existing prior to November 13, 1980, shall be exempt
from this requirement. II
(B) The
storage of unnecessary combustible materials in any part of a building in which
a licensed facility is located is prohibited. I/II
(C) Electric or gas clothes dryers shall be
vented to the outside. Lint traps shall be cleaned regularly to protect against
fire hazard. II/III
(D) In
facilities that are required to comply with the requirements of
19
CSR 30-86.043 and were formerly licensed as
residential care facilities II on or after November 13, 1980, each floor shall
be separated by construction of at least a one- (1-) hour fire-resistant
rating. Buildings equipped with a complete sprinkler system may have a nonrated
smoke separation barrier between floors. Doors between floors shall be a
minimum of one and three-fourths inches (1 3/4") thick and be solid core wood
doors or metal doors with an equivalent fire rating. II
(E) In facilities licensed prior to November
13, 1980, and multi-storied residential care facilities formerly licensed as
residential care facilities I licensed on or after November 13, 1980, there
shall be a smoke separation barrier between the floors of resident-use areas
and any floor below the resident-use area. This shall consist of a solid core
wood door or metal door with an equivalent fire rating at the top or the bottom
of the stairs. There shall not be a transom above the door that would permit
the passage of smoke. II
(F)
Atriums open between floors will be permitted if resident room corridors are
separated from the atrium by one- (1-) hour rated smoke walls. These corridors
must have access to at least one (1) of the required exits without traversing
any space opened to the atrium. II
(G) All doors providing separation between
floors shall have a self-closing device attached. If the doors are to be held
open, electromagnetic hold-open devices shall be used that are interconnected
with either an individual smoke detector or a complete fire alarm system.
II
(H) All facilities shall be
divided into at least two (2) smoke sections with each section not exceeding
one hundred fifty feet (150') in length or width. If the floor's dimensions do
not exceed seventy-five feet (75') in length or width, a division of the floor
into two (2) smoke sections will not be required. II
(I) In facilities whose plans were approved
or which were initially licensed after December 31, 1987, for more than twenty
(20) beds and all facilities licensed after August 28, 2007, each smoke section
shall be separated by one- (1-) hour fire-rated smoke partitions. The smoke
partitions shall be continuous from outside wall-to-outside wall and from
floor-to-floor or floor-to-roof deck. All doors in this wall shall be at least
twenty- (20-) minute fire-rated or its equivalent, self-closing, and may be
held open only if the door closes automatically upon activation of the complete
fire alarm system. II
(J) In all
facilities that were initially licensed on or prior to December 31, 1987, and
all facilities licensed for twenty (20) or fewer beds prior to August 28, 2007,
each smoke section shall be separated by a one-(1-) hour fire-rated smoke
partition that extends from the inside portion of an exterior wall to the
inside portion of an exterior wall and from the floor to the underside of the
floor or roof deck above, through any concealed spaces, such as those above
suspended ceilings, and through interstitial structural and mechanical spaces.
Smoke partitions shall be permitted to terminate at the underside of a
monolithic or suspending ceiling system where the following conditions are met:
The ceiling system forms a continuous membrane, a smoketight joint is provided
between the top of the smoke partition and the bottom of the suspended ceiling
and the space above the ceiling is not used as a plenum. Smoke partition doors
shall be at least twenty- (20-) minute fire-rated or its equivalent,
self-closing, and may be held open only if the door closes automatically upon
activation of the complete fire alarm system. II
(K) Facilities whose plans were approved or
which were initially licensed after December 31, 1987, for more than twenty
(20) beds which do not have a sprinkler system, shall have one- (1-) hour rated
corridor walls with one and three-quarters inch (1 3/4") solid core wood doors
or metal doors with an equivalent fire rating. II
(L) If two (2) or more levels of long-term
care or two (2) different businesses are located in the same building, the
entire building shall meet either the most strict construction and fire safety
standards for the combined facility or the facilities shall be separated from
the other(s) by two- (2-) hour fire-resistant construction. In buildings
equipped with a complete sprinkler system in accordance with NFPA 13 or NFPA
13R, 1999 edition, this separation may be rated at one (1) hour. II
(11) Sprinkler Systems.
(A) Facilities licensed on or after August
28, 2007, or any section of a facility in which a major renovation has been
completed on or after August 28, 2007, shall install and maintain a complete
sprinkler system in accordance with NFPA 13, 1999 edition. I/II
(B) Facilities that have a sprinkler system
installed prior to August 28, 2007, shall inspect, maintain, and test these
systems in accordance with the requirements that were in effect for such
facilities on August 27, 2007. I/II
(C) All residential care facilities, and
assisted living facilities that do not admit or retain a resident with a
physical, cognitive, or other impairment that prevents the individual from
safely evacuating the facility with minimal assistance, that were licensed
prior to August 28, 2007, with more than twenty (20) residents, and do not have
an approved sprinkler system in accordance with NFPA 13, 1999 edition, or NFPA
13R, 1999 edition, shall have until December 31, 2012, to install an approved
sprinkler system in accordance with NFPA 13 or 13R, 1999 edition. I/II
1. The department shall grant exceptions to
this requirement if the facility meets Chapter 33 of NFPA 101, 2000 edition,
and the evacuation capability of the facility meets the standards required in
NFPA 101A, Guide to Alternative Approaches to Life Safety, 2001 edition.
I/II
(D) Single-story
assisted living facilities that provide care to one (1) or more residents with
a physical, cognitive, or other impairment that prevents the individual from
safely evacuating the facility with minimal assistance shall install and
maintain an approved sprinkler system in accordance with NFPA 13R, 1999
edition. I/II
(E) Multi-level
assisted living facilities that provide care to one (1) or more residents with
a physical, cognitive, or other impairment that prevents the individual from
safely evacuating the facility with minimal assistance shall install and
maintain an approved sprinkler system in accordance with NFPA 13, 1999 edition.
I/II
(F) All facilities shall have
inspections and written certifications of the approved sprinkler system
completed by an approved qualified service representative in accordance with
NFPA 25, 1998 edition. The inspections shall be in accordance with the
provisions of NFPA 25, 1998 edition, with certification at least annually by a
qualified service representative. I/II
(G) When a sprinkler system is to be
out-of-service for more than four (4) hours in a twenty-four- (24-) hour
period, the facility shall immediately notify the department and implement an
approved fire watch in accordance with NFPA 101, 2000 edition, until the
sprinkler system has been returned to full service. I/II
(12) Emergency Lighting.
(A) Emergency lighting of sufficient
intensity shall be provided for exits, stairs, resident corridors, and required
attendants' station. II
(B) The
lighting shall be supplied by an emergency service, an automatic emergency
generator, or battery-operated lighting system. This emergency lighting system
shall be equipped with an automatic transfer switch. II
(C) If battery-powered lights are used, they
shall be capable of operating the light for at least one and one-half (1 1/2)
hours. II
(13) Interior
Finish and Furnishings.
(A) In a facility
licensed on or after November 13, 1980, for more than twelve (12) beds, wall
and ceiling surfaces of all occupied rooms and all exitways shall be classified
either Class A or B interior finish as defined in NFPA 101, 2000 edition.
II
(B) In facilities licensed prior
to November 13, 1980, all wall and ceiling surfaces shall be smooth and free of
highly combustible materials. II
(C) In facilities licensed for more than
twelve (12) beds, the new or replacement floor covering and carpeting in
buildings that do not have a sprinkler system shall be Class I in accordance
with NFPA 253, 2000 edition. II/III
(D) All curtains and drapes in a licensed
facility shall be certified or treated to be flame-resistant as defined in NFPA
101, 2000 edition. II
(14) Smoking.
(A) Smoking shall be permitted in designated
areas only. Areas where smoking is permitted shall be designated as such and
shall be supervised either directly or by a resident informing an employee of
the facility that the area is being used for smoking. II/III
(B) Ashtrays shall be made of noncombustible
material and safe design and shall be provided in all areas where smoking is
permitted. II/III
(C) The contents
of ashtrays shall be disposed of properly in receptacles made of
non-combustible material. II/III
(15) Trash and Rubbish Disposal.
(A) Only metal or UL- or FM-fire-resistant
rated wastebaskets shall be used for trash. II
(B) Trash shall be removed from the premises
as often as necessary to prevent fire hazards and public health nuisance.
II
(C) No trash shall be burned
within fifty feet (50') of any facility except in an approved incinerator.
I/II
(D) Trash may be burned only
in a masonry or metal container. II
(E) The container shall be equipped with a
metal cover with openings no larger than one-half inch (1/2") in size.
III
(16) Standards for
Designated Separated Areas.
(A) When a
resident resides among the entire general population of the facility, the
facility shall take necessary measures to provide such residents with the
opportunity to explore the facility and, if appropriate, its grounds. When a
resident resides within a designated, separated area that is secured by limited
access, the facility shall take necessary measures to provide such residents
with the opportunity to explore the separated area and, if appropriate, its
grounds. If enclosed or fenced courtyards are provided, residents shall have
reasonable access to such courtyards. Enclosed or fenced courtyards that are
accessible through a required exit door shall be large enough to provide an
area of refuge for fire safety at least thirty feet (30') from the building.
Enclosed or fenced courtyards that are accessible through a door other than a
required exit shall have no size requirements. II
(B) The facility shall provide freedom of
movement for the residents to common areas and to their personal spaces. The
facility shall not lock residents out of or inside their rooms. I/II
(C) The facility may allow resident room
doors to be locked providing the residents request to lock their doors. Any
lock on a resident room door shall not require the use of a key, tool, special
knowledge, or effort to lock or unlock the door from inside the resident's
room. Only one (1) lock shall be permitted on each door. The facility shall
ensure that facility staff has the means or mechanisms necessary to open
resident room doors in case of an emergency. I/II
(D) The facility may provide a designated,
separated area where residents, who are mentally incapable of negotiating a
pathway to safety, reside and receive services and which is secured by limited
access if the following conditions are met:
1. Dining rooms, living rooms, activity
rooms, and other such common areas shall be provided within the designated,
separated area. The total area for common areas within the designated,
separated area shall be equal to at least forty (40) square feet per resident;
II/III
2. Doors separating the
designated, separated area from the remainder of the facility or building shall
not be equipped with locks that require a key to open; I/II
3. If locking devices are used on exit doors
egressing the facility or on doors accessing the designated, separated area,
delayed egress magnetic locks shall be used. These delayed egress devices shall
comply with the following:
A. The lock must
unlock when the fire alarm is activated;
B. The lock must unlock when the power
fails;
C. The lock must unlock
within thirty (30) seconds after the release device has been pushed for at
least three (3) seconds, and an alarm must sound adjacent to the
door;
D. The lock must be manually
reset and cannot automatically reset; and
E. A sign shall be posted on the door that
reads: PUSH UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 30 SECONDS; and
I/II
4. The delayed
egress magnetic locks may also be released by a key pad located adjacent to the
door for routine use by staff. I/II
(17) Oxygen storage shall be in accordance
with NFPA 99, 1999 Edition. II/III
*Original authority: 198.073, RSMo 1979, amended 1984,
1992, 1999, 2006; 198.074, RSMo 2007; and 198.076, RSMo 1979, amended 1984,
2007.