Current through Register Vol. 49, No. 18, September 16, 2024
PURPOSE: This rule establishes the fire safety
requirements for family day care homes.
(1) The following definitions shall be used
in interpreting this rule:
(A) Alterations
are changes made to the structure or floor plan of the facility by removing or
adding walls and doors or adding space;
(B) Dead-end is a corridor or hallway with no
exit at the end that causes occupants to retrace their path to reach an
exit;
(C) Exit is the portion of a
means of egress that is separated from all other areas of the building or
structure by construction or equipment required to provide a protected way of
travel to the exit discharge. Exits include exterior exit doors, exit
passageways, horizontal exits, separated exit stairs, and separated exit
ramps;
(D) Exit access is the
portion of a means of egress that leads to an exit;
(E) Exit discharge is the portion of a means
of egress between the termination of an exit and a public way;
(F) Fire barrier is a structural element,
either vertical or horizontal, such as a wall or floor assembly that is
designed and constructed with a specified fire resistance rating to limit the
spread of fire and restrict the movement of smoke. Such barriers may have
protected openings;
(G) Fire
resistance rating is the length of time in minutes or hours that materials or
structural elements can withstand fire exposure;
(H) Flame resistant material is the property
of material or their structural elements that prevents or retards the passage
of excessive heat, hot gases, or flames under the conditions in which they are
used;
(I) Flame retardant is a
chemical applied to material or other substance that is designed to retard
ignition or the spread of fire;
(J)
Interior finish includes the interior wall and ceiling finish, and interior
floor finish;
(K) Level exit
discharge is a horizontal plane that is located from the point at which an exit
terminates and the exit discharge begins. The horizontal plane shall not vary
more than two inches (2") in rise or fall;
(L) Level is the portion of a building
included between the upper surface of a floor and the ceiling above it, or any
upper surface of a floor and the ceiling above it that is separated by more
than five (5) steps on a stairway;
(M) Means of egress is a continuous and
unobstructed way of travel from any point in a building or structure to a
public way. A means of egress consists of three (3) distinct parts: the exit
access, the exit, and the exit discharge;
(N) Mixed occupancy is when a family day care
home is located in the same building or structure as another occupancy. This
may include a business or place of assembly;
(O) Public way is an area such as a street or
sidewalk that is open to the outside and is used by the public for moving from
one location to another;
(P) Remote
exit or means of egress is when two (2) exits or two (2) exit access doors are
required. Each exit or exit access door shall be placed at a distance apart
equal to at least one-half (1/2) the length of the maximum overall diagonal
dimension of the building or area to be used;
(Q) Self-closing means to be equipped with an
approved device that will ensure closing after having been opened;
(R) Smoke barrier is a structural element,
either vertical or horizontal, such as a wall, floor, or ceiling assembly that
is designed and constructed to restrict the movement of smoke. A smoke barrier
may or may not have a fire resistance rating; and
(S) Supervised automatic sprinkler system is
a system with the initiating devices monitored by the fire alarm control panel.
This may include switches used to monitor the position of valves, a low air
pressure switch, a water flow switch, and a tamper switch.
(2) General Requirements.
(A) The Missouri Division of Fire Safety
shall inspect the facility annually for the capacity specified on the license
application and the fire inspection request. The inspection shall include a
determination of whether or not the facility is approved for overlap care as
provided in
19 CSR
30-61.155 Overlap Care of Children.
(B) At least one (1) portable, operable
flashlight for each staff member shall be located on each level of the home and
accessible to staff in the event of power failure.
(C) Child care staff shall conduct at least
one (1) fire drill each month and a disaster drill at least every three (3)
months. The disaster drills shall include tornado drills. The provider shall
maintain a written record at the facility of the date, type of drill, time
required to evacuate the building, and number of children present during the
drill.
1. Unscheduled drills may be held at
the fire inspector's discretion.
2.
A full evacuation of the home may be postponed during severe weather.
3. An evacuation/emergency plan for fires and
tornadoes that is approved by the fire inspector shall be posted in the home in
a central location and be visible to all occupants. The plan shall include
special instructions for infants and nonambulatory children.
4. Fire drills shall be conducted as follows:
A. Drills shall simulate an actual fire
condition;
B. The children shall
not obtain clothing or other items after the alarm has sounded;
C. The children shall proceed to a
predetermined location outside the building that is sufficiently remote to
avoid fire danger, interference with fire department operations, or confusion
among different groups of children; and
D. Groups shall remain in place until a
recall to the building is issued or the children are dismissed.
(D) Children shall have
no access to areas of the building that do not meet fire safety
requirements.
(E) All flammable or
combustible liquids, matches, lighters, or other hazardous items shall be
stored so they are inaccessible to the children.
(F) The house numbers shall be plainly
visible from the street in case of emergency.
(G) Housekeeping practices that ensure fire
safety shall be maintained daily.
(H) Stairways, walks, ramps, and porches
shall be kept free of ice and snow.
(I) The provider shall immediately report any
fire in the family day care home to the Office of the State Fire Marshal and
the Department of Health, Bureau of Child Care Safety and Licensure.
(J) No fresh-cut Christmas trees shall be
used unless they are treated with a flame resistant material. Documentation of
the treatment shall be on file at the facility and available for review by the
fire inspector.
(K) The Division of
Fire Safety may make additional requirements that provide adequate life safety
protection if it is determined that the safety of the occupants is endangered.
Every building or structure shall be constructed, arranged, equipped,
maintained, and operated to avoid danger to the lives and safety of its
occupants from fire, smoke, fumes, or resulting panic during the period of time
necessary for escape from the building.
(L) Mobile homes manufactured after November
27, 1973, shall comply with the Missouri Public Service Commission, regulations
for mobile home tie-down systems. Manufactured homes shall comply with section
700.070, RSMo 1994,
regarding tie-down systems.
(M) The
latest edition of the National Fire Protection Association (NFPA), Chapter 101,
Life Safety Code, shall prevail in the interpretation of this
rule.
(N) When the licensed
capacity increases, hours of care change, alterations are completed, or other
changes occur that affect fire safety, the provider shall meet all the
requirements of this rule unless otherwise excepted by the Division of Fire
Safety.
(O) Facilities that were
licensed and areas approved for child care prior to the effective date of this
rule shall have ceilings at least seven feet (7') in height. Facilities
initially licensed and areas initially approved for child care on or after the
effective date of this rule shall meet all the requirements of this rule and
shall have ceilings at least seven feet, six inches (7'6") in height. If
alterations are made in facilities licensed prior to the effective date of this
rule, those facilities shall meet all the requirements of this rule and shall
have ceilings at least seven feet, six inches (7'6") in height in the altered
space. The fire inspector may make an allowance for the installation of
ductwork and plumbing.
(P)
Facilities served by a volunteer or membership fire department shall be a
member in good standing with the fire department. A copy of the membership or
receipt for membership shall be on file at the facility and available for
review.
(Q) Clothes dryers shall be
vented and maintained properly.
(3) Mixed Occupancies.
(A) In addition to meeting all the
requirements of this rule, family day care homes initially licensed and areas
initially approved for child care on or after the effective date of this rule,
shall meet the following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities shall meet
these requirements in the altered space-
1.
When a facility is located in a building containing mixed occupancies, the
other occupancies shall be separated from the family day care home by at least
a one (1)-hour fire barrier; and
2.
In facilities in apartment buildings, when both exit accesses exit into the
same corridor, the corridor shall be protected throughout by a fire barrier
with at least a one (1)-hour fire resistance rated construction. All doors that
open into the corridor shall be at least thirty-two inches (32") wide, have a
twenty (20)-minute fire resistance rating, and be self-closing.
(4) Exiting and Means
of Egress.
(A) Each level occupied by
children shall have at least two (2) remotely located means of egress. Each
door opening in a means of egress shall be at least twenty-eight inches (28")
wide. In new construction, each door opening shall be a minimum of thirty-two
inches (32") wide.
(B) Each room
over three hundred (300) square feet in size that is used for day care shall
have at least two (2) means of egress. At least one (1) means of egress shall
be a door or stairway providing a means of unobstructed travel through the home
to the outside of the building at street or ground level. The second means of
egress may be a window in accordance with
19 CSR
30-61.086(5) Fire Safety.
(C) No room or space that is accessible only
by a ladder, folding stairs, overhead door, or through a trap door shall be
occupied at any time.
(D)
Facilities that use a garage as a second exit shall have no flammable or
combustible liquids stored in the garage unless approved by the fire inspector.
Overhead garage doors are not recognized as exit doorways.
(E) Automobiles shall not be stored in the
garage during day care hours if there is an exit through the garage, unless the
fire inspector determines that there is sufficient space for safe
evacuation.
(F) No door in a means
of egress shall be locked against egress travel when the building is occupied.
Locking devices that impede or prohibit egress or that cannot be disengaged
easily shall not be used. Dead bolt locks that require a key to unlock the door
from the inside shall not be used. Locking or latching devices installed on
doors shall not be located higher than fifty inches (50") above the finished
floor.
(G) Where two (2) exits or
exit access doors are required, they shall be remotely located from each
other.
(H) Closet door latches
shall be designed so children can open the doors from the inside. Bathroom door
locks shall be designed to permit opening of the door from the outside in an
emergency. The opening device or key shall be readily accessible to the
staff.
(I) Stairways, landings, and
ramps shall be free of all objects.
(J) Dead-ends as defined by
19 CSR
30-61.086(1)(B) Fire Safety shall not
exceed twenty feet (20').
(5) Windows for Rescue and Ventilation.
(A) In addition to meeting all the
requirements of this rule, facilities initially licensed and areas initially
approved for child care on or after the effective date of this rule, shall meet
the following requirements. If alterations are made in facilities licensed
prior to the effective date of this rule, those facilities shall meet these
requirements in the altered space-
1. Every
room or space greater than three hundred (300) square feet used by children
shall have at least one (1) outside window for emergency rescue and
ventilation. The window shall be operable from the inside without the use of
tools and shall provide a clear opening of at least twenty inches (20") wide,
twenty-four inches (24") in height. The total clear opening space shall be no
less than 5.7 square feet in size. The bottom of the opening shall be no more
than forty-four inches (44") above the floor and any latching device shall be
operated easily. The clear opening shall be a rectangular solid, with a minimum
width and height that provides the required 5.7 square feet opening and a
minimum depth of twenty inches (20") to allow passage through the opening. The
windows shall be accessible by the fire department and shall open into an area
having access to a public way. This does not apply when the room or space has a
door leading directly to the outside of the building; and
2. No windows shall have bars or any other
items placed over them in a stationary manner that would impede a rescue or
evacuation attempt.
(6) Level of Exit Discharge.
(A) Areas used for day care shall not be
located more than one (1) level below ground level.
(B) In addition to meeting all the
requirements of this rule, facilities initially licensed and areas initially
approved for child care on or after the effective date of this rule, shall meet
the following requirements. If alterations are made in facilities licensed
prior to the effective date of this rule, those facilities shall meet these
requirements in the altered space-
1. Where
children are occupying a level below or above the level of exit discharge
(basement or second floor), at least one (1) means of egress shall be an exit
discharging directly to the outside. The vertical travel to ground level shall
not exceed eight feet (8') for the basement and twelve feet (12') for the
second floor; and
2. Where children
are occupying a level below or above the level of exit discharge (basement or
second floor), arrangement of means of egress shall be remote from each
other.
(7)
Travel Distance.
(A) The travel distance
between any room door intended as an exit access or an exit shall not exceed
one hundred feet (100'). This travel distance may be increased by fifty feet
(50') in buildings protected throughout by a supervised automatic sprinkler
system that is approved by the fire inspector based on the National Fire
Protection Association's Standards for Sprinkler Systems.
(B) The travel distance between any point in
a room and an exit shall not exceed one hundred fifty feet (150'). This travel
distance may be increased by fifty feet (50') in buildings protected throughout
by a supervised automatic sprinkler system that is approved by the fire
inspector based on the National Fire Protection Association's Standards for
Sprinkler Systems.
(C) The travel
distance between any point in a sleeping room and an exit access to that room
shall not exceed fifty feet (50').
(8) Emergency Lighting.
(A) Emergency lighting shall be installed if
the facility is providing nighttime care or if the fire inspector determines
that the safety of the occupants is endangered. Emergency lights shall have a
ninety (90)-minute battery backup and shall be installed at a location
determined by the fire inspector.
(9) Interior Finish.
(A) Interior wall and ceiling finishes
throughout shall be Class C as provided in the latest edition of the National
Fire Protection Association, Chapter 101, Life Safety Code.
Textile materials having a napped, tufted, looped, woven, nonwoven, or similar
surface shall not be applied to walls or ceilings. Foam plastic materials or
other highly flammable or toxic material shall not be used as an interior wall,
ceiling, or floor finish.
(B) In
addition to meeting all the requirements of this rule, facilities initially
licensed and areas initially approved for child care on or after the effective
date of this rule, shall have wall studs, ceiling joists, and floor joists that
are covered with a minimum of Class C finish with no exposed studs or joists.
If alterations are made in facilities licensed prior to the effective date of
this rule, those facilities shall meet these requirements in the altered
space.
(10) Detection
and Extinguishment.
(A) Smoke detectors shall
be installed in all family day care homes.
(B) Smoke detectors shall be in good
operating condition with a functional battery installed. If the smoke detector
is not operational, the provider shall install a smoke detector that is powered
by the home's electrical system with a nine (9)-volt battery backup.
(C) Smoke detectors shall be installed on
each level of the home in or near all sleeping areas. Additional smoke
detectors shall be required in other rooms and areas if the fire inspector
determines that the safety of the occupants is endangered.
(D) Facilities using equipment or appliances
that pose a potential carbon monoxide risk, including homes with attached
garages, shall install a carbon monoxide detector(s). The detector(s) shall be
installed according to the manufacturer's instructions. The fire inspector may
require additional carbon monoxide detectors if the inspector determines that
the safety of the occupants is endangered.
1.
Carbon monoxide detectors shall be in good operating condition. If a
battery-operated detector is not operational, the provider shall install a
detector that is powered by the home's electrical system with a battery
backup.
2. If an elevated carbon
monoxide level is detected during a fire inspection, the provider shall have
all gas-fired appliances checked by a heating and air conditioning company to
identify the source of the carbon monoxide. Until the provider has
documentation on file at the facility verifying that all gas-fired appliances
were checked by a heating and air conditioning company and are in safe working
order, and the facility is determined safe by the fire inspector, the fire
inspection shall not be approved.
3. If a level of carbon monoxide is
determined that endangers the children in care, the fire inspector shall take
measures necessary to protect the children. This may include evacuation of the
building or closing the facility. The provider shall obtain and have on file at
the facility, documentation verifying that all gas-fired appliances were
checked by a heating and air conditioning company and are in safe working
order. The facility shall be reinspected by the fire inspector and determined
safe before the children can return to the building or the facility can
reopen.
(E) At least one
(1) portable, 5 lb., 2 A-10 BC, fire extinguisher shall be required in all
facilities and located near the kitchen or a location required by the fire
inspector. Facilities using more than one (1) level shall have an additional
extinguisher on each level.
(F)
Fire extinguishers shall be installed and maintained according to the
instructions of the fire inspector and shall be inspected and approved annually
by a fire extinguisher company. Documentation of the inspection and approval
shall be on file at the facility and available for review by the fire
inspector.
(G) In addition to
meeting all the requirements of this rule, facilities initially licensed and
areas initially approved for child care on or after the date of this rule,
shall meet the following requirements. If alterations are made in facilities
licensed prior to the effective date of this rule, those facilities shall meet
these requirements in the altered space-
1.
Smoke detectors shall be powered by the home's electrical system and have a
nine (9)-volt battery backup. When more than one (I) smoke detector is required
by the fire inspector, the smoke detectors shall be interconnected so that when
one smoke detector activates, it causes an alarm in all smoke detectors;
and
2. Where the family day care
home is located within a building of another occupancy such as in an apartment
building or office building, any corridors serving the family day care home
shall be provided with a smoke detector(s) that will activate the smoke
detector(s) inside the family day care home.
(H) Facilities that have a supervised
automatic sprinkler system installed shall have the system tested and approved
annually by a fire sprinkler company. A copy of the test report and approval of
the system shall be kept on file at the facility and available for review by
the fire inspector.
(11)
Electrical Services.
(A) Electrical wiring
shall be installed and maintained in good working order. If the fire inspector
considers the wiring to be unsafe for the occupants or it is installed
improperly, an inspection by a licensed electrician may be required prior to
fire safety approval. The inspection by the licensed electrician shall be based
on National Fire Protection Association, Chapter 70, National
Electrical Code.
(B)
Protective covers or inserts for electrical receptacles shall be installed in
all areas occupied by children.
(C)
Electrical extension cords shall not be used unless approved in writing by the
fire inspector.
(12)
Heating, Cooling, and Air Conditioning Equipment.
(A) Unvented fuel-fired room heaters and
portable electrical space heaters shall not be used during child care hours.
The provider shall sign a compliance letter verifying that such equipment will
not be used.
(B) Facilities with a
water heater over two hundred thousand (200,000) British thermal units (Btus)
per hour input or larger, or that is heating with a boiler, shall have a valid
permit from the Division of Fire Safety posted on the premises. A copy of the
permit shall be kept on file at the Division of Fire Safety.
(C) Floor furnaces shall have noncombustible
protective guards installed around them and shall be located so they do not
block access to an exit from any area of the licensed day care space.
(D) Heating equipment, fireplaces, and
radiators in areas occupied by children shall have partitions, screens, or
other means to protect children from hot surfaces and open flames. If solid
partitions are used, provisions shall be made to ensure adequate air for
combustion and ventilation for heating equipment. Partitions shall be
constructed of non-combustible material and shall not obstruct exit
access.
(E) Gas and electric
heating equipment shall be equipped with thermostatic controls. Gas water
heaters shall have a properly sized pressure relief valve and be vented
properly by galvanized flue pipe and screws at every joint in the pipe or by
material recommended by the manufacturer. The drip leg pipe on the pressure
relief valve shall extend to approximately six inches (6") above the
floor.
(F) Furnace rooms shall be
vented properly. Furnace flue pipes shall be constructed of galvanized pipe or
material recommended by the manufacturer. Galvanized pipe shall be secured by
screws at every joint in the pipe.
(G) Joints in gas supply pipes shall be
located outside the furnace cabinet housing.
(H) Furnaces, water heaters and boilers shall
be located inside a fire resistant room that is constructed of five-eighth inch
(5/8") sheet rock or equivalent on the interior, exterior, and ceiling. The
room shall have a one and three-quarter inch (1 3/4") thick solid core door.
Furnace rooms and rooms containing water heaters shall not be required to be
fire resistive if an automatic sprinkler head is installed off the domestic
water system and a smoke detector is located directly outside the room that is
interconnected to the other smoke detectors throughout the home.
(I) Furnace rooms and rooms containing water
heaters shall have adequate combustion air for the units. The vent size opening
for the combustion air shall be measured at one (1) square inch per one
thousand (1,000) Btu input, if the combustion air is drawn from inside the
structure and one (1) square inch per four thousand (4,000) Btu input if the
air is drawn from outside the structure through the attic or crawl space. There
shall be two (2) combustion air vent openings in each furnace room. One (1)
opening shall be located at the lower level and the other at the upper
level.
(J) Air conditioning,
heating, ventilating ductwork, and related equipment shall be installed safely
and be in good operating condition as determined by the fire inspector. The
fire inspector shall base this on the National Fire Protection Association,
Chapter 90A, Standard for the Installation of Air Conditioning and Ventilating
Systems; or National Fire Protection Association, Chapter 90B, Standard for the
Installation of Warm Air Heating and Air Conditioning Systems, as
applicable.
(K) Fireplaces and wood
burning stoves shall be installed safely and operate in good working condition
as determined by the fire inspector.
(L) Flues shall be inspected and cleaned once
a year, and the provider shall have documentation of the inspection and
cleaning on file at the facility and available for review by the fire
inspector. A spark arrestor shall be installed at the chimney outlet.
(M) In addition to meeting all the
requirements of this rule, facilities initially licensed and areas initially
approved for child care on or after the effective date of this rule, shall meet
the following requirements. If alterations are made in facilities licensed
prior to the effective date of this rule, those facilities shall meet these
requirements in the altered space-
1. Gas
shut off valves shall be located next to all gas appliances, furnaces, and
water heaters;
2. If a furnace or
water heater is located inside a garage, it shall be at least eighteen inches
(18") above the finished floor and enclosed inside a fire resistant room. The
room shall be constructed of five-eighth inch (5/8") sheet rock on the interior
and exterior wall and interior ceiling and shall have a one and three-quarter
inch (1 3/4") thick solid core door; and
3. Furnaces shall be equipped with an
electrical fused switch to protect the unit from electrical overloading and to
disconnect the electrical supply.
(13) Equivalency Concepts.
(A) Nothing in this rule is intended to
prevent the use of systems, methods, or devices of equivalent or superior
quality, strength, fire resistance, effectiveness, durability, and safety as
alternatives required by this rule. These alternatives may be used only if
technical documentation to demonstrate equivalency and the system, method, or
device is submitted and approved by the Missouri Division of Fire
Safety.
*Original authority: 210.221.1(3), RSMo 1949, RSMo 1955,
1987, 1993, 1995.