(4) General Design and
Construction Standards for New Inpatient Hospice Facilities.
(A) Health and Safety Laws. The hospice shall
meet all federal, state and local laws, ordinances, regulations and codes
pertaining to health and safety, including but not limited to, provisions
regulating construction, maintenance and equipment.
1. General Requirements.
A. After October 30, 1996, a new hospice
facility shall submit plans for approval to the Department of Health for the
construction of a new facility, expansion or renovation of an existing state
certified hospice or the conversion of an existing facility not previously and
continuously state certified and operated as a hospice facility under section
197.250,
RSMo.
B. New hospice facilities
shall be designed and constructed in conformance with this rule.
C. This rule is not intended to restrict
innovations and improvements in design or construction techniques. Accordingly,
the Department of Health may approve plans and specifications which contain
deviations from this rule. Requests for deviations from requirements on
physical facilities shall be in writing to the Department of Health and shall
contain information which determines that the respective intent or objectives
of this rule have been met. Approvals for deviations shall be in writing and
both requests and approvals shall be made a part of the permanent Department of
Health records for the hospice.
D.
Where renovation or replacement work is done within an existing licensed
facility, all new work, additions, or both, shall comply with the applicable
sections of this rule. Where existing major structural elements make total
compliance impractical or impossible, alternative proposals which result in an
equivalency may be considered by the department.
E. In renovation projects and additions to
existing state certified hospice facilities, only that portion of the total
facility affected by the project shall comply with the applicable sections of
this rule. However, upon construction completion, the facility shall satisfy
all functional requirements for state certified hospices.
F. Those existing portions of the facility
which are not included in the renovation but which are essential to the
functioning of the complete facility as well as existing state certified
building areas that receive less than substantial amounts of new work shall, at
a minimum, comply with the state certification requirements which were in
effect at the time that the existing portion of the building was state
certified.
G. All required fire
exits shall be maintained throughout the construction and the work shall be
phased as necessary to minimize disruption of the existing hospice
operation.
2. Planning
and Construction Procedures.
A. Any hospice
facility constructed or renovated after October 30, 1996 shall have plans and
specifications prepared in conformance with Chapter 327, RSMo by an architect
or engineer duly registered in Missouri. The owner of each new facility or the
owner of an existing licensed inpatient hospice being added to or undergoing
major alterations shall provide a program-scope of services- which describes
space requirements, staffing patterns, departmental relationships and other
basic information relating to the objectives of the facility. The program may
be general but it shall include a description of each function to be performed,
approximate space needed for these functions and the interrelationship of
various functions and spaces. The program shall describe how essential services
can be expanded in the future as the demand increases. Appropriate
modifications or deletions in space requirements may be made when services are
shared or purchased, provided the program indicates where the services are
available and how they are to be provided. This program shall be submitted to
the Department of Health for review along with the plans developed for the
project. Schematic and preliminary plans showing the basic layout of the
building and the general types of construction, mechanical and electrical
systems and details may be submitted to the department before the larger and
more complicated working drawings and specifications so that necessary
corrections can be easily made before final plans are completed. Working
drawings and specifications, complete in all respects, shall be prepared and
submitted to the Department of Health for approval. These plans shall cover all
phases of the construction project, including site preparation: paving; general
construction; mechanical work, including plumbing, heating, ventilating and air
conditioning; electrical work; and all built-in equipment, including elevators,
kitchen equipment, cabinet work, and the like.
B. The Department of Health shall be notified
in writing within five (5) days after construction begins. Construction shall
be in conformance with plans and specifications approved by the Department of
Health. The department may elect to inspect the construction of hospice
projects at any time during the development of the project. If construction of
the project is not started within one (1) year or completed within a period of
three (3) years after the date of the approval of the plans and specifications,
the plans and specifications shall be resubmitted to the Department of Health
for its approval and shall be amended, if necessary, to comply with the then
current rules before construction work is started or continued.
C. References in this rule to National Fire
Protection Association (NFPA) publications are those contained in the 12-volume
1994 Compilation of NFPA Codes, Standards, Recommended Practices and
Guides. Where there are discrepancies between referenced NFPA
publication requirements and this rule, the requirements of this rule shall
apply.
D. The design and
construction of hospices shall conform to the most stringent requirements of
this rule and the local governing building code and zoning
ordinances.
3. Site.
A. Adequate paved pedestrian access shall be
provided within the lot lines to the main entrance. Loading and unloading space
for delivery vehicles shall be paved.
B. Adequate paved parking shall be provided.
Parking space needs shall be determined by the local zoning requirement and the
operational program but shall not be less than one (1) space for each of the
maximum number of staff persons on duty at any given time plus one (1) parking
space for each licensed inpatient bed in the facility.
C. Fire lanes shall be provided as required
by local authority and kept clear to provide immediate access for fire fighting
equipment.
D. The site shall
provide reasonable access for those individuals to be served by the facility.
The facility shall be on an all-weather road for easy access by vehicular
traffic. Consideration should be given to locating the hospice to provide easy
access to public transportation services which may be available in the
community.
E. The site shall be
located within the service area of a public fire department.
4. Roads, parking facilities,
walks, ramps and entrances shall be accessible and usable by persons with
various physical handicaps.
A. At least one
toilet, telephone and drinking fountain shall be provided on each floor of a
hospice which is accessible for use by handicapped public and staff.
B. Elevator controls and alarms shall be
accessible to wheelchair occupants and shall be provided with tactile signage
for the visually impaired.
C.
Design details for handicapped accessible facilities should be consistent with
the Guidebook to: The Minimum Federal Guidelines of Requirements for
Accessible Design published January 6, 1981, by the U.S. Architectural
and Transportation Barriers Compliance Board.
D. At least ten percent (10%) of the patient
beds shall be located in handicapped-accessible rooms with accessible toilet
rooms which open directly into the patient room. All other clinical areas to
which patients have common access shall be handicapped-accessible.
5. Administrative and public areas
shall be provided.
A. All hospices shall
provide adequate work areas to support the administrative personnel and
governing body. The facilities shall allow business to be conducted in a
setting which provides confidentiality and privacy as required. The
administrative offices may be located remotely from a hospice inpatient unit or
may be housed within the inpatient facility.
B. Where administration is included within
the inpatient facility, the following shall be provided:
(I) Administrator's office;
(II) Business office including a work area
for quality assurance;
(III)
Storage and work area for archived medical records;
(IV) Conference room for governing board
meetings and personnel in-service training; and
(V) Office for director of patient-care
services.
C. Each
inpatient hospice facility shall provide the following public areas in a
location separated from the clinical and service areas of the facility:
(I) Lobby/waiting room with
reception;
(II) Wheelchair
accessible public toilet;
(III)
Wheelchair accessible public drinking fountain; and
(IV) Wheelchair accessible public
phone.
6.
Design of patient-care units.
A. One or more
patient-care units shall be provided. Each unit shall not exceed a maximum of
twenty (20) beds.
B. Each
patient-care unit shall be a continuous area which does not require
patient-care traffic to traverse other areas and shall be restricted to only
one (1) floor level. If justified by the program submitted under subparagraph
(2)(A)2.A. of this rule, the department may consider approval of designs which
provide for larger capacity patient-care units.
C. The bed area in a patient room exclusive
of toilet rooms, closets, alcoves or vestibules, shall not be less than one
hundred twenty (120) square feet in a private room and not less than two
hundred (200) square feet in a semi-private room. Heating units and lavatories
may protrude into this space.
D. No
dimension for the bed area in any patient room shall be less than ten (10)
feet.
E. No patient room shall
house more than two (2) patients.
F. Each patient-care unit shall have not
greater than fifty percent (50%) of its beds housed in semi-private rooms and
the remaining rooms shall be limited to occupancy by one (1) patient. If
justified by the program submitted under subparagraph (2)(A)2.A. of this rule,
the department may consider approval of designs which provide other ratios of
semi-private to private patient rooms.
G. Each patient shall have access to a toilet
room without entering the general corridor area.
H. One (1) toilet may serve not more than two
(2) adjacent rooms.
I. The toilet
room shall contain a lavatory and water closet and shall be sized to permit
access for the patient and an assisting member of the staff. The lavatory may
be omitted from the toilet room if a lavatory is provided in the patient
room.
J. At least one (1) patient
room per patient-care unit shall be provided to be used for isolation. This
unit shall have a toilet room equipped with a bathing facility which serves
this room exclusively.
K. Mirrors
shall be provided in each patient room or adjoining toilet room. Mirrors shall
be at least three (3) feet high located with the bottom edge no more than three
feet four inches (3'4") above the floor.
L. Patients shall have separate wardrobes,
lockers or closets located within their respective patient rooms. A clothes rod
and shelf shall be provided.
M. One
or more windows shall be provided, with the sash not more than three (3) feet
above the floor and with a gross area of not less than ten percent (10%) of the
floor area of the room. In each patient room at least one (1) window to the
outside shall be operable. Patient room windows shall be exposed to an outside
area not less than thirty (30) feet horizontally opposite the window which
contains no construction or grading which would further diminish the view and
the exposure of the window to natural light.
N. Social spaces (dining, recreation,
meditation) shall be provided throughout the facility with a cumulative area of
not less than thirty (30) square feet per patient bed. One social space may
serve more than one patient-care unit provided it is directly accessible from
each unit and is sized proportionate to the total number of patient beds it
serves. No social space shall be smaller than one hundred fifty (150) square
feet in area.
O. Unless bathing
facilities are included in the toilets serving each patient room, central
bathing facilities shall be provided in each patient-care unit at a ratio of
not fewer than one for each ten (1:10) beds.
P. Each bathing facility shall be located in
its own room and shall be directly accessible from the general corridor. The
bathing facility may be either a tub, shower or tub/shower
combination.
Q. However, at least
one (1) handicapped accessible shower shall be provided on each patient
unit.
R. A locked cabinet for the
storage of cleaning supplies shall be available in or near each
bathroom.
7. Support and
services areas. The following staff support and service areas shall be located
directly accessible to each patient care unit:
A. Clean work and storage facilities shall be
equipped with counter and sink and storage space provided for clean linen and
supplies;
B. A separate
soiled/decontamination utility room shall be equipped with a clinic sink (this
fixture is not required where bedpan-flushing devices have been installed at
each patient toilet), counter and sink and sufficient floor space shall be
provided to accommodate storage containers for soiled linen, trash and
infectious waste;
C. Space shall be
provided for secure storage of staff personal items;
D. A staff station shall be located to
provide visual supervision of the patient-care unit corridors. The station
shall consist of a work counter and secure storage space for charts;
E. A medication storage and preparation
station which has a means of locked storage for all medications shall be
equipped with a work counter, sink, and refrigerator;
F. Separate locked storage facilities shall
be provided in the station for controlled substances;
G. If medications are held in each patient
room, the room shall include separate locked storage facilities for each
patient's medications;
H. A
nourishment station shall be equipped with a work counter, sink, and
refrigerator and shall be provided physically remote from the medication
preparation station;
I. Storage
space shall be provided for mobile equipment used on the unit;
J. A janitor's closet shall be provided which
is equipped with a mop sink and has sufficient space for the cleaning equipment
and open supplies used to maintain the patient-care unit; and
K. All clean support functions may be located
in one clean workroom provided the room is carefully designed to provide
adequate storage and function separations.
8. Food service facilities shall be designed
and equipped to meet the requirements of the scope of services outlined as
follows:
A. Dietary facilities shall comply
with
19 CSR
20-1.010;
B. In hospice facilities where food is
prepared on-site, the dietary facilities shall, as a minimum, have-a storage
space including cold storage for four-day supply, space and equipment for food
preparation to facilitate efficient food preparation and to provide for a safe
and sanitary environment, conveniently located handwashing facilities, space
for preparing food for distribution to patients, warewashing facilities which
are isolated from the food preparation and serving area, and storage facilities
for waste which is inaccessible for insects and rodents and accessible to the
outside for pickup or disposal.
C.
The warewashing processes shall produce dietary ware which is free of
pathogenic organisms; and
D. In
hospice facilities where the food service is provided through a vendor
contract, dietary facilities shall, as a minimum, include space for receiving
and holding the food transport equipment, utility connections for food
transport equipment to maintain appropriate serving temperatures, and a holding
area for soiled dietary ware transport equipment which is out of the patient
area and located near the service entrance for pick-up.
(B) Service Facilities Shall Meet
the Following Standards:
1. Services
including linen service.
A. Service
facilities shall be provided in each inpatient hospice facility and located to
be out of the normal public and clinical traffic flow.
B. A weather-protected service entrance shall
be provided separate from entrances used by public and patients.
C. Space and facilities shall be provided for
the sanitary storage and disposal of waste. Exterior dumpsters will suffice
provided they can be accessed under the protection provided at the service
entrance.
D. A general storage room
shall be provided with an area not less than ten (10) square feet per bed for
the first fifty (50) beds, plus eight (8) square feet per bed for the next
twenty-five (25) beds, plus five square feet per bed for any additional beds
over seventy-five (75). No storage room shall be less than one hundred (100)
square feet of floor space. Off-site storage is acceptable, however, one half
(1/2) of the required storage space shall be located in the inpatient hospice
facility. General storage shall be concentrated in one area.
E. Space shall be provided to house
mechanical equipment. The space shall be adequate for initial installation and
ongoing maintenance access for each component of the systems housed in it.
Mechanical equipment shall not be installed in rooms designated to house other
functions.
F. A housekeeping room
shall be provided with a janitor's sink and space to store opened containers of
cleaning supplies and housekeeping equipment used to maintain the facility.
This room is not required if the hospice is maintained by a contract cleaning
service which transports the necessary cleaning supplies and equipment to the
facility on a daily basis.
G. An
oxygen storage room shall be provided. This room shall be enclosed with
one-hour rated construction and shall have a powered or gravity vent to the
outside. Permanent racks or fasteners shall be provided and used in the oxygen
storage room to prevent accidental damage or dislocation of oxygen cylinders.
In facilities storing quantities of oxygen less than one thousand five hundred
(1,500) cubic feet in total, a power ventilated storage cabinet will comply. No
ventilated gas storage facilities are required in hospices which store no
medical gases within the building.
H. Laundry services may be provided by the
hospice operator or may be obtained through contract with a linen service
vendor. If laundry for the facility is done commercially, either entirely or in
part, space shall be provided for the sorting, processing and storing of both
soiled and clean linen. Storage space shall be located to facilitate convenient
pickup and delivery by commercial laundry personnel. Hospices with only one
patient-care unit may accommodate these functions within the utility facilities
provided in the unit's staff support area.
I. Hospice-operated laundry facilities shall
be designed and procedures instituted to prevent cross-contamination of clean
and dirty linen. The laundry room shall be in a separate room from the kitchen,
patients' rooms, the dining room and the bathrooms or the nursing utility room.
Adequate space shall be provided in the laundry room for the storing, sorting
and processing of soiled linen. The processes of the laundry operation shall be
appropriate to the production of patient linens which are free of pathogenic
organisms. Space shall be provided for the storage of clean linen in a separate
room from the laundry.
J. As may be
required by the program, laundry facilities provided for cleaning patients'
clothing exclusively shall be located in the patient-care unit but in a room
separate from other functions. A residential-style laundry equipment
installation is acceptable.
K. As
required by the program, living and sleeping quarters, separate from patients'
facilities, shall be provided for the employees and their families who may
reside in the facility;
2. Elevators.
A. All inpatient hospice facilities having
patient-care facilities located on any floor other than the main entrance floor
shall have at least one (1) electric or electrohydraulic elevator. Hospice
facilities with more than thirty (30) beds located on any floor other than the
main entrance floor shall have at least two (2) elevators. Hospice facilities
with more than two hundred (200) beds located on any floor other than the main
entrance floor shall provide passenger and service elevators in numbers and at
locations determined by a professionally conducted study of the hospice
operation and its estimated vertical transportation needs.
B. Inside dimensions of patient-use elevators
shall be not less than five feet four inches (5'4") by eight feet (8')with a
capacity of 3,500 pounds. Cab and hoistway doors shall be not less than three
feet ten inches (3'10") clear opening.
C. Elevators shall be equipped with an
automatic leveling device of the two-way automatic maintaining type with an
accuracy of plus or minus one-half inch.
D. Elevator call buttons, controls and door
safety stops shall be of a type that will not be activated by heat or
smoke.
E. Elevator controls, alarm
buttons and telephones shall be accessible to wheelchair occupants and usable
by others with various physical disabilities.
F. Elevator hoistway doors shall be fire
rated to maintain the integrity of the fire-rated shaft enclosure;
3. Chutes and dumbwaiters.
A. Chutes and dumbwaiters may be installed in
hospice facilities as required by the operational program.
B. Linen and trash chutes shall be of
fire-resistant material and shall be installed with flushing ring, vent to
atmosphere and floor drain at the floor of the chute discharge. An automatic
sprinkler shall be provided at the top of each linen and trash chute.
C. Service openings to chutes shall not be
located in corridors or passageways but shall be located in a room having a
fire-resistant construction of not less than one hour. Doors to the rooms shall
be not less than 3/4-hour labeled doors equipped with an automatic closing
device.
D. Service openings to
chutes and other vertical openings shall have an approved self-closing labeled
fire door rating not less than the fire-resistant rating of the shaft in which
the chute is installed.
E. Chutes
shall discharge directly into collection rooms separate from the incinerator,
laundry or other services. Separate collection rooms shall be provided for
trash and for linen. These rooms shall have a fire-resistant construction of
not less than one hour. Doors to these rooms shall be not less than 3/4-hour
labeled doors equipped with an automatic closing device.
F. Dumbwaiters, conveyors and
material-handling systems shall not open directly into a corridor or exitway
but shall open into a room enclosed by construction having a fire resistance of
not less than one hour and provided with a 3/4-hour labeled fire door with a
self-closing device.
G. Where
horizontal conveyors and material-handling systems penetrate fire-rated walls
or smoke walls, the penetrations shall be protected to maintain the integrity
of the wall;
4. General
design, finish and life safety requirements.
A. A continuous system of unobstructed
corridors, referred to as required corridors, shall extend through the enclosed
portion of each story of the building, connecting all rooms and spaces with
each other and with all entrances, exitways and elevators, with the following
exceptions: work suites such as the administrative suite and dietary area,
which are occupied primarily by employed personnel, may have within them
corridors or aisles as considered advisable, but are not subject to the
regulations applicable to required corridors. Areas may be open to the required
corridor system as permitted by NFPA 101 (1994), The Life Safety
Code.
B. The arrangement
of the physical plant shall provide for separation of the
administrative/business, service and public areas from patient service
areas.
C. Ceilings shall be at a
height of at least eight feet. Ceilings in corridors, storage rooms, toilet
rooms and other minor rooms shall not be less than seven feet six inches
(7'6"). Suspended fixtures located in the path of normal traffic shall not be
less than six feet eight inches (6'8") above the floor.
D. Handrails may be provided on both sides of
all corridors and aisles used by patients and, if provided, corridor handrails
shall have ends return to the wall.
E. New inpatient hospice facilities shall be
designed and constructed in compliance with Chapters Five through Seven and
Chapter Twelve of NFPA 101 (1994), Life Safety Code and NFPA
99 (1993) Standard for Health Care Facilities, NFPA 13 (1994)
Standard for Installation of Sprinkler Systems and NFPA 90A
(1993) Standard for the Installation of Air Conditioning and
Ventilation Systems. Section 12-6 of NFPA 101 shall not apply to these
facilities.
F. Hardware on toilet
room doors shall be operable from both the inside and the outside. All toilet
room doors shall provide a net clear opening of not less than 32
inches.
G. The corridor doors from
all patient-use areas as well as all doors through which patients may need to
pass for emergency exit shall be not less than thirty-six (36) inches
wide.
H. Every window in
patient-use areas shall be provided with shades, curtains or drapes. Curtains
and drapes shall be made of fabric which is treated to be or is inherently
flame-retardant.
I. The floors of
toilets, baths, utility rooms and janitor's closets shall have smooth,
waterproof surfaces which are wear-resistant. The floors of kitchens and food
preparation areas shall be waterproof, greaseproof, smooth and resistant to
heavy wear.
J. The walls of all
rooms where food and drink are prepared, served or stored shall have a smooth
surface with painted or equally washable finish. At the base they shall be
waterproof and free from spaces which may harbor insects. The walls of
kitchens, utility rooms, baths, warewashing rooms, janitor's closets and spaces
with sinks shall have waterproof, painted, glazed, or similar finishes to a
point above the splash and spray line.
K. The ceilings of all kitchens, sculleries
and other rooms where food and drink are prepared shall be painted with
washable paint.
L. All casework in
the facility shall be finished with at least a sealer on all interior surfaces.
Casework with sinks installed in the counter shall be caulked to provide a
watertight joint between the backsplash and the wall.
M. All floor covering used in inpatient
hospice facilities shall have either Class A or B fire ratings as required by
Chapter Twelve of NFPA 101 (1994), The Life Safety
Code.
N. Stairways, ramps,
elevator hoist-ways, light or ventilation shafts, chutes and other vertical
openings between stories shall be enclosed with construction which is equal to
or greater than the required floor assembly rating of the building's
construction type.
O. The number of
stories in a building housing a hospice facility shall be determined by
counting the number of occupiable levels in the building regardless of their
location at, above or below grade.
P. Each room or patient-use area shall be
conspicuously and unmistakably identifiable at its entrance by patients,
visitors and staff.
Q. All signage
within six feet (6') of the floor shall be tactile to be usable by visually
impaired persons.
R. Fire-resistant
ratings-
(I) Definitions-
(a) Fire-separation distance is the distance
in feet measured from the building face to the closest interior lot line, to
the centerline of a street or public way or to an imaginary line between two
(2) buildings on the same property.
(b) Fire-protection rating is the time in
hours, or fractions of an hour, that an opening protective assembly will resist
fire exposure as determined in accordance with the test procedures set forth in
ASTM E119.
(II) Exterior walls with a fire-separation
distance less than five feet (5') shall have a fire-resistant rating of one (1)
hour.
(III) In exterior walls with
a fire-separation distance of three feet or less, no openings will be allowed,
from three feet (3') to five feet (5') no unprotected openings will be allowed,
and protected openings will be allowed with a total aggregate area of fifteen
percent (15%) of the wall surface.
(IV) Approved fire protective assemblies
shall be fixed, self-closing or equipped with approved automatic-closing
devices, a fire-resistant rating of not less than three-quarters (3/4) of an
hour shall be required.
(V) Fire
protective assemblies are not required where outside automatic sprinklers are
installed for the protection of the exterior openings. The sprinklers shall be
installed in accordance with NFPA 13;
5. Structural design.
A. All new facilities and additions to all
areas of existing licensed facilities which undergo major remodeling, in all
their parts, shall be of sufficient strength to resist all stresses imposed by
dead loads, live loads and lateral or uplift forces such as wind, without
exceeding, in any of the structural materials, the allowable working stress
established for these materials by generally accepted good engineering
practice.
B. Foundations shall rest
on solid ground or properly compacted fill and shall be carried to a depth of
not less than one foot below the estimated frost line or shall rest on leveled
rock or load-bearing piles when solid ground is not encountered. When
engineered fill is used, site preparation and placement of fill shall be done
under the direct full-time supervision of the soils engineer. The soils
engineer shall issue a final report on the compacted fill operation and certify
its compliance with the job specifications. Reasonable care shall be taken to
establish proper soil-bearing values for soil at the building site. If the
bearing capacity of the soil is in question, a recognized load test may be used
to determine the safe bearing value. Footings, piers and foundation walls shall
be adequately protected against deterioration from the action of
groundwater;
6.
Electrical systems.
A. The entire electrical
system shall be designed, installed and tested in compliance with NFPA 70
(1993) The National Electrical Code and NFPA 99 (1993)
Standard for Health Care Facilities.
B. Emergency lighting shall be provided for
exits, stairs and exit access corridors which shall be supplied by an emergency
service and automatic electric generator or battery lighting system. This
emergency lighting system shall be equipped with an automatic transfer switch.
If battery lights are used, they shall be wet cell units or other
rechargeable-type batteries equipped with automatic trickle charger. These
units shall be rated at four (4) hours.
C. Patient rooms shall have a minimum general
illumination of ten foot-candles, a night-light and a patient's reading light.
The general illumination fixtures and the night-light shall be switched at the
patient room door.
D. Ceiling
lighting fixtures, if used, shall be of a type which are shaded or globed to
minimize glare.
E. Each patient
room shall have not less than one duplex receptacle on each wall in the room.
The spacing of receptacles around the perimeter of the room shall not be
greater than twelve (12) feet.
F.
All occupied areas shall be adequately lighted as required by the duties
performed in the space.
G.
Night-lights shall be provided in corridor, stairways and patient rooms.
Toilets adjacent to patient rooms are not required to have
night-lights.
H. An electrically
powered communication system shall be provided which allows staff to respond to
patient calls regardless of patient location.
I. An electrically powered fire alarm system
shall be provided as required by NFPA 101 (1994) The Life Safety
Code. The fire alarm system shall have an emergency backup source of
electrical power and a direct connection for notifying the fire department or
fire department dispatch service. Fire alarm manual pull stations shall be
provided at each exit and at each staff workstation in the patient-care units.
Smoke detectors shall be installed in social space rooms which open directly to
the corridor, in the vicinity of any smoke or fire door which is permitted to
be held open by a magnetic hold-open device, and in the corridors at intervals
not exceeding 30 feet.
J. Portable
fire extinguishers shall be provided as required by NFPA 101 (1994) The
Life Safety Code and the local authority;
7. Mechanical systems.
A. The heating, ventilation and
air-conditioning systems shall be capable of providing temperature ranges
between 72oF-80oF in all
patient-care areas. The heating system shall be capable of maintaining a winter
indoor temperature of not less than 72oF in all
nonpatient areas. The air-conditioning system shall be capable of maintaining a
summer indoor temperature of not more than 80oF in
all nonpatient areas.
B. The
heating system shall have automatic controls adequate to provide comfortable
conditions in all portions of the building at all times.
C. Heating, ventilation and air-conditioning
systems installed in inpatient hospice facilities shall be designed, installed
and balanced in compliance with NFPA 90A (1993)
Standard for the
Installation of Air Conditioning and Ventilation Systems, and shall
provide the pressure relationships and at least the minimum air change rates
indicated in Table 1.
TABLE 1-VENTILATION REQUIREMENTS
Area Designation
|
Pressure Relationship to Adjacent Areas
|
Minimum Air Changes of Outdoor Air Per Hour
Supplied to Room
|
Minimum Total Air Changes Per Hour Supplied to
Room
|
All Air Exhausted
Directly to
Outdoors
|
Air Returned From This Room
|
Patient Room |
E |
2 |
2 |
Optional |
Optional |
Patient Area Corridor and Patient Living Room |
P |
2 |
2 |
Optional |
Optional |
Soiled Workroom and Soiled Linen Holding |
N |
Optional |
6 |
Yes |
No |
Clean Staff Work Area |
P |
2 |
6 |
Optional |
Optional |
Toilet Room |
N |
Optional |
6 |
Yes |
No |
Clean Linen Storage |
P |
Optional |
2 |
Optional |
Optional |
Designated Smoking Area |
N |
Optional |
10 |
Yes |
No |
Food Preparation Area |
E |
2 |
6 |
Yes |
No |
Warewashing |
N |
Optional |
6 |
Yes |
No |
Dietary and General Storage |
V |
Optional |
2 |
Optional |
Optional |
Linen and Trash Chute Room |
N |
Optional |
6 |
Yes |
No |
Medical Gas Storage and Manifold Rooms |
N |
Optional |
6 |
Yes |
No |
Administrative and Public Areas |
E |
2 |
2 |
Optional |
Optional |
P = Positive
N = Negative
V = Variable
E = Equal
D. All air-moving, heating, ventilation and
air-conditioning equipment shall be equipped with at least one filter located
upstream of the conditioning equipment. If a pre-filter is employed, the
pre-filter shall be upstream of the conditioning equipment and the main filter
shall be located farther downstream. All filters shall be easily accessible for
maintenance. Filter frames shall be durable and carefully dimensioned and shall
provide an airtight fit with the enclosing ductwork. All joints between the
filter segments and the enclosing ductwork shall be sealed to preclude air
leakage.
E. Outside air intakes
shall be located no less than 25 feet from exhaust outlets of ventilation
systems, combustion equipment stacks, clinical suction discharges and plumbing
vent stacks or from areas which may collect vehicular exhaust and other noxious
fumes.
F. Corridors shall not be
used to supply air to or exhaust air from any room, except that air from
corridors may be used to ventilate bathrooms, toilet rooms, janitor's closets
and small electrical or telephone closets opening directly onto corridors
provided that ventilation can be accomplished by the undercutting of doors. The
installation of louvers in corridor doors is prohibited. The space above the
finished ceiling may be used as a plenum for return air only.
G. Exhaust hoods in meal preparation areas
shall comply with the requirements of NFPA 96 (1994). All hoods and cooktop
surfaces in meal preparation areas shall be equipped with automatic fire
suppression systems, automatic fan controls and fuel shutoff;
8. Plumbing systems.
A. The entire plumbing system, its design,
operation and maintenance shall comply with the requirements of all applicable
local and state codes including the requirements set forth in this
rule.
B. Plumbing fixtures.
(I) All plumbing fixtures shall be of
nonabsorptive acid-resistant material.
(II) Clinical sinks shall have a
bedpan-flushing device and shall have an integral trap in which the upper
portion of a visible trap seal provides a water surface.
(III) Showers and tubs shall be provided with
nonslip surfaces.
(IV) Water
closets in patient areas shall be quiet operating types.
(V) Stools in patient toilet facilities shall
be the elongated bowl type with nonreturn stops, backflow preventers and
silencers. Seats shall be the split type and white in color.
(VI) Grab bars or handrails shall be provided
adjacent to all bathtubs.
(VII) All
lavatories shall be trimmed with valving operable without the use of
hands.
C. Water supply
systems.
(I) A reliable source of potable
water shall be provided at the site to supply water in sufficient quantities to
meet the various use demands of the hospice. The source of water shall have
been tested and approved by the Missouri Department of Natural
Resources.
(II) The water supply
systems shall be designed to supply water at sufficient pressure to operate all
fixtures and equipment during maximum demand periods.
(III) Each water service main, branch main,
riser and branch to a group of fixtures shall be valved. Stop valves shall be
provided at each fixture.
(IV)
Reduced pressure backflow preventers shall be installed on water service
entrance, hose bibbs, janitors' sinks, bedpan-flushing attachments, and on all
other fixtures to which hoses or tubing can be attached. The installation of
backflow preventors shall provide safeguards against waterline
expansion.
(V) The water supply
system shall be designed to provide hot water at each hot water outlet at all
times. The water-heating equipment shall have sufficient capacity to supply
five gallons of water at 120oF per hour per bed for
hospice fixtures and eight gallons per bed for kitchen and laundry. Lesser
capacities may be accepted upon submission of the calculation for the
anticipated demand of all fixtures and equipment in the building. Hot water at
showers and bathing facilities shall not exceed
110oF. Hot water at handwashing facilities shall not
exceed 120oF. Hot water circulating mains and risers
shall be run from the hot storage tank to a point directly below the highest
fixture at the end of each branch main.
D. Drainage systems.
(I) All fixtures and equipment shall be
connected through traps to soil and waste piping and to the sewer and they
shall all be properly vented to the outside.
(II) Courts, yards and drives which do not
have natural drainage from the building shall have catch basins and drains to
low ground, storm-water drainage system or dry wells.
(III) The building sanitary drain system
shall be piped in cast iron, steel, copper or plastic.
(IV) Building sewers shall discharge into a
community sewerage system when available. If such a system is not available, a
facility providing sewage treatment shall conform to the rules of the
Department of Natural Resources.
(V) Drainage piping shall not be installed
within the ceiling or exposed in food preparation centers, food service
facilities, food storage areas and clean linen storage rooms; special
precautions shall be taken to protect any of these areas from possible leakage
or condensation from necessary overhead drainage piping systems. These special
precautions include requiring noncorrosive drip troughs with a minimum
four-inch outside diameter to be installed under the drainage pipe in the
direction of slope to a point where the pipe leaves the protected space and
terminates at that point-usually at a wall. The trough shall be supported with
noncorrosive strap hangers and screws from the pipe above. Trough joints and
hanging screw penetrations shall be sealed to maintain watertight integrity
throughout.
E. Natural
or liquefied petroleum (LP) gas systems.
(I)
Where gas-fire equipment is used, all gas piping, fittings, tanks and
specialties shall be provided and installed in compliance with NFPA 54 (1992),
NFPA 58 (1992), and the instructions of the gas supplier, except where more
strict requirements are stated. Where liquefied petroleum gas (LPG) is used,
compliance with the rules of the Missouri Department of Agriculture is also
required.
(II) Where gas piping
enters the building below grade, it shall have an outside vent as follows: a
concrete box shall be made 18 inches by 18 inches with three-inch thick walls,
of a height to rest on top of the entering gas pipe, and the top of the box to
coming within six inches of top grade. The box shall be filled with coarse
gravel. A one-inch upright vent line shall be to 1/2 the depth of the box and
extend 12 inches above grade with a screened U-vent looking down. The vent line
shall be anchored securely to the building wall.
(III) Gas outlets and gas-fired equipment
shall not be installed in any patients' bedrooms.
F. Where a piped central medical gas
distribution system is installed, the oxygen piping, outlets, manifold rooms,
and storage rooms shall be installed in accordance with the requirements of
Chapter 4 of NFPA 99 (1993); and
9. Fire prevention and general operating
requirements.
A. The hospice facility shall
be maintained in a manner which provides a clean safe environment for the
delivery of patient care and shall, until remodeled or renovated with the
approval of the Department of Health, remain compliant with the codes and
regulations under which the facility was constructed.
B. Exitways shall always be maintained free
of obstructions.
C. Curtains,
drapes and cubicle curtains shall be maintained in a manner which does not
compromise their fire-resistant properties.
D. Smoking may be permitted in the patient's
room by the patient only, and designated smoking areas by others. Designated
smoking areas shall be ventilated as required by Table 1 of this rule.
Modification of the patient room ventilation system is not required to permit
occasional authorized smoking by a patient.
E. All waste containers shall be of
noncombustible construction.
F.
Electrical systems and medical gas systems shall be tested according to the
provisions of NFPA 99 (1993) and shall be modified as necessary to comply with
the operational requirements of that standard.