(1) This regulation
does not apply to abortion facilities that do not perform surgical abortions or
surgical intervention for abortion complications.
(2) Requests for
deviations from requirements on physical facilities shall be in writing to the
Department of Health and Senior Services. Approvals for deviations shall be in
writing and both requests and approvals shall be made a part of the permanent
Department of Health and Senior Services records for the abortion
facility.
(3) Any abortion facility constructed or renovated
after October 25, 1987 shall have plans prepared by an architect or engineer
registered in Missouri. These plans shall be submitted to the department for
review and approval prior to construction. New abortion facilities shall have
the following:
(A) At least two (2) remote
exits shall be provided for each floor directly to the outside or through an
enclosed stairway or passageway to the outside;
(B) Corridors serving patients shall be at
least six feet (6') wide;
(C) All
doors through which patients pass shall be at least forty-four inches (44")
wide and of solid-core construction;
(D) One- (1-) story buildings shall be at
least of Type II (111) protected noncombustible construction as described in
Standard on Types of Building Construction 1979 published by the National Fire
Protection Association;
(E)
Multistory buildings shall be constructed of at least Type II (222)
fire-resistive construction as described in Standard on Types of Building
Construction published by the NFPA, or shall be protected throughout by an
approved automatic sprinkler system;
(F) Multistory buildings shall have at least
one (1) elevator. The elevator cab shall be at least five feet by seven feet
(5' x 7') clear inside. The car door shall have a clear opening of not less
than forty-four inches (44");
(G)
Trickle-charge battery pack units shall be located to provide emergency
lighting in the procedure room, recovery room, exit corridors, and exit stairs
to grade;
(H) A manual fire alarm
break station shall be located near each exit and connected to a local audible
alarm which can be heard throughout the facility;
(I) At least two (2) ABC-type fire
extinguishers are to be located in the facility, one (1) in the clinical
area;
(J) Illuminated exit signs
shall be located above each exit and illuminated directional exit signs shall
be located where needed to direct patients and personnel to exits in event of
an emergency;
(K) Ceiling, wall,
and floor finishes in the clinical area including the procedure rooms, recovery
room, personnel change rooms, central sterile and supply, janitor's closet, and
laboratory shall be smooth and easily cleanable;
(L) Scrub-up facilities shall be knee- or
foot-operated and provided at the rate of one (1) per procedure room. Scrub-up
facilities shall be located outside but immediately available to the procedure
room;
(M) Procedure rooms shall
have the following:
1. A minimum length and
width of twelve feet (12');
2. A
minimum ceiling height of nine feet (9');
3. A door with a minimum width of forty-four
inches (44"); and
4. There shall be
no windows in the room except there may be a fixed-view window in the wall
between the procedure room and the adjacent corridor;
(N) The recovery room shall be separated from
the procedure room and be of sufficient size to accommodate at least four (4)
recovery beds or recliners for each procedure room. There shall be three feet
(3') of clear space on both sides and at the foot of each recovery bed or
recliner;
(O) The procedure room
and recovery room shall be provided with a minimum of six (6) air changes per
hour. Air supplied to all areas shall be filtered through a filter with at
least a twenty-five percent (25%) efficiency rating;
(P) Personnel change rooms shall be provided
for each sex and located convenient to the procedure room. Each change room
shall be equipped with a toilet and lavatory;
(Q) The laboratory shall be equipped with a
counter, sink, and refrigerator;
(R) The procedure room shall be equipped with
a ceiling-mounted surgical light, operating table or a conventional
gynecological examining table with accessories, closed cabinets for equipment,
and sufficient tables to hold an emergency tray and other necessary
equipment;
(S) There shall be one
(1) electrical outlet in the procedure room for the emergency light and at
least one (1) duplex outlet on each wall;
(T) There shall be one (1) electrical outlet
in the recovery room for the emergency light and at least one (1) duplex outlet
for each two (2) recovery beds or recliners;
(U) Piped-in or portable oxygen and suction
equipment shall be located in the recovery room;
(V) The sterilizing room shall be equipped
with a steam sterilizer, counter and sink, and storage space for clean
supplies. Air pressure in this room shall be positive in relation to adjacent
areas;
(W) The
soiled/decontamination room shall be equipped with a counter and sink. This
room shall be equipped with a constant running exhaust;
(X) A patient toilet with lavatory shall be
located convenient to the recovery room. This room shall be equipped with a
constant running exhaust;
(Y) At
least two (2) patient change rooms with secure storage for personal effects
shall be provided; and
(Z) Office
space, waiting room, record storage space, and counseling rooms shall be
provided. Counseling rooms shall be separate and not smaller than ten feet by
ten feet (10' x 10').
(4) Any abortion
facility in operation at the time these rules are adopted shall comply with the
following:
(A) Smoke detectors shall be
located in all rooms and in corridors at thirty-feet (30') intervals unless the
building is rated Type II (222) fire-resistive or if it is a one- (1-) story
building rated Type II (111) protected-noncombustible as described in Standard
on Types of Building Construction 1979 published by the NFPA. If the building
is multistoried and rated combustible, it shall be protected throughout by an
approved automatic sprinkler system;
(B) There shall be a system of corridors,
passageways, and elevators adequate in size and arrangement to allow a patient
on a stretcher to be moved from any point in the abortion facility to a
street-level exit;
(C) Space shall
be provided for waiting, registration, counseling, medical evaluation,
examination, and referral. This space shall be equipped with suitable
furnishings and accommodations;
(D)
Dressing rooms shall be provided for the privacy, physical comfort, and
convenience of patients and personnel;
(E) At least one (1) procedure room shall be
adequately equipped, supplied, and staffed to safely perform abortions. The
procedure room shall be equipped with an operating table or a conventional
gynecologic examining table with accessories, a closed cabinet for equipment,
and tables to hold an emergency tray and other necessary equipment. The
procedure room shall be well-lighted and maintained at a comfortable
temperature;
(F) Personnel change
rooms and scrub-up facilities shall be located convenient to the procedure
room;
(G) A utility room with
facilities for steam sterilization and space for storage of clean and
sterilized supplies shall be provided. There shall be sufficient surgical
instruments sterilized and available for each patient who presents herself for
an abortion. The room shall be arranged to prevent cross traffic of clean and
dirty material;
(H) The recovery
room shall be separate from the procedure room and be of sufficient size to
accommodate at least four (4) recovery beds or recliners for each procedure
room. The recovery room shall be well-lighted and maintained at a comfortable
temperature. Recovery beds or recliners shall be spaced to permit easy staff
access to each patient;
(I)
Piped-in or portable oxygen and suction equipment shall be located in the
recovery room;
(J) Trickle charge
battery pack units shall be located to provide emergency lighting in the
procedure room, recovery room, exit corridors, and exit stairs to
grade;
(K) A manual fire alarm
break station shall be located near each exit and connected to a local audible
alarm which can be heard throughout the facility;
(L) At least two (2) ABC-type fire
extinguishers shall be located in the facility, one (1) in the clinical
area;
(M) Illuminated exit signs
shall be located above each exit door and illuminated directional exit signs
shall be located where needed to direct patients and personnel to exits in
event of an emergency;
(N) Wall and
floor finishes in the procedure room, recovery room, and the sterilization area
shall be smooth and easily cleanable;
(O) The laboratory shall be equipped with a
counter, sink, and refrigerator; and
(P) At least two (2) remote exits shall be
provided for each floor. Each exit shall discharge directly to the outside or
through an enclosed stairway or passageway to the outside.