Mississippi Administrative Code
Title 15 - Mississippi Department of Health
Part 21 - Division of Radiological Health
Subpart 78 - Radiological Health
Chapter 1 - REGULATIONS FOR CONTROL OF RADIATION IN MISSISSIPPI
Subchapter 9 - Radiation Safety Requirements for Particle Accelerators
Rule 15-21-78-1.9.11 - Radiation Monitoring Requirements

Current through September 24, 2024

1. There shall be available, at each particle accelerator facility, appropriate portable monitoring equipment which is operable and has been appropriately calibrated for the radiations being produced at the facility. Such equipment shall be tested for proper operation daily and calibrated at intervals not to exceed one year and after each servicing and repair.

2. A radiation protection survey shall be performed and documented by a qualified expert, acceptable to the Agency, when changes have been made in shielding, operation, equipment, or occupancy of adjacent areas.

3. Radiation levels in all high radiation areas shall be continuously monitored. The monitoring devices shall be electrically independent of the accelerator control and safety interlock systems and capable of providing a readout at the control panel.

4. All area monitors shall be calibrated at intervals not to exceed one year and after each servicing and repair.

5. Whenever applicable, periodic surveys shall be made to determine the amount of airborne particulate radioactivity present.

6. Whenever applicable, periodic smear surveys shall be made to determine the degree of contamination.

7. All surveys shall be made in accordance with the written procedures established by a qualified expert, acceptable to the Agency, or the radiation safety officer.

8. Records of all radiation protection surveys, calibrations, and instrumentation tests shall be maintained at the accelerator facility for inspection by the Agency.

Miss. Code Ann. § 45-14-11

Disclaimer: These regulations may not be the most recent version. Mississippi may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.