Mississippi Administrative Code
Title 15 - Mississippi Department of Health
Part 20 - Bureau of Public Water Supply
Subpart 72 - Public Water Supply
Chapter 1 - MISSISSIPPI PRIMARY DRINKING WATER REGULATION
Subchapter 12 - Recommended Backflow Preventers
Rule 15-20-72-1.12.2 - Recommended Devices for High Hazard Cross Connections

Current through September 24, 2024

1. Reduced Pressure Principle Backflow Prevention Assemblies. Backflow prevention assemblies recommended to protect high hazard cross connections shall include reduced pressure principle backflow prevention assemblies.

2. Pressure Vacuum Breaker Assemblies. Backflow prevention assemblies recommended to protect high hazard cross connections shall include pressure vacuum breaker assemblies. Pressure vacuum breaker assemblies shall not be used in locations where the vacuum breaker may be subject to back pressure and shall not be used in locations where the vacuum breaker is not higher than all downstream connections.

3. Atmospheric Vacuum Breakers. Backflow prevention devices recommended to protect high hazard cross connections shall include atmospheric vacuum breakers. Atmospheric vacuum breakers shall not be installed in locations that may be subject to back pressure, shall not be installed in locations where the vacuum breaker is not higher than all downstream locations, shall not be installed in locations with valves downstream and shall not be installed in locations of continuous use.

Miss. Code Ann. § 41-26-14

Disclaimer: These regulations may not be the most recent version. Mississippi may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.