Rule 15-20-72-1.12.2 - Recommended Devices for High Hazard Cross Connections
Current through September 24, 2024
1. Reduced Pressure Principle Backflow Prevention Assemblies. Backflow prevention assemblies recommended to protect high hazard cross connections shall include reduced pressure principle backflow prevention assemblies.
2. Pressure Vacuum Breaker Assemblies. Backflow prevention assemblies recommended to protect high hazard cross connections shall include pressure vacuum breaker assemblies. Pressure vacuum breaker assemblies shall not be used in locations where the vacuum breaker may be subject to back pressure and shall not be used in locations where the vacuum breaker is not higher than all downstream connections.
3. Atmospheric Vacuum Breakers. Backflow prevention devices recommended to protect high hazard cross connections shall include atmospheric vacuum breakers. Atmospheric vacuum breakers shall not be installed in locations that may be subject to back pressure, shall not be installed in locations where the vacuum breaker is not higher than all downstream locations, shall not be installed in locations with valves downstream and shall not be installed in locations of continuous use.
Miss. Code Ann. § 41-26-14