Mississippi Administrative Code
Title 11 - Mississippi Department of Environmental Quality
Part 5 - Underground Storage Tank Regulations
Chapter 2 - Mississippi Commission on Environmental Quality Underground Storage Tanks Regulations Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage Tanks (UST) (Adopted March 22, 1989; Amended August 25, 2011, Last Amended August 23, 2018)
Rule 11-5-2.4 - Leak Detection
Section 11-5-2.4-280.44 - Methods of leak detection for piping

Current through September 24, 2024

Each method of leak detection for piping used to meet the requirements of § 280.41 must be conducted in accordance with the following:

(a) Automatic line leak detectors. Methods which alert the operator to the presence of a leak by restricting or shutting off the flow of regulated substances through piping or triggering an audible or visual alarm may be used only if they detect leaks of 3 gallons per hour at 10 pounds per square inch line pressure within 1 hour. Testing must be performed in accordance with the following requirements:

(1) Frequency.
(i) Automatic line leak detectors installed on or after October 1, 2008, must be tested in accordance with the requirements of this rule at startup to verify proper operation and at least once every 12 months thereafter.

(ii) Automatic line leak detectors installed before October I, 2008, must be tested in accordance with the requirements of this rule by no later than October 1, 2009, and at least once every 12 months thereafter.

(2) Criteria. All testing of automatic line leak detectors must be conducted in accordance with the manufacturer's specifications and any applicable code of practice listed in § 280.13 and
(i) Involve the simulation of a leak in the piping at the dispenser that is at the highest elevation above the submersible pump. If there is no change in elevation, the test must be conducted at the dispenser that is the furthest away from the submersible pump;

(ii) Be conducted with the leak detector installed in the system as it normally would be during operation;

(iii)Verify that the leak detector is capable of detecting a leak equivalent to 3 gallons per hour at 10 pounds per square inch line pressure within 1 hour; and

(iv) Be conducted finitely and the test results reported quantitatively.

(3) Records. A written record documenting the testing of automatic line leak detectors must be maintained (in accordance with § 280.35) to demonstrate compliance with this section. These records must provide the results of the last two (2) tests required in this section.

(b) Line tightness testing. A periodic test of piping may be conducted only if it can detect a 0.1 gallon per hour leak rate at one and one-half times the operating pressure and the test is conducted in accordance with manufacturer specifications or other recommended code of practice.

(c) Interstitial monitoring. Monitoring of the space between the inner (primary) and the outer (secondary) pipe walls may be used, but only if the system is designed, constructed and installed to meet the following requirements:

(1) The sampling or testing method can detect a leak from any portion of the pipe that routinely contains product;

(2) The sampling or testing method can detect ingress of water or other external fluids into the interstice;

(3) Records must be maintained that show the interstice has been checked at least every 30 days for evidence of a leak or ingress of external fluids;
(i) If the interstice is monitored continuously, records must document that the electronic device monitoring the interstice is in communication with the control console at least monthly;

(ii) If the interstice is monitored continuously, records must document the alarm history and provide the appropriate reporting (if applicable) and reconciliation of each alarm;

(iii)Any electronic device that monitors the interstice must be tested at least once every 12 months for proper function. The functionality test must be in accordance with the manufacturer's specifications and any applicable industry code or recommended practice listed in § 280.13. The functionality test must simulate a leak; and

(4) Any regulated substance that enters the interstice must be removed within 24 hours of discovery or another time frame determined by the MDEQ to be reasonable.

(d) Applicable tank methods. Any of the methods in § 280.43(e), (0 or (h) may be used if they are designed to detect a leak from any portion of the underground piping that routinely contains regulated substances.

Disclaimer: These regulations may not be the most recent version. Mississippi may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.