Mississippi Administrative Code
Title 11 - Mississippi Department of Environmental Quality
Part 5 - Underground Storage Tank Regulations
Chapter 2 - Mississippi Commission on Environmental Quality Underground Storage Tanks Regulations Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage Tanks (UST) (Adopted March 22, 1989; Amended August 25, 2011, Last Amended August 23, 2018)
Rule 11-5-2.4 - Leak Detection
Section 11-5-2.4-280.44 - Methods of leak detection for piping
Current through September 24, 2024
Each method of leak detection for piping used to meet the requirements of § 280.41 must be conducted in accordance with the following:
(a) Automatic line leak detectors. Methods which alert the operator to the presence of a leak by restricting or shutting off the flow of regulated substances through piping or triggering an audible or visual alarm may be used only if they detect leaks of 3 gallons per hour at 10 pounds per square inch line pressure within 1 hour. Testing must be performed in accordance with the following requirements:
(b) Line tightness testing. A periodic test of piping may be conducted only if it can detect a 0.1 gallon per hour leak rate at one and one-half times the operating pressure and the test is conducted in accordance with manufacturer specifications or other recommended code of practice.
(c) Interstitial monitoring. Monitoring of the space between the inner (primary) and the outer (secondary) pipe walls may be used, but only if the system is designed, constructed and installed to meet the following requirements:
(d) Applicable tank methods. Any of the methods in § 280.43(e), (0 or (h) may be used if they are designed to detect a leak from any portion of the underground piping that routinely contains regulated substances.