Mississippi Administrative Code
Title 11 - Mississippi Department of Environmental Quality
Part 5 - Underground Storage Tank Regulations
Chapter 2 - Mississippi Commission on Environmental Quality Underground Storage Tanks Regulations Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage Tanks (UST) (Adopted March 22, 1989; Amended August 25, 2011, Last Amended August 23, 2018)
Rule 11-5-2.4 - Leak Detection
Section 11-5-2.4-280.43 - Methods of leak detection for tanks

Current through September 24, 2024

Each method of leak detection for tanks used to meet the requirements of § 280.41 must be conducted in accordance with the following:

(a) Inventory control. Product inventory control (or another test of equivalent performance) must be conducted monthly to detect a leak of at least 1.0 percent of flow-through plus 130 gallons on a monthly basis in the following manner:

(1) Inventory volume measurements for regulated substance inputs, withdrawals, and the amount still remaining in the tank are recorded each operating day;

(2) The equipment used is capable of measuring the level of product over the full range of the tank's height to the nearest one-eighth of an inch;

(3) The regulated substance inputs are reconciled with delivery receipts by measurement of the tank inventory volume before and after delivery;

(4) Deliveries are made through a drop tube that extends to within one foot of the tank bottom;

(5) Product dispensing is metered and recorded within the local standards for meter calibration or an accuracy of 6 cubic inches for every 5 gallons of product withdrawn; and

(6) The measurement of any water level in the bottom of the tank is made to the nearest one-eighth of an inch at least once a month.

(b) Manual tank gauging. Manual tank gauging must meet the following requirements:

(1) Tank liquid level measurements are taken at the beginning and ending of a period using the appropriate minimum duration of test value in the table below during which no liquid is added to or removed from the tank;

(2) Level measurements are based on an average of two consecutive stick readings at both the beginning and ending of the period;

(3) The equipment used is capable of measuring the level of product over the full range of the tank's height to the nearest one-eighth of an inch;

(4) A leak is suspected and subject to the requirements of Rule 2.5 if the variation between beginning and ending measurements exceeds the weekly or monthly standards in the following table:

Nominal tank capacity

Minimum Duration

Weekly standard (one test)

Monthly standard (average of four tests)

550 gallons or less

36 hours

10 gallons

5 gallons.

551-1,000 gallons

(when tank diameter is 64 inches)

44 hours

9 gallons

551-1,000 gallons

(when tank diameter is 48 inches)

58 hours

12 gallons

551-1,000 gallons

36 hours

13 gallons

7 gallons.

1,001-2,000 gallons

36 hours

26 gallons

13 gallons.

(5) Only tanks of 550 gallons or less nominal capacity may use this as the sole method of leak detection. Tanks of 551 to 2,000 gallons may use this method in place of manual inventory control in § 280.43(a). Tanks of greater than 2,000 gallons nominal capacity may not use this method to meet the requirements of this rule.

(c) Tank tightness testing. Tank tightness testing (or another test of equivalent performance) must be capable of detecting a 0.1 gallon per hour leak rate from any portion of the tank that routinely contains product while accounting for the effects of thermal expansion or contraction of the product, vapor pockets, tank deformation, evaporation or condensation, and the location of the water table.

(d) Automatic tank gauging. Equipment for automatic tank gauging that tests for the loss of product must meet the following requirements:

(1) The automatic product level monitor test can detect a 0.2 gallon per hour leak rate from any portion of the tank that routinely contains product. The equipment must be capable of visual or audible alarms and the equipment must be capable of printing the completed 0.2 gallon per hour leak rate test; and

(2) The equipment is inspected for proper operation at least once every 12 months. The inspection must be conducted in accordance with the manufacturer's periodic maintenance specifications and any applicable code of practice listed in § 280.13.

(3) The test must be performed with the system operating in one of the following modes:
(i) In-tank static testing conducted at least once every 30 days; or

(ii) Continuous in-tank leak detection operating on an uninterrupted basis or operating within a process that allows the system to gather incremental measurements to determine the leak status of the tank at least once every 30 days.

(e) Vapor monitoring. Testing or monitoring for vapors within the soil gas of the excavation zone must meet the following requirements:

(1) The materials used as backfill are sufficiently porous (e.g., gravel, sand, crushed rock) to readily allow diffusion of vapors from releases into the excavation area;

(2) The stored regulated substance, or a tracer compound placed in the tank system, is sufficiently volatile (e.g., gasoline) to result in a vapor level that is detectable by the monitoring devices located in the excavation zone in the event of a release from the tank;

(3) The measurement of vapors by the monitoring device is not rendered inoperative by the ground water, rainfall, or soil moisture or other known interferences so that a release could go undetected for more than 30 days;

(4) The level of background contamination in the excavation zone will not interfere with the method used to detect releases from the tank;

(5) The vapor monitors are designed and operated to detect any significant increase in concentration above background of the regulated substance stored in the tank system, a component or components of that substance, or a tracer compound placed in the tank system;

(6) In the UST excavation zone, the site is assessed to ensure compliance with the requirements in paragraphs (e) (1) through (4) of this rule and to establish the number and positioning of monitoring wells that will detect releases within the excavation zone from any portion of the tank that routinely contains product and

(7) Monitoring wells are clearly marked and secured to avoid unauthorized access and tampering.

(f) Ground-water monitoring. Testing or monitoring for liquids on the ground water must meet the following requirements:

(1) The regulated substance stored is immiscible in water and has a specific gravity of less than one;

(2) Ground water is never more than 20 feet from the ground surface and the hydraulic conductivity of the soil(s) between the UST system and the monitoring wells or devices is not less than 0.01 cm/sec (e.g., the soil should consist of gravels, coarse to medium sands, coarse silts or other permeable materials);

(3) The slotted portion of the monitoring well casing must be designed to prevent migration of natural soils or filter pack into the well and to allow entry of regulated substance on the water table into the well under both high and low ground-water conditions;

(4) Monitoring wells shall be sealed from the ground surface to the top of the filter pack;

(5) Monitoring wells or devices intercept the excavation zone or are as close to it as is technically feasible;

(6) The continuous monitoring devices or manual methods used can detect the presence of at least one-eighth of an inch of free product on top of the ground water in the monitoring wells;

(7) Within and immediately below the UST system excavation zone, the site is assessed to ensure compliance with the requirements in paragraphs (f) (1) through (5) of this rule and to establish the number and positioning of monitoring wells or devices that will detect releases from any portion of the tank that routinely contains product; and

(8) Monitoring wells are clearly marked and secured to avoid unauthorized access and tampering.

(g) Interstitial monitoring. Monitoring of the space between the inner (primary) and the outer (secondary) tank walls may be used, but only if the system is designed, constructed and installed to meet the following requirements:

(1) The sampling or testing method can detect a release from any portion of the tank that routinely contains product;

(2) The sampling or testing method can detect ingress of external fluids (groundwater or other fluids not intended as monitoring fluids) into the interstice;

(3) Records must be maintained that show the interstice has been checked at least every 30 days for evidence of a leak or ingress of external fluids;
(i) If the interstice is monitored continuously, records must document that the electronic device monitoring the interstice is in communication with the control console at least monthly;

(ii) If the interstice is monitored continuously, records must document the alarm history and provide the response action taken, appropriate reporting (if applicable) and reconciliation of each alarm;

(iii) Any electronic device that monitors the interstice must be tested at least once every 12 months for proper function. The functionality test must simulate a leak and be in accordance with the manufacturer's specifications and any applicable industry code or recommended practice listed in § 280.13; and

(4) Any regulated substance that enters the interstice must be removed within 24 hours of discovery or another time frame determined by the MDEQ to be reasonable.

(h) Other methods. Any other type of leak detection method, or combination of methods, can be used if:

(1) It can detect a 0.2 gallon per hour leak rate or a release of 150 gallons within a month with a probability of detection of 0.95 and a probability of false alarm of 0.05; or

(2) The MDEQ may approve another method if the owner and operator can demonstrate that the method can detect a release as effectively as any of the methods allowed in paragraphs (c) through (h) of this rule. In comparing methods, the MDEQ shall consider the size of leak that the method can detect and the frequency and reliability with which it can be detected. If the method is approved, the owner and operator must comply with any conditions imposed by the MDEQ on its use to ensure the protection of human health and the environment.

Disclaimer: These regulations may not be the most recent version. Mississippi may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.