Rule 11-5-2.1 - Program Scope and Interim Prohibition
Section 11-5-2.1-280.11 - Installation requirements for partially excluded UST systems
Universal Citation: MS Code of Rules 11-5-2.1-280.11
Current through September 24, 2024
(a) No person may install an UST system listed in § 280.10(c) for the purpose of storing regulated substances unless the UST system (whether of single- or double-wall construction):
(b) Will prevent leaks due to corrosion or structural failure for the operational life of the UST system:
(1) Is cathodically protected
against corrosion, constructed of non-corrodible material, steel clad with a
non-corrodible material, or designed in a manner to prevent the leak or
threatened leak of any stored substance; and
(2) Is constructed of materials that are
compatible with the stored substance.
Disclaimer: These regulations may not be the most recent version. Mississippi may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.