7081.0140 - INFILTRATION.

Universal Citation: MN Rules 7081.0140
7081.0140 INFILTRATION.

The design flow must also include 200 gallons of infiltration and inflow per inch of collection pipe diameter per mile per day with a minimum pipe diameter of two inches to be used for the calculation. Flow values are allowed to be further increased if the system employs treatment devices that are exposed to atmospheric conditions that will infiltrate precipitation. Flow estimates as calculated in this chapter shall not be relied upon for the design of collection systems.

Statutory Authority:

MS s 115.03; 115.55

History:

32 SR 1400

Published Electronically:

March 11, 2011

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.