7080 - INDIVIDUAL SUBSURFACE SEWAGE TREATMENT SYSTEMS
7080.1990 - TANK STORAGE, TRANSPORT, AND USE.

Universal Citation: MN Rules 7080.1990
7080.1990 TANK STORAGE, TRANSPORT, AND USE.
Subpart 1. Precast reinforced concrete tanks.

Precast reinforced concrete tanks must:

A. have a method to lift the tank for an ultimate load that is four times the working load;

B. undergo proper curing to achieve a compressive strength of 4,000 pounds per square inch before transport, placement, or use; and

C. have no pipe penetration points or openings in the exterior walls or tank bottom below the tank liquid level, unless designed for a specific operational purpose and approved by the local unit of government.

Subp. 2. Other tanks.

Fiberglass-reinforced polyester or polyethylene tanks must be protected against deterioration during storage.

Statutory Authority:

MS s 115.03; 115.55

History:

32 SR 1347

Published Electronically:

October 10, 2013

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.