Minnesota Administrative Rules
Plumbing Board
4714 - PLUMBING CODE
4714.0717 - SIZE OF BUILDING SEWERS.

Universal Citation: MN Rules 4714.0717
4714.0717 SIZE OF BUILDING SEWERS.

UPC section 717, Table 717.1, is amended to read as follows:

TABLE 717.1
Maximum/Minimum Fixture Unit Loading on Building Sewer Piping
Size of Pipe (inches) SLOPE (inches per foot)
1/16 1/8 1/4
6 and smaller (As specified in Table 703.2/No minimum loading)
8 1950/1500 2800/625 3900/275
10 3400/1600 4900/675 6800/300
12 5600/1700 8000/725 11 200/325

For SI units: 1 inch= 25 mm, 1 inch per foot= 83.3 mm/m

Statutory Authority:

MS s 326B.43; 326B.435

History:

40 SR 71

Published Electronically:

January 25, 2016

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.