Minnesota Administrative Rules
Plumbing Board
4714 - PLUMBING CODE
4714.0602 - UNLAWFUL CONNECTIONS.

Universal Citation: MN Rules 4714.0602
4714.0602 UNLAWFUL CONNECTIONS.
Subpart 1. Section 602.2.

UPC section 602.2 is amended to read as follows:

602.2 Cross-Contamination. Unless there is provided a backflow prevention device approved for the potential hazard and maintained in accordance with this code, no person shall make a connection or allow one to exist between pipes or conduits carrying domestic water supplied by a public or private building supply system, and (1) pipes, conduits, or fixtures containing or carrying water from any other source or containing or carrying water that has been used for any purpose whatsoever, or (2) any piping carrying chemicals, liquids, gases, or substances whatsoever.

Each point of use shall be separately protected where potential cross-contamination of individual units exists. Water used for cooling or heating of equipment or other purposes shall not be returned to the potable water system. Such water shall be discharged into the drainage system through an air-gapped indirect waste or other approved method of disposal.

Subp. 2. Section 602.4.

UPC section 602.4 is amended to read as follows:

602.4 Approval by Authority. No water piping supplied by a private water supply system shall be connected to any other source of supply without the approval of the Authority Having Jurisdiction.

Statutory Authority:

MS s 326B.43; 326B.435

History:

40 SR 71

Published Electronically:

January 25, 2016

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.