Part 4714.0905 - VENT PIPE GRAPES AND CONNECTIONS

Universal Citation: MN Rules 4714.0905
Current through Register Vol. 48, No. 39, March 25, 2024

UPC section 905.3 is amended to read as follows:

905.3 Vent Pipe Rise. Except as provided elsewhere in this code, each vent shall rise vertically to a point not less than 6 inches (152 mm) above the flood-level rim of the fixture served before offsetting horizontally, and where two or more vent pipes converge, each such vent pipe shall rise to a point not less than 6 inches (152 mm) in height above the flood-level rim of the plumbing fixture it serves before being connected to any other vent.

Statutory Authority: MS s 326B.43; 326B.435

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.