Part 4714.0717 - SIZE OF BUILDING SEWERS
Universal Citation: MN Rules 4714.0717
Current through Register Vol. 48, No. 39, March 25, 2024
UPC section 717, Table 717.1, is amended to read as follows:
TABLE 717.1
Maximum/Minimum Fixture Unit Loading on Building Sewer Piping SLOPE (inches per loot)
Size of Pipe (inches) |
1/16 |
1/8 |
1/4 |
6 and smaller |
(As specified in Table 703.2/No minimum loading) |
||
8 |
1950/1500 |
2800/625 |
3900/275 |
10 |
3400/1600 |
4900/675 |
6800/300 |
12 |
5600/1700 |
8000/725 |
11 200/325 |
For SI units: 1 inch = 25 mm, 1 inch per foot = 83.3 mm/m
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.