Part 4714.0504 - WATER HEATER REQUIREMENTS

Universal Citation: MN Rules 4714.0504

Current through Register Vol. 48, No. 39, March 25, 2024

Subpart 1. Sections 504.1 to 504.2.

UPC sections 504.1 to 504.2 are deleted in their entirety.

Subp. 2. Section 504.6.

UPC section 504.6 is amended to read as follows:

504.6 Temperature, Pressure, and Vacuum Relief Devices. The installation of temperature, pressure, and vacuum relief devices, or combinations thereof, shall be installed in accordance with the terms of their listings and the manufacturers installation instructions. A shutoff valve shall not be placed between the relief valve and the water heater or on discharge pipes between the valves and the atmosphere. The hourly British thermal units (Btu) (kW-h) discharge capacity or the rated steam relief capacity of the device shall be not less than the input rating of the water heater. [NFPA 54:10.28.5]

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.