Minnesota Administrative Rules
Agency 222 - Plumbing Board
Chapter 4714 - PLUMBING CODE
Part 4714.0403 - WATER-CONSERVING FIXTURES AND FITTINGS

Universal Citation: MN Rules 4714.0403

Current through Register Vol. 48, No. 39, March 25, 2024

UPC section 403.3 is amended to read as follows:

403.3 Urinals. Urinals shall have an average water consumption not to exceed 1 gallon (4 L) of water per flush.

403.3.1 Nonwater urinals. Nonwater urinals shall be listed and comply with the applicable standards referenced in Table 1401.1. Nonwater urinals shall have a barrier liquid sealant to maintain a trap seal. Nonwater urinals shall permit the uninhibited flow of waste through the urinal to the sanitary drainage system. Nonwater urinals shall be cleaned and maintained in accordance with the manufacturers instructions after installation. Where a nonwater urinal is installed, a water-supplied fixture shall be installed upstream of the nonwater urinal at the end of that same drainage branch.

Statutory Authority: MS s 326B.43; 326B.435

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.