Part 7511.1015 - SECTION 1015, EXIT AND EXIT ACCESS DOORWAYS
Universal Citation: MN Rules 7511.1015
Current through Register Vol. 48, No. 39, March 25, 2024
IFC section 1015.1 is amended to read:
1015.1 Exit or exit access doorways required from spaces. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:
1. The occupant load of the space exceeds the
values in Table 1015.1.
Exceptions:
a. In Groups R-2 and R-3 occupancies, one
means of egress is permitted within and from individual dwelling units with a
maximum occupant load of 20 if the dwelling unit is equipped throughout with an
automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2.
b. Care suites in Group
I-2 occupancies complying with section 407.4.3 of chapter 1305, the Minnesota
Building Code.
2. The
common path of egress travel exceeds the limitations of Section
1014.3.
3. Where required by
Sections 1015.3, 1015.4, 1015.5, and 1015.6.
4. When located in buildings used for
educational purposes, laboratories and prep rooms that exceed 500 square feet
in area and contain hazardous materials.
Where a building contains mixed occupancies, each individual occupancy shall comply with the applicable requirements for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered in accordance with the provisions of Section 1004.1.
Statutory Authority: MS s 299F.011; 326B.02
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.