Minnesota Administrative Rules
Agency 171 - Public Safety Department
Chapter 7511 - FIRE CODE
Part 7511.0912 - SECTION 912, FIRE DEPARTMENT CONNECTIONS

Universal Citation: MN Rules 7511.0912

Current through Register Vol. 48, No. 39, March 25, 2024

IFC Section 912.2 is amended by adding a section to read:

912.2.3 Connection height. Newly installed fire department connections shall be located not less than 18 inches (457 mm) and not more than 4 feet (1.2 m) above the level of the adjacent grade or access level.

Statutory Authority: MS s 299F.011

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.