The owner or operator of indirect heating equipment who elects to achieve compliance with an applicable standard of performance by derating must:
A. advise the commissioner in writing of the intent to achieve compliance by derating and the capacity level at which the owner or operator intends to operate this equipment;
B. agree to a permit condition in the required operating permit that prohibits operating the equipment over the derate level;
C. install a boiler steam flow meter to continuously record, indicate, and integrate boiler steam flow, and must:
D. submit an effective method of physical limitation of boiler load for approval by the commissioner before authorization of a boiler derate. The limitation may include a tieback signal from the steam flow meter to the combustion control system cutting back fuel input at the derate load, a maximum limit stop on the fuel input control drive or valve, or other equivalent physical means.