Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 7511 - FIRE CODE
Part 7511.2307
Current through Register Vol. 49, No. 13, September 23, 2024
IFC section 2307. IFC section 2307 is deleted and replaced with the following:
2307.1 General. Motor fuel-dispensing facilities for liquefied petroleum gas (LP-gas) fuel shall be constructed and installed in accordance with NFPA 58 and this section.
2307.2 Approvals. Storage vessels and equipment used for the storage or dispensing of LP-gas shall be approved or listed in accordance with Sections 2307.2.1 and 2307.2.2.
2307.3 Dispensing. Motor fuel-dispensing operations for LP-gas shall comply with Section 2304 and NFPA 58.
In addition, the following requirements shall apply:
2307.4 Vehicle impact protection. Vehicle impact protection for LP-gas storage containers, pumps, and dispensers shall be provided in accordance with Section 2306.7.3 or 312.
2307.5 Self-service fueling of motor vehicles. Self-service LP-gas dispensing systems shall be controlled by key, code, or access card issued to trained persons and shall be limited to the filling of permanently mounted fuel containers on LP-gas powered vehicles.
2307.6 Operational requirements. Self-service LP-gas dispensing systems shall comply with the operational requirements of Section 2305.
2307.7 Emergency shutoff switch. The LP-gas motor fuel-dispensing system shall be provided with an emergency shutoff distinctly labeled as EMERGENCY LP-GAS FUEL SHUTOFF installed in accordance with Section 2303.2.
2307.8 Overfilling. LP-gas containers shall not be filled in excess of the fixed outage installed by the manufacturer or the weight stamped on the tank.
Statutory Authority: MS s 326B.02