Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 7511 - FIRE CODE
Part 7511.1010 - SECTION 1010, DOORS, GATES AND TURNSTILES
Current through Register Vol. 48, No. 39, March 25, 2024
Subpart 1. IFC section 1010.1.5.
IFC section 1010.1.5 is amended by modifying exception 5 to read as follows:
Subp. 1a. IFC section 1010.1.9.1.
IFC section 1010.1.9.1 is amended to read:
Subp. 1b. IFC section 1010.1.9.2.
The exception to IFC section 1010.1.9.2 is amended to read as follows:
Exception: The ingress side of access doors or gates in barrier walls and fences protecting pools, spas, and hot tubs shall be permitted to have operable parts of the latch release on self-latching devices at 54 inches (1,370 mm) maximum above the finished floor or ground, provided that the self-latching devices are not also self-locking devices operated by means of a key, electronic opener, or integral combination lock. All hardware shall comply with Section 1010.1.9.6.
Subp. 1c. IFC section 1010.1.9.4.
IFC section 1010.1.9.4 is amended to read as follows:
Subp. 1d. IFC section 1010.1.9.7.
IFC section 1010.1.9.7 is amended to read:
Exceptions to items 1 through 11:
Subp. 2. IFC sections 1010.1.9.8 and 1010.1.9.8.1.
IFC sections 1010.1.9.8 and 1010.1.9.8.1 are amended to read:
Exception: Delayed egress locking systems shall be permitted to be installed on exit or exit access doors, other than the main exit or exit access door, serving a courtroom in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
Exception to item 4. Where approved, a delay of not more than 30 seconds is permitted on a delayed egress door.
Exceptions to item 5.
Exception to item 6. Where approved, in Group I occupancies, the installation of a sign is not required where care recipients, because of clinical needs, require restraint or containment as part of the function of the treatment area.
Subp. 2a. IFC section 1010.1.9.12.
IFC section 1010.1.9.12 is amended by revising exception 3 to read as follows:
Subp. 3. IFC section 1010.1.
IFC section 1010.1 is amended by adding subsections to read:
All locking devices shall be designed to fail in the open position. Following the release of the locking devices for any of the conditions specified in Items 1 through 6, relocking the devices shall be by manual means only at the door.