Current through Register Vol. 49, No. 13, September 23, 2024
Subpart
1.
Attendance; plant of 0 to 50 horsepower.
At a minimum, a high pressure boiler plant of 0 to 50
horsepower, when in operation, must be visually observed at least once every 24
hours by an operating engineer. The operating engineer must document the
findings and conditions in the boiler room logbook maintained pursuant to part
5225.1110.
Subp. 2.
Attendance; plant of 51 to 500
horsepower.
A. A high pressure boiler
plant of 51 to 500 horsepower may be left in operation unattended by an
operating engineer for no more than two consecutive hours, except as permitted
by item B or subpart 5. The operating engineer must visually observe the
operating condition of the boiler and appurtenances at least every two hours
and document the findings and conditions in the boiler room logbook maintained
pursuant to part
5225.1110.
B. A high pressure boiler plant of 51 to 500
horsepower is exempt from the high pressure attendance requirements of item A
if the plant is operated at low pressure. All boilers must either be shut down
or shifted to low pressure. If a boiler is shifted to low pressure, it must
have the following controls, safety devices, and conditions:
(1) the boiler must be equipped with high
pressure controls and low pressure controls. These controls must be arranged so
that they cannot be operated at the same time. The header connecting the low
pressure controls to the boiler must have an isolation valve and a drain
valve;
(2) the boiler must be
equipped with fail-safe type safety controls for regulating pressure, water
level, and fuel supply. Controls and safety devices must meet the minimum
requirements for automatically fired boilers in Code Sections I, IV, and
Controls and Safety Devices for Automatically Fired Boilers (CSD-1) of the
American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel
Code;
(3) the boiler must be
equipped with a low pressure header designed to prevent the system pressure
from exceeding 15 psi. The low pressure header must have ASME code stamped
safety valves set at 15 psi or less. The low pressure header safety valves must
be constructed to ASME Code Section I or IV requirements;
(4) the low pressure header must be equipped
with an isolation valve that isolates the header from the boiler or piping. The
valve must be interlocked with the controls to prevent the valve from being
opened when the system pressure is greater than 15 psi. The valve must be
interlocked with the high pressure controls to prevent the high pressure
controls from operating when the valve is open;
(5) the building in which the boiler is
located must not be occupied by the public or employees except for custodial,
maintenance, or security personnel;
(6) an operating engineer must manually
switch over the valves and controls between high and low pressure, enter the
date and time of the switch in the boiler room logbook, and sign the logbook
entry; and
(7) when the boiler is
operating on low pressure, an operating engineer must visually observe the
boiler operating conditions at least once every 24 hours and record the
conditions in the boiler room logbook pursuant to part
5225.1110.
Subp. 3.
Attendance; plant
over 500 horsepower.
A. A high
pressure boiler plant of more than 500 horsepower, when in operation, requires
constant attendance, except as otherwise provided in item B or subpart
5.
B. The operating engineer in a
high pressure boiler plant of over 500 horsepower may leave the boiler room for
up to 30 minutes if all boilers are equipped with dual pressure controls and
dual low water fuel cutouts, one of which must be the manual reset type. The
operating engineer must stay within 500 feet of the boiler room at all times
during the shift.
Subp.
5.
Attendance; unoccupied plant.
This subpart applies to plants with individual boilers that
are 51 to 500 horsepower located in an unoccupied plant. A high pressure boiler
51 to 500 horsepower may participate in the remote monitoring program if it
complies with the requirements in items A to N.
A. Boiler owners must submit an application
in a manner prescribed by the commissioner to the department for review and
approval to participate in the remote monitoring program for unoccupied
plants.
B. The building must be
completely unoccupied and the boiler owner must demonstrate with substantiated
data that the unattended boiler is located within a safe unoccupied
radius.
C. An operating engineer
must perform the remote monitoring. The boiler owner must develop a written
policy for safe response time for each individual boiler. The operating
engineer must be able to respond to any of the safety concerns listed in item L
within the safe response time specified in the policy.
D. The operating engineer must visually
observe the operating condition of the boiler and appurtenances in person and
document the findings and conditions in the boiler room logbook, maintained
pursuant to part
5225.1110, at least once every 24
hours.
E. When remotely monitoring
high pressure boilers 51 to 500 horsepower, the operating engineer must
continuously monitor the following boiler conditions:
(1) water level for steam boilers;
(2) boiler pressure;
(3) temperature for high temperature hot
liquid;
(4) stack
temperature;
(5) feedwater
flow;
(6) make-up water flow for
high temperature hot liquid;
(7)
steam flow;
(8) fuel flow, at
burner;
(9) gas/oil
pressure;
(10) concentration of
carbon monoxide in boiler room; and
(11) a video camera providing a continuous
live video feed of the burner, sight glass, and pressure gauge. The live video
feed must be continuously available to the operating engineer for remote
viewing.
F. The boiler
must have two feed pumps that supply water to the boiler.
G. A boiler firing with gas must have a
flammable gas detection system in the boiler room with a visible and audible
alarm. The alarm must trigger before the gas reaches an explosive level. The
alarms must be visible and audible inside the boiler room and on the remote
monitoring device. Located immediately outside the boiler room door, there must
be:
(1) visible and audible alarms;
(2) an independent remote water level
indicator; and
(3) remote boiler
shutdown switches.
H.
Boilers using gas or liquid fuels must have a written fuel-rich condition
shutdown procedure, which must be made available to the operators.
I. Each boiler must have written standard and
emergency operating procedures, which include testing of all safety devices at
the manufacturers' recommended scheduled intervals.
J. A diary must be maintained in the boiler
room in a manner that prevents revisions, additions, or deletions. The diary
must document, at a minimum, equipment start-up and shutdown times; equipment
repairs; equipment inspections; equipment maintenance; equipment testing
performed; and the name of the operating engineer documenting these actions,
inspections, and tests performed. The diary must be provided to a national
board-commissioned inspector upon request.
K. The remote monitoring device and system
must have a communication failure alarm. The operating engineer must return to
the boiler room immediately upon notification of a communication
failure.
L. As recommended by the
boiler manufacturer, the operating engineer must establish a primary set point
that triggers an alarm and a secondary set point that automatically shuts down
the boiler. The primary set point must trigger an alarm if the boiler
conditions fall outside of the boiler's normal operating conditions but are
within an operating range in which the boiler is safe to operate temporarily.
The secondary set point must trigger the boiler to automatically shut down when
the boiler conditions are outside of safe operating conditions. The following
items must have primary and secondary set points:
(1) high and low water level for steam
boilers;
(2) high and low boiler
pressure;
(3) temperature for high
temperature hot water heating;
(4)
concentration of carbon monoxide in boiler room;
(5) fuel flow;
(6) steam flow;
(7) gas/oil pressure; and
(8) flammable gas detection.
A fame sensor must trigger an alarm when a fame is not
detected and automatically shut down the boiler.
M. A national board-commissioned inspector
must conduct both an initial internal and external inspection of the boilers to
determine compliance with this subpart to qualify for remote monitoring. The
internal inspection must be conducted while the boiler is not in operation. The
external inspection must be conducted while the boiler is in operation.
Annually thereafter, the national board-commissioned inspector must conduct
internal and external inspections to ensure continued compliance with this
subpart. The inspector must document the name of the water treatment company
and the name of the certified water treatment specialist. The water treatment
specialist must be certified to treat, test, and monitor the boiler water.
Inspection reports must be submitted to the chief boiler inspector.
N. The water treatment specialist must
establish a water treatment program that contains boiler water quality
parameters. The specialist must monitor the program at least every 60 days by
testing the boiler water and reviewing the operating engineer's test results.
The operating engineer must test and document the results of the boiler water
at least every 24 hours. The test results must be provided to the specialist,
the national board-commissioned inspector, or chief boiler inspector upon
request. The boiler owner and operating engineer are responsible for ensuring
that the boiler meets all of the requirements of the remote monitoring program
identified in subpart 5. If the boiler owner or operating engineer determines
that the boiler fails to meet the requirements of the remote monitoring program
at any time, the owner or engineer must immediately comply with the constant
attendance requirements in subpart
3 until all deficiencies are
corrected and restored to compliance with the remote monitoring program. All
deficiencies and subsequent corrections must be documented by the operating
engineer in the diary. If the chief boiler inspector or national
board-commissioned inspector determines that the boiler fails to comply with
the requirements of this subpart, the boiler is disapproved for the remote
monitoring program and must begin immediate compliance with the constant
attendance requirements identified in subpart
3. Reinstatement in the
remote monitoring program is granted to the boiler owner by correcting the
deficiency and obtaining verification of the correction from the national
board-commissioned inspector. Evidence of the correction and verification must
be submitted to the chief boiler inspector prior to reinstatement.