Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 1346 - MINNESOTA MECHANICAL AND FUEL GAS CODES
MINNESOTA FUEL GAS COD
Part 1346.5602 - SECTION 602 (IFGC) DECORATIVE APPLIANCES FOR INSTALLATION IN FIREPLACES
Universal Citation: MN Rules 1346.5602
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. Section 602.1.
IFGC Section 602.1 is amended to read as follows:
602.1
General. Decorative
appliances for installation in approved solid fuel burning fireplaces shall be
tested in accordance with ANSI Z21.50-2000, Vented Gas
Fireplaces, and ANSI Z21.88-2000, Vented Gas Fireplace
Heaters, and shall be installed in accordance with the manufacturer's
installation instructions. Manually lighted natural gas decorative appliances
shall be tested in accordance with an approved method.
Subp. 2. Section 602.3.
IFGC Section 602.3 is amended to read as follows:
602.3
Prohibited installations.
Decorative appliances for installations in fireplaces shall not be installed
where prohibited by IFGC Section 303.3. Unvented decorative appliances shall
not be installed in any dwelling or occupancy.
Statutory Authority: MS s 16B.59; 16B.61; 16B.64; 326B.101; 326B.106; 326B.13
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.