Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 1346 - MINNESOTA MECHANICAL AND FUEL GAS CODES
MINNESOTA FUEL GAS COD
Part 1346.5303 - SECTION 303, (IFGC) APPLIANCE LOCATION
Universal Citation: MN Rules 1346.5303
Current through Register Vol. 49, No. 13, September 23, 2024
IFGC section 303.3, Prohibited locations, is amended by deleting items 3 and 4 from the list of exceptions.
Subpart 1. Section 303.3.
IFGC section 303.3, Prohibited locations, is amended by deleting items 3 and 4 from the list of exceptions.
Subp. 2. Section 303.3.1.
IFGC section 303.3.1 is amended to read as follows:
303.3.1
Fireplaces and decorative
appliances in Group I-1, Condition 2 and Group I-2, Condition 2
occupancies. Direct-vent gas fireplaces shall be permitted inside smoke
compartments containing dwelling units, sleeping rooms, and patient sleeping
areas where all of the following conditions are met:
1. The direct-vent gas fireplaces are not
located within a sleeping room.
2.
The direct-vent fireplaces have a sealed glass front with a wire mesh panel or
screen.
3. The controls for the
direct-vent gas fireplace are located where they can be accessed only by
facility staff.
4. Electrically
supervised carbon monoxide detection is provided in the room where the
direct-vent gas fireplace is located.
5. The direct-vent fireplace includes a guard
in front of the glass where the glass temperature is equal to or exceeds
125°F (52°C).
Statutory Authority: MS s 326B.02; 326B.101; 326B.106; 326B.13
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.