Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1.
Chapter 9.
The IFGC is amended by adding a chapter to read as
follows:
CHAPTER 9
Subp.
2.
Installation and testing of fuel gas-fired equipment;
general.
Chapter 9 shall regulate the installation and testing or
repair of gas or fuel burning systems, gas or fuel burners, and gas or fuel
burning equipment installed within, or in conjunction with, building or
structures. The requirements of this chapter shall apply to the following
equipment:
1. Equipment utilized to
provide control of environmental conditions.
Exception: Equipment and appliances listed and
labeled to an appropriate standard by a nationally recognized testing
laboratory, which is qualified to evaluate the equipment or appliance, when
installed and tested according to the manufacturer's installation
instructions.
2. Equipment
with a fuel input of 1,000,000 Btu/hr or greater.
3. Unlisted equipment.
4. Miscellaneous equipment when required by
the building official.
Subp.
3.
Placing equipment in operation.
After completion of the installation, all safety and
operating controls and venting shall be tested before placing the burner in
service. The correct input of fuel shall be determined and the fuel-to-air
ratio set. Each gas or fuel burner shall be adjusted to its proper input
according to the manufacturer's instructions. Overrating the burners or
appliance is prohibited. Btu/hr input range shall be appropriate to the
appliance.
1. The rate of flow of the
gas or fuel shall be adjusted to within plus or minus two percent of the
required Btu/hr rating at the manifold pressure specified by the manufacturer.
When the prevailing pressure is less than the manifold pressure specified, the
rates shall be adjusted at the prevailing pressure.
2. For conversion burners installed in hot
water (liquid) boilers or warm air furnaces, the rate of flow of the gas or
fuel in Btu/hr shall be adjusted to within plus or minus five percent of the
calculated Btu/hr heat loss of the building in which it is installed, or the
design load, and shall not exceed the design rate of the appliance.
3. For conversion burners installed in steam
boilers, the gas or fuel hourly input demand shall be adjusted to meet the
steam load requirements. The gas or fuel input demand necessitated by an
oversized boiler shall be established and added to the input demand for load
requirements to arrive at a total input demand.
Subp. 4.
Pilot operation.
Pilot flames shall ignite the gas or fuel at the main burner
or burners and shall be adequately protected from drafts.
Pilot flames shall not become extinguished during pilot
cycle when the main burner or burners are turned on or off in a normal manner,
either manually or by automatic controls.
Subp. 5.
Burner operation.
When testing to determine compliance with this section, care
shall be exercised to prevent the accumulation of unburned gas or fuel in the
appliance or flues that might result in explosion or fire.
1. The flames from each burner shall freely
ignite the gas or fuel from adjacent burners when operating at the prevailing
gas or fuel pressure and when the main control valve is regulated to deliver at
one-third of the fuel gas or fuel rate.
2. Burner flames shall not flash back after
immediate ignition nor after turning the fuel cock until the flow rate to the
burner is one-third the full supply.
3. Burner flames shall not flash back when
the gas or fuel is turned on or off by an automatic control
mechanism.
4. Main burner flames
shall ignite freely from each pilot when the main control valve is regulated to
one-third the full gas or fuel rate and when the pilot flame is reduced to a
minimum point at which it will actuate the safety device.
5. When ignition is made in a normal manner,
the flame shall not flash outside the appliance.
6. Burners shall not expel gas or fuel
through air openings when operating at prevailing pressure.
7. Burners shall have proper fuel air mixture
to ensure smooth ignition of the main burner.
8. Dual fuel burners may have controls common
or independent to both fuels. Transfer from one fuel to the other shall be by a
manual interlock switching system to prevent the gas and other fuel being used
simultaneously except by special permission from the building official. The
building official shall consider whether an exception will provide equivalent
safety. The transfer switch shall have a center off position and shall not pass
through the center off position without stopping in the center off
position.
Subp. 6.
Method of test.
1.
Operational checking. The flue gas, venting, safety and operating
controls of the appliance shall be checked to ensure proper and safe
operation.
2.
Method of test
- atmospheric type/induced draft type/fan-assisted type. The appliance
shall be allowed to operate until the stack temperature becomes stabilized
after which a sample of the undiluted flue products shall be taken from the
appliance flue outlet. The sample taken shall be analyzed for carbon monoxide,
carbon dioxide and oxygen. Stack temperature shall be noted.
Note: Appliance designs incorporating induced
draft assemblies may require a flue gas sample to be taken after the draft
regulator or induced draft fan.
3.1.
Performance standards for
atmospheric type.
a. Minimum of 75
percent efficiency as determined by flue gas analysis method at appliance flue
outlet.
b. Carbon monoxide
concentration in flue gas not greater than 0.04 percent on an air-free
basis.
c. Stack temperature not
greater than 480°F, plus ambient.
d. Carbon dioxide concentration between 6 and
9 percent, inclusive.
e. Oxygen
concentration between 4 and 10 percent, inclusive.
3.2.
Performance standards for induced
draft type/fan-assisted type.
a.
Minimum of 75 percent efficiency as determined by flue gas analysis method at
appliance flue outlet.
b. Carbon
monoxide concentration in flue gas not greater than 0.04 percent on an air free
basis.
c. Stack temperature not
greater than 480°F, plus ambient.
d. Oxygen concentration between 4 and 10
percent, inclusive, with carbon dioxide concentration between 6 and 9 percent,
inclusive. Note: Induced draft type and fan-assisted type
appliances may require a sample to be taken after the induced draft fan, which
may cause oxygen figures in excess of limits stated. In such cases, safe fuel
combustion ratios shall be maintained and be consistent with appliance listing.
4.
Method of
test - power type. The appliance shall be allowed to operate until the
stack temperature becomes stabilized after which a sample of the undiluted flue
products shall be taken from the appliance flue outlet. The sample shall be
analyzed for carbon monoxide, carbon dioxide and oxygen. Stack temperature
shall be recorded.
5.
Performance standards for power type.
a. Minimum of 80 percent efficiency as
determined by flue gas analysis method method at appliance flue
outlet.
b. Carbon monoxide
concentration in flue gas not greater than 0.04 percent.
c. Stack temperature not greater than
480°F plus ambient, or 125°F in excess of fluid temperature plus
ambient.
d. Carbon dioxide
concentration between 6 and 9 percent, inclusive.
e. Oxygen concentration between 3 and 10
percent, inclusive.
6.
After completion of the test of newly installed gas or fuel burner equipment as
provided in this section, complete test records shall be filed with the
building official on an approved form. The tag stating the date of the test and
the name of the installer shall be attached to the appliance at the main
valve.
7.
Oxygen
concentration.
a. The concentration of
oxygen in the undiluted flue products of gas or fuel burners shall in no case
be less than 3 percent nor more than 10 percent, shall be in conformance with
applicable performance standards and shall be consistent with the appliance
listing.
b. The allowable limit of
carbon monoxide shall not exceed 0.04 percent.
c. The flue gas temperature of a gas
appliance, as taken on the appliance side of the draft regulator, shall not
exceed applicable performance standards and shall be consistent with the
appliance listing.
8.
Approved oxygen trim system. The oxygen figures may not apply
when there is an approved oxygen trim system on the burner that is designed for
that use, including a low oxygen interlock when approved by the building
official. The building official shall consider whether an exception will
provide equivalent safety.
9.
Supervised start-up.a.
Supervised start-up may be required to verify safe operation of gas or fuel
burner and to provide documentation that operation is consistent with this
code, listing and approval. Supervised start-up is required for all fuel
burners in b, c, and d. Supervised startup requires that fuel burners shall be
tested in the presence of the building official in an approved manner. Testing
shall include safety and operating controls, input, flue gas analysis, and
venting. Flue gas shall be tested at high, medium and low fires. Provisions
shall be made in the system to allow firing test in warm weather. After
completion of the test of newly installed gas or fuel burner equipment as
provided in this section, complete test records shall be filed with the
building official on an approved form. The tag stating the date of the test and
the name of the installer shall be attached to the appliance at the main
valve.
b. Gas and fuel burners of
1,000,000 Btu/hr input or more require a supervised start-up as in a.
c. Installation of oxygen trim systems,
modulating dampers, or other draft control or combustion devices require a
supervised startup as in a.
d. All
direct fired heaters require a supervised start-up as in a.
10. A complete control diagram of
the installation and suitable operating instructions shall be supplied to the
building official.
Subp.
7.
Pressure regulators.
(a) General.
1. Regulators shall be provided with access
for servicing.
2. Regulators shall
be provided with a shutoff valve, union and test taps (both upstream and
downstream of the regulator) for servicing.
3. All regulators with inlet gas pressure
exceeding 14 inches water column pressure or used on an appliance having an
input exceeding 400,000 Btu/hr shall have an approved high pressure manual gas
valve in the supply piping upstream of the regulator.
4. All regulators with inlet gas pressure
exceeding 14 inches water column pressure or used on an appliance having an
input exceeding 400.000 Btu/hr shall be vented to the outdoors in separate
vents sized according to the manufacturer's specifications.
Exception: Regulators equipped with limiting
orifices installed in accordance with amended IFGC Section 410.3.
5. Regulators may not be vented
into a combustion chamber or an appliance vent.
6. Regulator vents shall terminate at least 3
feet (914 mm) from doors, operable windows, nonmechanical intake openings, and
openings into direct-vent appliances. The vent termination shall be located at
least 12 inches (305 mm) above grade and shall be suitably screened and hooded
to prevent accidental closure of the vent pipe.
7. All pounds-to-pounds and pounds-to-inches
regulators used as appliance regulators where downstream controls are not rated
for upstream pressure shall be of the full lock-up type.
(b) Appliance.
1. Appliance regulators shall be installed
consistent with the listing and approval of the equipment and the listing and
approval of the regulator manufacturer.
2. Each gas burner or appliance shall have
its own gas pressure regulator. This appliance regulator is in addition to any
pounds-to-pounds or pounds-to-inches regulators in the system.
Subp. 8.
Equipment information.
A. All
installations of gas or fuel burners with input above 400,000 Btu/hr and all
combination gas or fuel burners shall be approved before installation. The
following information shall be supplied if required by the building official.
1. Name, model, and serial number of the
burner.
2. Input rating and type of
fuel.
3. Name of the nationally
recognized testing laboratory that tested and listed the unit.
4. Name, model, and serial number of the
furnace or boiler that the burner will be installed in if not part of a
complete package.
5. A complete
wiring diagram showing the factory and fuel wiring installed or to be installed
including all controls, identified by the brand name and model
number.
6. A print of the gas or
fuel train from the manual shutoff to the appliance showing all controls that
will be installed, their names, model numbers, and approvals.
B. All installations of gas or
fuel burners with input above 400,000 Btu/hr and all combination gas and oil or
other combination fuel burners that are installed in new or renovated boiler or
equipment rooms, or are installed in a package with the boiler or furnace,
shall include the following information in addition to that required in item A,
subitems 1 to 6.
1. A complete piping diagram
from the supply source showing all components and materials identified by brand
name and model number with relevant approvals.
2. Detailed provisions for combustion air,
venting, and stacks.
3. A floor
plan drawn to scale showing all relevant equipment. Plans and specifications
shall be approved before proceeding with an installation.