Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 1323 - COMMERCIAL ENERGY CODE
Part 1323.0642 - SECTION 6.4.2, CALCULATIONS
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. 6.4.2.1.1 Climatic data design conditions.
ASHRAE 90.1 section 6.4.2.1 is amended by adding a subsection to read as follows:
Climatic data design conditions for the calculation of heating and cooling loads shall be determined by using either item 1 or 2:
Subp. 2. Table 6.4.2.1. Climatic data design conditions.
ASHRAE 90.1 section 6.4.2.1 is amended by adding a table to read as follows:
TABLE 6.4.2.1 CLIMATIC DATA DESIGN CONDITIONS
City |
Winter Design db °F |
Summer db °F/coincident wb °F |
Aitkin |
-28 |
82/72 |
Albert Lea |
-19 |
86/72 |
Alexandria |
-23 |
85/70 |
Bemidji |
-30 |
82/67 |
Brainerd |
-27 |
85/69 |
Cloquet |
-24 |
82/68 |
Crookston |
-28 |
84/70 |
Duluth |
-23 |
81/67 |
Ely |
-34 |
82/67 |
Eveleth |
-31 |
82/67 |
Faribault |
-21 |
88/73 |
Fergus Falls |
-26 |
85/70 |
Grand Marais |
-19 |
73/62 |
Grand Rapids |
-25 |
82/67 |
Hibbing |
-31 |
82/68 |
International Falls |
-35 |
82/67 |
Litchfield |
-20 |
86/72 |
Little Falls |
-26 |
86/70 |
Mankato |
-16 |
86/72 |
Minneapolis/St. Paul |
-17 |
88/72 |
Montevideo |
-19 |
88/73 |
Mora |
-24 |
86/70 |
Morris |
-23 |
86/72 |
New Ulm |
-19 |
88/73 |
Owatonna |
-19 |
86/72 |
Pequot Lakes |
-31 |
85/68 |
Pipestone |
-19 |
86/73 |
Redwood Falls |
-19 |
88/73 |
Rochester |
-19 |
85/72 |
Roseau |
-31 |
84/72 |
St. Cloud |
-24 |
86/71 |
Silver Bay |
-28 |
82/66 |
Thief River Falls |
-27 |
82/68 |
Tofte |
-14 |
75/61 |
Virginia |
-31 |
82/67 |
Warroad |
-32 |
82/70 |
Wheaton |
-23 |
86/72 |
Willmar |
-22 |
86/72 |
Winona |
-18 |
88/73 |
Worthington |
-16 |
86/71 |
Db = dry bulb temperature, degrees Fahrenheit
Wb = wet bulb temperature, degrees Fahrenheit