R402.1.1
Insulation, waterproofing, and
fenestration criteria. The building thermal envelope shall meet the
requirements of Table R402.1.1 based on the climate zone specified in chapter
3, and the requirements contained in section R402.2. Cast-in-place concrete and
masonry block foundation walls shall be waterproofed according to IRC section
R406 and the following requirements:
1. The
waterproofing shall extend from the top interior wall edge, across the top of
the wall, and down the exterior wall face to the top of the footing. If a full
width, closed-cell material is installed to create a seal between the sill
plate and the top of the foundation wall, the installation is deemed to meet
the requirements for the top of the wall waterproofing.
2. If the walls are exposed to the exterior
environment, the waterproofing system shall have a rigid, opaque, and
weather-resistant protective covering to prevent degradation of the
waterproofing system. The protective covering shall cover the exposed
waterproofing and extend a minimum of 6 inches (152 mm) below grade. The
protective covering system shall be flashed in accordance with IRC section
R703.8.
R402.1.1.1
Integral
foundation insulation requirements. Any insulation assembly installed
integral to the foundation walls shall be manufactured for that intended use
and installed according to the manufacturers installation
instructions.
R402.1.1.2
Exterior draining foundation insulation requirements. Any
insulation assembly installed on the exterior of the foundation walls and on
the perimeter of slabs-on-grade that permits water drainage shall:
1. be made of water-resistant materials
manufactured for that intended use;
2. be installed according to the
manufacturers installation instructions;
3. comply with either ASTM C578, C612, or
C1029, as applicable; and
4. have a
rigid, opaque, and weather-resistant protective covering to prevent the
degradation of the insulations thermal performance. The protective covering
shall cover the exposed exterior insulation and extend a minimum of 6 inches
(152 mm) below grade. The insulation and protective covering system shall be
flashed in accordance with IRC section R703.8.
R402.1.1.3
Exterior nondraining
foundation insulation requirements. Any insulation assembly installed on
the exterior of the foundation walls or on the perimeter of slabs-on-grade that
does not permit bulk water drainage shall:
1.
be made of water-resistant materials manufactured for that intended
use;
2. be installed according to
the manufacturers installation instructions;
3. comply with either ASTM C578 or C1029, as
applicable;
4. be covered with a
6-mil polyethylene slip sheet over the entire exterior surface; and
5. have a rigid, opaque, and
weather-resistant protective covering to prevent degradation of the insulations
thermal performance. The protective covering shall cover the exposed exterior
insulation and extend a minimum of 6 inches (152 mm) below grade. The
insulation and protective covering system shall be flashed in accordance with
IRC section R703.8.
R402.1.1.4
Interior foundation
insulation requirements. Any insulation assembly installed on the
interior of foundation walls shall meet the following requirements:
1. Masonry foundation walls shall be drained
through each masonry block core to an approved interior drainage
system.
2. If a frame wall is
installed, it shall not be in direct contact with the foundation
wall.
3. The insulation assembly
shall comply with the interior air barrier requirements of section
R402.4.
4. The insulation assembly
shall comply with section R402.1.1.5, R402.1.1.6, or R402.1.1.7, as
applicable.
R402.1.1.5
Rigid interior insulation. Rigid interior insulation shall comply
with ASTM C578 or ASTM C1289 and the following requirements:
1. For installation:
a. the insulation shall be in contact with
the foundation wall surface;
b.
vertical edges shall be sealed with acoustic sealant;
c. all interior joints, edges, and
penetrations shall be sealed against air and water vapor penetration;
d. continuous acoustic sealant shall be
applied horizontally between the foundation wall and the insulation at the top
of the foundation wall; and
e.
continuous acoustic sealant shall be applied horizontally between the basement
floor and the bottom insulation edge.
2. The insulation shall not be penetrated by
the placement of utilities, fasteners, or connectors used to install a frame
wall, with the exception of through penetrations.
3. Through penetrations shall be sealed
around the penetrating products.
R402.1.1.6
Spray-applied interior foam
insulation. Spray-applied interior foam insulation shall comply with the
following:
1. Closed-cell foam:
a. The foam shall comply with ASTM C1029 and
have a permeance not greater than 0.8, in accordance with ASTM E96 procedure A,
and a permeance of not less than 0.3, in accordance with ASTM E96 procedure
B.
b. The foam shall be sprayed
directly onto the foundation wall surface. There shall be a 1-inch minimum gap
between the foundation wall surface and any framing.
c. The insulation surface shall not be
penetrated by the placement of utilities, fasteners, or connectors used to
install a frame wall, with the exception of through penetrations.
d. Through penetrations shall be sealed
around the penetrating products.
2. Open-cell foam:
a. The foam shall be sprayed directly onto
the foundation wall surface. There shall be a 1-inch minimum gap between the
foundation wall surface and any framing.
b. The insulation surface shall not be
penetrated by the placement of utilities, fasteners, or connectors used to
install a frame wall, with the exception of through penetrations.
c. Through penetrations shall be sealed
around the penetrating product.
d.
A vapor retarder and air barrier shall be applied to the warm-in-winter side of
the assembly with a permeance not greater than 1.0, in accordance with ASTM E96
procedure A, and a permeance not less than 0.3, in accordance with ASTM E96
procedure B.
R402.1.1.7
Fiberglass batt interior
insulation. Fiberglass batt insulation shall comply with the following:
1. The above-grade exposed foundation wall
height shall not exceed 1.5 ft.
2.
The top and bottom plates shall be air sealed to the foundation wall surface
and the basement floor.
3. A vapor
retarder and air barrier shall be applied to the warm in winter side of the
wall with a permeance not greater than 1.0 in accordance with ASTM E96
procedure A and a permeance not less than 0.3 in accordance with ASTM E96
procedure B meeting the following requirements:
a. the vapor and air barrier shall be sealed
to the framing with construction adhesive or equivalent at the top and bottom
plates and where the adjacent wall is insulated;
b. the vapor and air barrier shall be sealed
around utility boxes and other penetrations; and
c. all seams in the vapor and air barrier
shall be overlapped at least 6 inches and sealed with compatible sealing tape
or equivalent.
R402.1.1.8
Foundation wall insulation
performance option. Insulated foundation systems designed and installed
under the performance option shall meet the requirements of this section and
the foundation, basement, or crawl space wall equivalent U-factor from Table
402.1.3.
1.
Water separation
plane. The foundation shall be designed and built to have a continuous
water separation plane between the interior and exterior. The interior side of
the water separation plane shall:
a. have a
stable annual wetting and drying cycle whereby foundation wall system water
(solid, liquid, and vapor) transport processes produce no net accumulation of
ice or water over a full calendar year and the foundation wall system is free
of absorbed water for at least 4 months over a full calendar year;
b. prevent conditions of moisture and
temperature to prevail for a time period favorable to mold growth for the
material used; and
c. prevent
liquid water from the foundation wall system from reaching the foundation floor
system at any time during a full calendar year.
2.
Documentation. The foundation
insulation system designer shall provide documentation certified by a
professional engineer licensed in Minnesota demonstrating how the requirements
of this section are fulfilled. The foundation insulation system designer shall
also specify the design conditions for the wall and the design conditions for
the interior space for which the water separation plane will meet the
requirements of this section. The foundation insulation system designer shall
provide a label disclosing these design conditions. The label shall be posted
according to section R401.3.
3.
Installation. The water separation plane shall be designed and
installed to prevent external liquid or capillary water flow across it after
the foundation is backfilled.
4.
Foundation air barrier. The foundation insulation system shall be
designed and installed to have a foundation air barrier system between the
interior and the exterior. The foundation air barrier system shall be a
material or combination of materials that is continuous with all joints sealed
and is durable for the intended application. Material used for the foundation
air barrier system shall have an air permeability not to exceed 0.004
ft3/min.ft2 under a
pressure differential of 0.3 inches water (1.57 psf) (0.02
L/s.m2 at 75Pa) as determined by either commonly
accepted engineering tables or by being labeled by the manufacturer as having
these values when tested according to ASTM E2178.