Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 1309 - INTERNATIONAL RESIDENTIAL CODE
Part 1309.0903 - SECTION R903, WEATHER PROTECTION
Current through Register Vol. 49, No. 13, September 23, 2024
IRC section R903.2.1 is amended as follows:
R903.2.1 Locations. Flashings shall be installed at wall and roof intersections, wherever there is a change in roof slope or direction and around roof openings. A kick-out flashing shall be installed to divert the water away from where the eave of a sloped roof intersects a vertical sidewalk The kick-out flashing on the roof shall be a minimum of 2-1/2 inches (63.5 mm) long. Where flashing is of metal, the metal shall be corrosion-resistant with a thickness of not less than 0.019 inch (0.5 mm) (No. 26 galvanized sheet).
Exception: Kick-out flashings are not required when only re-roofing existing buildings and structures.
Statutory Authority: MS s 16B.59; 16B.61; 16B.64; 326B.101; 326B.106; 326B.13