Current through Register Vol. 49, No. 13, September 23, 2024
Subpart
1.
IBC Section 3001, General.
IBC Section 3001 is amended to read as follows:
3001.1
Scope. This chapter
governs the design, construction, installation, alteration, and repair of
elevators and conveying systems and their components.
3001.2
Referenced standards.
Except as otherwise provided by applicable law, the design, construction,
installation, alteration, repair, and maintenance of elevators and conveying
systems and their components shall conform to Minnesota Rules, chapter
1307.
3001.3
Accessibility. Passenger elevators required to be accessible by the 2006
IBC, Chapter 11, shall conform to Minnesota Rules, chapter 1341.
3001.4
Change in use. A change
in use of an elevator from freight to passenger, passenger to freight, or from
one freight class to another freight class shall comply with Minnesota Rules,
chapter 1307.
Subp. 2.
IBC Section 3002, Hoistway enclosures.
IBC Section 3002 is amended to read as follows:
3002.1
Hoistway enclosure
protection. Elevators, dumbwaiters, and other hoistway enclosures shall
be shaft enclosures complying with Section 707.
3002.1.1
Opening protectives.
Openings in hoistway enclosures shall be protected as required in Chapter 7.
Exception: The elevator car doors and the
associated hoistway enclosure doors at the floor level designated for recall in
accordance with Section 3003.2 shall be permitted to remain open during Phase I
Emergency Recall Operation.
3002.1.2
Hardware. Delete this
section in its entirety.
3002.2
Number of elevator cars in a
hoistway. Where four or more elevator cars serve all or the same portion
of a building, the elevators shall be located in at least two separate
hoistways. Not more than four elevator cars shall be located in any single
hoistway enclosure.
3002.3
Emergency signs. An approved pictorial sign of a standardized design
shall be posted adjacent to each elevator call station on all floors
instructing occupants to use the exit stairways and not to use the elevators in
case of fire. The sign shall be as illustrated in ASME A17.1-2004; Appendix O.
The emergency sign shall not be required for elevators that are part of an
accessible means of egress complying with Section 1007.4.
3002.4
Elevator car to accommodate
ambulance stretcher. Where elevators are provided in buildings four or
more stories above grade plane or four or more stories below grade plane, at
least one elevator shall be provided for fire department emergency access to
all floors. The elevator car shall be of such a size and arrangement to
accommodate a 24-inch by 84-inch (610 mm by 2133.5 mm) ambulance stretcher in
the horizontal, open position and shall be identified by the international
symbol for emergency medical services (star of life). The symbol shall not be
less than three inches (76 mm) high and shall be placed inside on both sides of
the hoistway door frame.
Exception: When approved by the authority having
jurisdiction, passenger elevators to be installed in existing buildings where
existing hoistway configuration or technical infeasibility prohibits strict
compliance with the minimum inside car size, the minimum inside car area may be
reduced to not less than 48 inches by 48 inches.
3002.5
Emergency doors. Where
an elevator is installed in a single blind hoistway or on the outside of a
building, there shall be installed in the blind portion of the hoistway or
blank face of the building, an emergency door in accordance with ASME
A17.1-2004.
3002.6
Prohibited doors. Doors, other than hoistway doors, elevator car doors,
and smoke control doors, when required, shall be prohibited at the point of
access to an elevator car. Smoke control doors shall be:
1. held open during normal operation by a
"hold open" device that is activated for closure by fire or smoke sensing
devices located in the elevator lobby or its immediate vicinity; and
2. readily openable from the car side without
a key, tool, special knowledge, or effort when closed.
3002.7
Common enclosure with
stairway. Elevators shall not be in a common shaft enclosure with a
stairway.
3002.8
Glass in
elevator enclosures. Glass in elevator enclosures shall comply with
Section 2409.1.
Subp. 3.
IBC Section 3003, Emergency operations.
IBC Section 3003 is amended to read as follows:
3003.1
Standby power. In
buildings and structures where standby power is required or furnished to
operate an elevator, the operation shall be in accordance with Sections
3003.1.1 through 3003.1.4.
3003.1.1
Manual transfer. Standby power shall be manually transferable to all
elevators in each bank.
3003.1.2
One elevator. Where only one elevator is installed, the elevator
shall automatically transfer to standby power within 60 seconds after failure
of normal power.
3003.1.3
Two or more elevators. Where two or more elevators are controlled by a
common operating system, all elevators shall automatically transfer to standby
power within 60 seconds after failure of normal power where the standby power
source is of sufficient capacity to operate all elevators at the same time.
Where the standby power source is not of sufficient capacity to operate all
elevators at the same time, the elevators shall operate according to ASME
A17.1-2004 2.27.2.
3003.1.4
Venting. Where standby power is connected to elevators, machine room
ventilation or air conditioning, if provided, shall be connected to the standby
power source.
3003.2
Firefighters' emergency operation. Elevators shall be provided
with Phase I emergency recall operation and Phase II emergency in-car operation
in accordance with ASME A17.1-2004.
Subp. 4.
IBC Section 3004, Hoistway
venting.
IBC Section 3004 is amended to read as follows:
3004.1
Vents required.
Hoistways of elevators and dumbwaiters having a travel of 25 feet or more shall
be provided with a means for venting smoke and hot gases to the outer air in
case of fire.
Exceptions:
1. In occupancies of other than Groups R-1,
R-2, I-1, I-2, as defined in Minnesota Rules, chapter 1305, and similar
occupancies with overnight sleeping quarters, venting of hoistways is not
required when the building is equipped throughout with an approved automatic
sprinkler system installed in accordance with the 2006 International Building
Code, Section 903.3.1.1 or 903.3.1.2 and similar local codes.
2. Sidewalk elevator hoistways are not
required to be vented.
3004.2
Location of vents. Vents
shall be located directly (directly is defined as being as close as technically
possible to the top of the hoistway including the supporting structures located
at the top of the hoistway) below the top of the hoistway and shall be open
either directly to the outer air or through noncombustible ducts to the outer
air. Noncombustible ducts shall be permitted to pass through the elevator
machine room provided the portions of the ducts located outside the hoistway or
machine room are enclosed by construction having not less than the fire
protection rating required for the hoistway. Holes in the machine room floors
for the passage of ropes, cables, or other moving elevator equipment shall be
limited so as not to provide greater than two inches (51 mm) of clearance on
all sides.
1. Protective grilles must be
installed at vent openings in the top of the hoistway to prevent people from
falling into the hoistway. The protective grilles must be securely mounted to
the building structure.
2.
Interconnection of separate hoistways for the purpose of venting is
prohibited.
3. Vents must be
operated by a keyed manual remote device and equipped with a remote visual
LED-type indicator device for indicating the full open position.
a. The indicator device shall be activated by
a device having a direct mechanical connection to vent shutters.
b. The keyed manual remote control device
shall have two positions: vent closed and vent open. The markings for both
positions shall be permanent. The key shall be removable only in the closed
position.
c. The keyed manual
remote control device must be located adjacent to the fire control panel, if
provided, or in the elevator lobby of a designated floor. The designated floor
shall be approved by the authority having jurisdiction.
d. The keyed manual remote control device may
not be co-located with any operating devices for the elevators.
3004.3
Area of
vents. Except as provided for in Section 3004.3.1, the area of the vents
shall not be less than 3-1/2 percent of the area of the hoistway nor less than
three square feet (0.28 m2) for each elevator car
and not less than 3-1/2 percent nor less than 0.5 square foot (0.047
m2) for each dumbwaiter car in the hoistway,
whichever is greater.
3004.3.1
Reduced
vent area. Where mechanical ventilation conforming to the International
Mechanical Code is provided, a reduction in the required vent area is allowed,
provided that all of the following conditions are met:
1. The occupancy is not in Group R-1, R-2,
I-1, or I-2, as defined in chapter 1305, or of a similar occupancy with
overnight sleeping quarters.
2. The
vents required by Section 3004.2 do not have outside exposure.
3. The hoistway does not extend to the top of
the building.
4. The hoistway and
machine room exhaust fan is automatically reactivated by thermostatic
means.
5. Equivalent venting of the
hoistway is accomplished.
3004.4
Plumbing and mechanical
systems. Delete this section in its entirety.
Subp. 5.
IBC Section 3005, Conveying
systems.
IBC Section 3005 is amended to read as follows:
3005.1
General. Escalators,
moving walks, conveyors, personnel hoists, and material hoists shall comply
with Minnesota Rules, chapter 1307.
3005.2
Escalators and moving
walks. Escalators and moving walks shall be constructed of approved
noncombustible and fire-retardant materials. This requirement shall not apply
to electrical equipment, wiring, wheels, handrails, and the use of 1/28-inch
(0.9 mm) wood veneers on balustrades backed up with noncombustible materials.
3005.2.1
Enclosure. Escalator
floor openings shall be enclosed with shaft enclosures complying with Section
707.
3005.2.2
Escalators. Where provided in below-grade transportation stations,
escalators shall have a clear width of 32 inches (815 mm) minimum.
Exception: The clear width is not required in
existing facilities undergoing alterations.
3005.3
Conveyors. Conveyors and
conveying systems shall comply with ASME B20.1-2003.
3005.3.1
Enclosure. Conveyors
and related equipment connecting successive floors or levels shall be enclosed
with shaft enclosures complying with Section 707.
3005.3.2
Conveyor safeties.
Power-operated conveyors, belts, and other material-moving devices shall be
equipped with automatic limit switches that will shut off the power in an
emergency and automatically stop all operation of the device.
3005.4
Personnel and
material hoists. Personnel and material hoists shall be designed
utilizing an approved method that accounts for the conditions imposed during
the intended operation of the hoist device. The design shall include, but is
not limited to, anticipated loads, structural stability, impact, vibration,
stresses, and seismic restraint. The design shall account for the construction,
installation, operation, and inspection of the hoist tower, car, machinery and
control equipment, guide members, and hoisting mechanism. Additionally, the
design of personnel hoists shall include provisions for field testing and
maintenance that will demonstrate that the hoist device functions in accordance
with the design. Field tests shall be conducted upon the completion of an
installation or following a major alteration of a personnel hoist.
Subp. 6.
IBC Section 3006,
Machine rooms.
IBC Section 3006 is amended to read as follows:
3006.1
Access. An approved
means of access shall be provided to elevator machine rooms and overhead
machinery spaces.
3006.2
Venting. Delete this section in its entirety.
3006.3
Pressurization. The
elevator machine room serving a pressurized elevator hoistway shall be
pressurized upon activation of a heat or smoke detector located in the elevator
machine room.
3006.4
Machine
rooms and machinery spaces. Elevator machine rooms and machinery spaces
shall be enclosed with construction having a fire-resistance rating not less
than the required rating of the hoistway enclosure served by the machinery.
Openings shall be protected with assemblies having a fire-resistance rating not
less than that required for the hoistway enclosure doors.
3006.5
Shunt trip. Delete this
section in its entirety.
3006.6
Plumbing systems. Delete this section in its entirety.
Statutory Authority: MS s 16B.59; 16B.61;
16B.64; 16B.748;
326B.101;
326B.106;
326B.13;
326B.187