Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 1305 - ADOPTION OF INTERNATIONAL BUILDING CODE
Part 1305.1020 - SECTION 1020, CORRIDORS
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. IBC Table 1020.1.
IBC Table 1020.1 is amended as follows:
TABLE 1020.1 CORRIDOR FIRE-RESISTANCE RATING
REQUIRED FIRE-RESISTANCE RATING (hours) | |||
OCCUPANCY | OCCUPANT LOAD SERVED BY CORRIDOR | Without sprinkler system | With sprinkler systemc |
H-1, H-2, H-3 | All | Not permitted | 1 |
H-4, H-5 | Greater than 30 | Not permitted | 1 |
A, B, E, F, M, S U | , Greater than 30 | 1 | 0 |
R | Greater than 10 | 1 | 0.5c/1d |
I-2a | All | Not permitted | 0 |
I-1, I-3 | All | Not permitted | 1b |
I-4 | All | 1 | 0 |
a For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3.
b For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8.
c Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, where allowed.
d Group R-3 and R-4 buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.3.
Subp. 2. IBC section 1020.6.
IBC section 1020.6 is amended by modifying the exceptions to read as follows:
Exceptions: