Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 1305 - ADOPTION OF INTERNATIONAL BUILDING CODE
Part 1305.0915 - IBC [F] SECTION 915, CARBON MONOXIDE DETECTION
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. IBC [F] section 915.1.
IBC [F] section 915.1 and subsection 915.1.1 are amended to read as follows:
Exception: In multi-family dwellings, approved and operational carbon monoxide alarms may be installed between 15 and 25 feet of carbon monoxide-producing central fixtures and equipment provided there is a centralized alarm system or other approved mechanism for responsible parties to hear the alarms at all times.
(Sections 915.1.2 through 915.1.6 remain unchanged.)
Subp. 2. IBC [F] section 915.2.
IBC [F] section 915.2 and subsections 915.2.1 and 915.2.2 are amended to read as follows:
Exception: Carbon monoxide detection shall be allowed to be installed outside of each separate sleeping area within ten feet of the sleeping unit where the sleeping unit or its attached bathroom does not contain a fuel-burning appliance and is not served by a forced air furnace.
(Section 915.2.3 remains unchanged.)