Minnesota Administrative Rules
Agency 151 - Labor and Industry Department
Chapter 1305 - ADOPTION OF INTERNATIONAL BUILDING CODE
Part 1305.0909 - SECTION 909, SMOKE CONTROL SYSTEMS
Universal Citation: MN Rules 1305.0909
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. [Repealed, 39 SR 1605; 44 SR 609 effective 3/31/2020]
Subp. 1a. IBC [F] section 909.1.
IBC [F] section 909.1 is amended to read:
909.1
Scope and purpose. This
section applies to mechanical or passive smoke control systems for new
buildings or portions of new buildings when they are required by other
provisions of this code. The purpose of this section is to establish minimum
requirements for the design, installation, and acceptance testing for smoke
control systems that are intended to provide a tenable environment for the
evacuation or relocation of occupants and for fire suppression and overhaul
efforts. These provisions are not intended for the preservation of contents or
the timely restoration of operations.
Subp. 1b. IBC [F] section 909.4.6.
IBC [F] section 909.4.6 is amended to read:
909.4.6
Duration of operation.
All portions of the active or passive smoke control system shall be capable of
continued operation after detection of the fire event for a period of not less
than 20 minutes. System design shall be for 20 minutes; however, fans shall
continue to operate after 20 minutes and shall continue to operate
automatically for smoke removal during fire suppression and overhaul efforts
for a minimum of 5 minutes for every 10 feet vertically of protected
space.
Subp. 1c. IBC [F] section 909.4.8.
IBC [F] section 909.4 is amended by adding a section to read:
909.4.8
Door opening
force. With any of the design methods allowed by Section 909, the door
opening force, latch release, and set-in-motion force shall comply with Section
1010.1.3 requirements when the system is in smoke control mode.
Subp. 1d. IBC [F] section 909.22.
IBC [F] section 909 is amended by adding a section to read as follows:
909.22
High-rise and
covered mall smoke-exhaust systems. High-rise buildings, not provided
with a smoke control or a post-fire smoke exhaust system, shall be equipped
with a smoke removal system installed in accordance with this code. Covered
mall buildings exceeding 50,000 square feet (4,645
m2) in floor area, excluding anchor stores, and not
provided with a smoke control system, shall be equipped with a post-fire smoke
exhaust system installed in accordance with this code.
Subp. 2. [Repealed, 44 SR 609 effective 3/31/2020]
Statutory Authority: MS s 16B.37; 16B.59 to 16B.76; 326B.101 to 326B.194
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.