Part 1305.0403 - SECTION 403, HIGH-RISE BUILDINGS
Universal Citation: MN Rules 1305.0403
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. IBC section 403.2.1.2.
IBC section 403.2.1.2 is deleted in its entirety.
Subp. 2. [Repealed, ]
Subp. 3. IBC section 403.4.8.3.
IBC section 403.4.8.3 is amended to read as follows:
403.4.8.3
Standby power loads.
The following are classified as standby power loads:
1. power and lighting for the fire command
center required by Section 403.4.6;
2. ventilation and automatic fire detection
equipment for smokeproof enclosures; and
3. passenger elevators serving occupied
floors more than 75 feet (22, 860 mm) above the lowest level of fire department
vehicle access.
Statutory Authority: MS s 16B.37; 16B.59 to 16B.76; 326B.101 to 326B.194
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.