Minnesota Administrative Rules
Agency 144 - Health Department
Chapter 4725 - WELLS AND BORINGS
WELL AND BORING GENERAL CONSTRUCTION AND USE REQUIREMENTS
Part 4725.2550 - PLASTIC CASING AND COUPLING REQUIREMENTS
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. General requirements.
Plastic casing and couplings used in the permanent construction of a well or boring must:
Standard dimension ratios (SDR) and water pressure ratings (PR) at 23 degrees Celsius (73 degrees Fahrenheit) for nonthreaded polyvinyl chloride (PVC) and acrylonitrile-butadiene-styrene (ABS) plastic casing equal to or greater than 200 psi are as follows:
SDR | PVC 1120 | PVC 1220 | PVC 2112 | PVC 2116 | PVC 2120 |
13.5 | 315 psi | 315 psi | 200 psi | 250 psi | 315 psi |
17 | 250 psi | 250 psi | - | 200 psi | 250 psi |
21 | 200 psi | 200 psi | - | - | 200 psi |
SDR | ABS 1316 | ABS 2112 |
13.5 | 250 psi | 200 psi |
17 | 200 psi | - |
The sources of the pressure rating in item B are the American Society for Testing and Materials Standard D2241-04a "Standard Specifications for Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)" Table XI.I Standard Thermoplastic Pipe Dimension Ratios (SDR) and Water Pressure Rating (PR) at 73 degrees Fahrenheit (23 degrees Celsius) for Nonthreaded Plastic Pipe; and Standard D2282-99e "Standard Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe (SDR-PR)," Table XI.I Standard Plastic Pipe Dimension Ratios (SDR) and Water Pressure Ratings (PR) at 73 degrees Fahrenheit (23 degrees Celsius) for Nonthreaded ABS Plastic Pipe.
Subp. 2. Additional approved fittings and couplings.
In addition to the plastic couplings approved under subpart 1, the following fittings and couplings may be used to connect a steel pitless unit or screen to plastic casing:
Subp. 3. Compliance with ANSI/NSF standard required.
All plastic casings, couplings, components, and related joining materials including solvents, cements, or primers used in the construction of a well or boring must conform with the requirements of ANSI/NSF Standard 61-2003e or the health effects portion of ANSI/NSF Standard 14-2003 and be tested as conforming by an agency certified by the ANSI. Conformance to the ANSI/NSF standard must be coded, stamped, or marked on the casings, couplings, components, and related joining materials including solvents, cements, or primers.
Statutory Authority: MS s 103I.101; 103I.111; 103I.205; 103I.221; 103I.301; 103I.401; 103I.451; 103I.501; 103I.525; 103I.531; 103I.535; 103I.541; 103I.621; 144.05; 144.12; 144.383; 157.04; 157.08; 157.09; 157.13