WATER-SUPPLY WELLS
Part 4725.5350 - PRESSURE TANKS FOR WATER-SUPPLY WELLS
Universal Citation: MN Rules 4725.5350
Current through Register Vol. 49, No. 13, September 23, 2024
Subpart 1. Venting.
A pressure relief or air release valve on a pressure tank that contains subterranean gas and is located in a building must be vented to the outside.
Subp. 2. Buried tanks.
A buried or partially buried pressure tank installed on a water-supply well must:
A. be
identified with the manufacturer's name, a serial number, the allowable working
pressure, and the year fabricated;
B. have an interior coating that complies
with ANSI/NSF Standard 61-2003e if the tank has an interior coating in contact
with water;
C. have a minimum
one-fourth inch wall thickness for a steel pitless adapter tank attached
directly to the well casing;
D.
have all connections to the pressure tank welded or threaded; and
E. be installed above the water
table.
Statutory Authority: MS s 103I.101; 103I.111; 103I.205; 103I.221; 103I.301; 103I.401; 103I.451; 103I.501; 103I.525; 103I.531; 103I.535; 103I.541; 103I.621; 144.05; 144.12; 144.383; 157.04; 157.08; 157.09; 157.13
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.