Subpart 1. General.
When enclosure, removal, or encapsulation is completed during an abatement, clearance air sampling must be performed to ensure that fiber levels in the air within the containment area do not exceed the clearance standard or alternative clearance standard.
A. The asbestos containment area must not be
reoccupied until compliance with subitem (1) or (2) is achieved:
(1) each of five clearance air samples,
collected according to subpart 2, is less than or equal to the clearance
standard or the alternative clearance standard; or
(2) for a small residential abatement each of
three clearance air samples, collected according to subpart 2, are less than or
equal to the clearance standard.
B. If any clearance air sample result exceeds
the clearance standard or alternative clearance standard, or any clearance air
sample is too heavily loaded to be quantitatively analyzed, the containment
area must be recleaned and reinspected according to part 4620.3575, subpart 4.
Following compliance with part 4620.3575, subpart 4, clearance air sampling
must be repeated according to this subpart.
Subp. 2. Clearance air sampling procedures.
Clearance air sampling must be conducted in the containment area after the containment has been cleaned thoroughly, dried completely, and passed the visual inspection required under part 4620.3575, subpart 4.
A. The critical barriers specified in part
4620.3567 must remain in place.
B.
The decontamination unit must remain in place and remain operational.
C. Negative pressure within the containment
must be maintained until analysis of clearance air samples is
complete.
D. The clearance air
sampling sites must be selected on a random basis within the containment to
provide unbiased and representative sampling of the air within the
containment.
E. Clearance air
sampling must be performed with equipment that has been cleaned and
decontaminated before use.
F.
Clearance air sampling must be conducted as specified in subitems (1) to (3).
(1) Except for clearance air sampling
specified in part 4620.3581, subpart 6, item G, subitem (2), before clearance
air sampling, all surfaces must be blown with the air from a one horsepower
leaf blower to agitate the air and reentrain loose fibers in the air within the
containment.
(2) Except for
clearance air sampling specified in part 4620.3581, subpart 6, item G, subitem
(2), stationary fans must be placed in locations that do not interfere with air
monitoring equipment. Fan air must be directed toward the ceiling. One fan must
be used for each 10,000 cubic feet of containment area.
(3) When electrical power is provided, the
power supply equipment must be underwriter laboratory approved and not
modified. Wiring must be grounded and the circuits protected by ground fault
interrupt devices.
G.
Equipment such as fans and pumps must be wet wiped with clean water and
disposable wipes before removal from the containment.
Statutory Authority: MS s 144.05; 326.70 to 326.81
Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.