Minnesota Administrative Rules
Agency 105 - Agriculture Department
Chapter 1513 - ANHYDROUS AMMONIA
SYSTEMS USING STATIONARY, PIER-MOUNTED, OR SKID-MOUNTED ABOVEGROUND OR UNDERGROUND, NONREFRIGERATED STORAGE
Part 1513.0320 - CONTAINER VALVES, ACCESSORIES, AND DISCHARGE CONNECTIONS

Universal Citation: MN Rules 1513.0320

Current through Register Vol. 48, No. 39, March 25, 2024

Subpart 1. Excess flow valves.

All vapor and liquid connections, except for pressure relief valves and those specifically exempted in part 1513.0150, subparts 5 and 6, must be equipped with approved excess flow valves. Back-pressure check valves are acceptable in container filling connections. Alternatively, vapor and liquid connections covered by this subpart may be fitted with quick-closing internal valves which, except during operating periods, shall remain closed. If internal valves are not practical, external quick-closing valves may be used according to part 1513.0150, subpart 6, and with appropriate protection as required in part 1513.0370.

Subp. 2. Pressure gauge.

Each storage container must be provided with a pressure gauge graduated from 0 to 400 psig. Gauges must be designated for use in ammonia service.

Subp. 3. Vapor equalizing connection.

All containers must be equipped with a vapor equalizing connection.

Statutory Authority: MS s 18C.121

Disclaimer: These regulations may not be the most recent version. Minnesota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.