Current through Vol. 24-16, September 15, 2024
Rule 7.
(1) The
following shall be the protocol for testing animal contact current when the
utility utilizes a grounded distribution system with a primary neutral
conductor, except that a utility may submit an alternative protocol to the
commission for approval to determine the utility contribution to animal contact
current:
(a) Identify animal contact location
to be tested.
(b) Measure and
record the steady state animal contact voltage (AcV) at the animal contact
location concurrently with the neutral-to-earth voltage at utility primary
distribution system (NpEV) and at the animal building panel (NbEV) for a period
of 72 hours during a mutually agreed upon time frame to determine the maximum
probable level of animal contact current under normal operating
conditions.
(c) Determine the
highest level of animal contact voltage that occurred during the 72?hour
monitoring, and the primary neutral-to-earth voltage at the utility transformer
location that occurred at that same time.
(d) Turn off farm electrical load and apply a
temporary electrical load at the utility transformer to produce the same level
of neutral-to-earth voltage at the utility transformer as found in subdivision
(c) of this subrule. Measure the animal contact voltage again.
(e) Using the animal contact voltage measured
in subdivision (d) of this subrule, compare it to the animal contact voltage
measured in subdivision (b) of this subrule to determine the utility
contribution to animal contact current using Ohm's law.
(2) The following measurement and monitoring
procedures shall be used:
(a) Conduct an
evaluation of animal contact voltage (AcV) to determine the location that may
result in the maximum probable current flow through the animal. This location
shall be called the chosen animal contact location and shall be monitored for a
period of 72 hours during a mutually agreed upon time frame. The following
shall apply:
(i) Identify all probable animal
contact locations where an animal is likely to simultaneously make contact with
2 points between which a voltage may be present. This includes locations of
concern identified by the complainant.
(ii) Measure animal contact voltage (AcV)
with a nominal 500-ohms shunt resistor (R shunt) placed across the input leads
of the voltage measuring instrument.
(iii) Measurements to the floor or earth
shall be made with a metal plate with an area of 12 to 16 square inches, and
with a conductive material between the metal plate and the floor or
earth.
(iv) Measuring instruments
shall be capable of digitally recording necessary measurements to determine the
steady state voltage. Measuring instruments shall be calibrated to factory
specifications by a recognized and certified laboratory. The commission shall
determine the acceptability of each measuring device. The data recorded shall
become part of the report.
(b) Establish the locations from which to
monitor neutral-to-earth voltage (NpEV and NbEV) measurements. The following
procedures shall be followed:
(i) Establish
an earth reference ground by installing a metal rod or pipe, with a diameter
not less than 1/2 inch, in the earth to a depth of not less than 1 foot and
located not less than 50 feet from any underground water pipes, utility lines,
metal equipment making contact with the earth, or grounding electrodes of any
electrical system.
(ii) Determine
which farm electrical panel serves the equipment or general location of the
animal contact location. This electrical panel shall be called the animal
building panel. The neutral-to-earth voltage at the animal building panel
(NbEV) shall be measured from the panel grounding terminal to the reference
ground established in subdivision (b)(i) of this subrule. This measurement can
be used to validate that the animal contact voltage (AcV) was not inadvertently
disconnected or disturbed during the 72-hour monitoring period.
(iii) The neutral-to-earth voltage at the
utility's primary distribution neutral conductor (NpEV) shall be measured from
the utility's primary neutral grounding electrode conductor at the utility
transformer serving the farm to the reference ground established in subdivision
(b)(i) of this subrule.
(c) Simultaneously measure and record the 3
steady state voltages, AcV, NpEV and NbEV, for a period of 72 hours during a
mutually agreed upon time frame. If more than 1 instrument is used, then the
instrument clocks shall be synchronized. The following shall be used:
(i) The animal contact voltage (AcV) with a
nominal 500-ohm shunt resistor (R shunt) placed across the input leads of the
voltage measuring instrument.
(ii)
The neutral-to-earth voltage at the animal building panel (NbEV).
(iii) The neutral-to-earth voltage of the
utility primary distribution system neutral (NpEV) at the utility transformer
serving the farm.
(3) Determine the utility contribution to
animal contact current. This procedure may be conducted using non-recording
digital voltage measuring instruments. All of the following apply:
(a) Examine the voltage recordings and locate
the highest steady state value of animal contact voltage (AcV) which will be
called the animal contact test voltage (AcVt).
(b) Determine the steady state value of
utility primary distribution system neutral voltage (NpEV) that was present at
the time the animal contact test voltage occurred. This will be called the
primary neutral-to-earth test voltage (NpEVt).
(c) Install 1 voltage instrument to measure
the voltage of the utility primary distribution system neutral to the reference
ground (NpEV) and another voltage instrument to measure the animal contact
voltage (AcV) with a nominal 500-ohm shunt resistor (R shunt) placed across the
input leads of the voltage measuring instrument.
(d) Turn off all farm electrical loads while
leaving the transformer energized and leaving the secondary neutral conductor
connected to the farm electrical system. This can be accomplished by opening
the main farm electrical disconnect and removing the electric meter, or by some
other effective means.
(e) Add a
temporary load to the transformer (that does not utilize the secondary neutral)
until the primary neutral to reference ground test voltage (NpEVt) is achieved,
and record the animal contact voltage that occurs. This measurement will be
called the utility contribution to animal contact voltage (AcVu).
(f) If the primary neutral to reference test
voltage (NpEVt) cannot be achieved as described in subrule 3(e) of this rule,
then the utility contribution to the animal contact voltage (AcVu) will be
determined by using the linear relationship between the primary neutral to
reference voltage
(NpEV) and the animal contact voltage (AcV) with and without
the temporary load applied to the transformer where the following apply:
(i) AcVo means the animal contact voltage
measured with all farm electrical loads turned off as determined in (d) of this
subrule.
(ii) AcVtemp means the
animal contact test voltage as determined in subdivision (e) of this subrule at
the level of temporary load applied.
(iii) NpEVo means the primary
neutral-to-earth voltage with all farm electrical loads off as determined in
(d) of this subrule.
(iv) NpEVt
means the primary neutral-to-earth voltage as determined in subdivision (b) of
this subrule.
(v) NpEVtemp means
the primary neutral-to-earth voltage as determined in subdivision (e) at the
level of temporary load applied.
(g) If paragraphs (i) to (v) of subdivision
(f) of this rule apply, then the utility contribution to animal contact voltage
(AcVu) shall be scaled by multiplying the change in animal contact voltage
(AcV) resulting from the temporary load at the utility's transformer (AcVtemp -
AcVo) by the ratio of (NpEVt - NpEVo) divided by (NpEVtemp - NpEVo). The
resulting scaling in animal contact voltage shall be added to the animal
contact voltage (AcVo) to determine the utility contribution to animal contact
voltage (AcVu) as follows:
(i) AcVu =
{[(NpEVt - NpEVo) / (NpEVtemp - NpEVo)] x (AcVtemp - AcVo)} +
AcVo.
(h) Animal contact current contributed by the
utility system (AcCu) is determined by using Ohm's law. To determine the
current contributed by the utility, divide the utility contribution to animal
contact voltage (AcVu) by the value of shunt resistance or R shunt. The formula
for determining AcCu is AcCu amps = AcVu volts / R shunt
ohms.